Plan Review Details - Permit 14120094
Plan Review Stops For Permit 14120094
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-10-17 Cont ID  
Sent By skennedy Date 2015-10-17 Time 18:26 Rev Time 0.00
Received By skennedy Date 2015-10-17 Time 18:26 Sent To  
Notes
2015-10-17 18:26:464TH REVIEW: FBC 2010
  
 SEE ZONING NOTES. THE ACCESSORY BUILDING CANNOT BE A
 SEPARATE DWELLING. THERE APPEARS TO BE TWO ELECTRICAL
 SERVICES AT THIS ADDRESS AND THE ACCESSORY BUILDING IS
 PROVIDED WITH A 200AMP PANEL. THERE SHOULD BE ONE
 SERVICE AND THE ACCESSORY BULDING FEDFROM THE HOUSE.
 THE PLAN STATES TO PROVIDE A KITCHEN THIS CANNOT BE
 PLEASE REVISE AS NEEDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-20 Cont ID  
Sent By skennedy Date 2015-04-20 Time 14:20 Rev Time 0.00
Received By skennedy Date 2015-04-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:57 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-02-15 10:57:232ND REVIEW: FBC 2010
  
 THE RE-SUBMITTED SETS ARE NOT PROVIDED IN DUPLICATE
 SET. PLEASE MAKE AN APPOINTMENT WITH ME TO RE-SUBMIT OR
 DO SO PROPERLY NEXT TIME.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 12:27 Rev Time 0.00
Received By skennedy Date 2014-12-28 Time 12:27 Sent To  
Notes
2014-12-28 12:48:531ST REVIEW: FBC 2010
  
 THE OVERALL SCOPE OF WORK AND WHAT IS PROPOSED AS NEW
 IS UNCLEAR. ACCORDINGLY THE VALUATION IS NOT PRESUMED
 TO BE ACCURATE. PROVIDE A SCOPE OF WORK AND A COST
 BREAKDOW IF THAT MAY BE HELPFUL. ADDITIONALLY, IT IS
 UNCLEAR WHO THE MECHANICAL DESIGNER OF RECORD IS AND IF
 THE DUCT SYSTEM, HAND DRAWN, ON SHEET A-1 IS NEW OR
 EXISTING. IS THE ROOF COVERING TO BE REPLACED? IS THERE
 AN ADDITION PROPOSED? PLAN INDICATES 1,152 SF RECORSD
 SHOW EXISTING TOTAL UNDER AIR IS 720 SF. PLEASE PROVIDE
 A SITE PLAN OR SURVEY.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (MECHANICAL PLAN)
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 ADDITIONALLY, IT SEEMS YOU ARE REPLACING SOME WINDOWS.
 THE PRODUCT APPROVAL SUBMITTED HAS AN "OREIAL " & AN
 "EQUAL SPLIT" OPTION, WHICH IS PROPOSED. NO PRODUCT WAS
 SUBMITTED FOR THE MULLIONS. ADDITIONALLY,
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING,(IF APPLIABLE) & WINDOW
 MULLION.
  
 THE ENERGY SUBMITTAL WILL BE EVALUATED UPON
 RESUBMITTAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-10-17 Cont ID  
Sent By skennedy Date 2015-10-17 Time 18:22 Rev Time 0.00
Received By skennedy Date 2015-10-17 Time 18:22 Sent To  
Notes
2015-10-17 18:26:284TH REVIEW: FBC 2010
  
 SEE ZONING NOTES. THE ACCESSORY BUILDING CANNOT BE A
 SEPARATE DWELLING. THERE APPEARS TO BE TWO ELECTRICAL
 SERVICES AT THIS ADDRESS AND THE ACCESSORY BUILDING IS
 PROVIDED WITH A 200AMP PANEL. THERE SHOULD BE ONE
 SERVICE AND THE ACCESSORY BULDING FEDFROM THE HOUSE.
 THE PLAN STATES TO PROVIDE A KITCHEN THIS CANNOT BE
 PLEASE REVISE AS NEEDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-04-20 Cont ID  
Sent By skennedy Date 2015-04-20 Time 14:20 Rev Time 0.00
Received By skennedy Date 2015-04-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:54 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-02-15 10:54:25SEE NOTES UNDER BUILDING

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 13:05 Rev Time 0.00
Received By skennedy Date 2014-12-28 Time 13:05 Sent To  
Notes
2014-12-28 13:15:451ST REVIEW: FBC 2010
  
 THE PLAN IS UNCLEAR AS TO THE EXTENT OF THE PROPOSED
 ELECTRICAL WORK. IS THE SERVICE NEW? THE PANEL SCHEDULE
 IS INCONSISTENT WITH THE MECHANICAL EQUIPMENT SPECIFIED
 IN THE ENERGY SUBMITTAL AS TO BREAKER SIZE AND HEAT
 STRIP KW. THERE IS NO INDICATION OF A LUMINARE IN THE
 ATTIC FOR THE AHU, SEE MECHANICAL COMMENTS.
  
