Plan Review Details - Permit 14120093
Plan Review Stops For Permit 14120093
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-12-30 Cont ID  
Sent