 THE PLAN DOES NOT HAVE ADEQUATE DETAIL TO DETERMINE
 COMPLIANCE WITH THE FOLLOWING SECTIONS:
  
 FBC- 107.3.5.3 ? SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
 NEC 210.63 - GFI SERVICE OUTLET FOR WITHIN 25? OF
 MECHANICAL EQUIPMENT.
 NEC 406.11- TAMPER RESISTANT RECEPTACLES.
  
 ADDITIONALLY, THERE ARE NO DISCONNECTS SHOWN FOR
 MECHANICAL EQUIPMENT OR WH AND NO WATER HEATER LOCATION
 SHOWN.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
2014-12-03 13:39:52INADVERTANT PUNCH BY FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-21 Time 09:40 Rev Time 0.00
Received By skennedy Date 2015-06-18 Time 10:29 Sent To  
Notes
2015-06-18 15:41:46SENT TO S. KENNEDYS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-04-20 Time 14:27 Rev Time 0.00
Received By skennedy Date 2015-03-03 Time 18:41 Sent To  
Notes
2015-03-03 18:41:33SENT TO S KENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:57 Rev Time 0.00
Received By skennedy Date 2015-02-03 Time 11:24 Sent To B
Notes
2015-02-05 11:24:58TO S. KENNEDY'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 13:21 Rev Time  
Received By skennedy Date 2014-12-02 Time   Sent To  
Notes
2014-12-03 06:43:58INCOMING SENT TO R21.(FRONT UNIT).

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-06-24 Cont ID  
Sent By skennedy Date 2015-06-24 Time 10:28 Rev Time 0.00
Received By skennedy Date 2015-06-24 Time 10:28 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 12:50 Rev Time 0.00
Received By skennedy Date 2014-12-28 Time 12:50 Sent To  
Notes
2014-12-28 12:52:101ST REVIEW: FBC 2010
  
 IT APPEARS AN ADDITION IS PROPOSED? IF SO, SEE BELOW.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 14:26 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 14:26 Sent To  
Notes
2015-04-20 14:22:503RD REVIEW
  
 CHECKED OUT MID CYCLE TO UPDATE MECHANICAL EQUIPMENT
 SCHEDULE.
  
 STEVEN KENNEDY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:53 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-02-15 10:53:58SEE NOTES UNDER BUILDING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 12:52 Rev Time 0.00
Received By skennedy Date 2014-12-28 Time 12:52 Sent To  
Notes
2014-12-28 13:00:251ST REVIEW: FBC 2010
  
 WHO IS THE MECHANICAL DESIGNER OF RECORD? IS THE
 EQUIPMENT SCHEDULE ATTTACHED TO THE ENERGY SUBMITTAL
 SPECIFIED BY A DESIGNE? IT SHHOULD BE SIGNED OR
 INCORPORATED INTO THE PLAN.
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 THE PLAN LACKS DETAIL TO DEMONSTRATE COMPLICANCE WITH
 THE SECTIONS BELOW:
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-04-20 Cont ID  
Sent By skennedy Date 2015-04-20 Time 14:20 Rev Time 0.00
Received By skennedy Date 2015-04-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:54 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-02-15 10:55:03SEE NOTE UNDER BUILDING

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-06 Time 09:22 Rev Time 0.00
Received By tklarge Date 2014-12-06 Time 09:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-04-20 Cont ID  
Sent By skennedy Date 2015-04-20 Time 14:20 Rev Time 0.00
Received By skennedy Date 2015-04-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 13:01 Rev Time 0.00
Received By skennedy Date 2014-12-28 Time 13:01 Sent To  
Notes
2014-12-28 13:02:351ST REVIEW: FBC 2010
  
 IS ROOFING WORK PROPOSED? SEE BUILDING REVIEW COMMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2015-10-19 Cont ID  
Sent By   Date 2015-10-19 Time   Rev Time 0.00
Received By   Date 2015-10-19 Time   Sent To B
Notes
2015-10-19 14:43:5610/19/15 ZONING FAILED
  
 1. THE PLANS ARE STILL SHOWING A RANGE IN THE ELECTRIC
 CALCULATIONS, THE GARAGE CAN NOT HAVE A KITCHEN OR CAN
 IT BE RENT. THIS BUILDING CAN NOT HAVE A SEPARATE METER
 FROM THE MAIN HOUSE.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-07-08 Cont ID  
Sent By sgraham Date 2015-07-08 Time 15:01 Rev Time 0.00
Received By sgraham Date 2015-07-08 Time 15:01 Sent To  
Notes
2015-07-08 15:03:307/8/15 ZONING FAILED
  
 1. THE ZONING FOR THIS DISTRICT IS SF7 (ONE FAMILY
 ONLY), THE GARAGE CAN NOT HAVE A KITCHEN NOR CAN IT BE
 RENTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-05 Cont ID  
Sent By sgraham Date 2014-12-05 Time 08:47 Rev Time 0.00
Received By sgraham Date 2014-12-05 Time 08:47 Sent To  
Notes
***NONE***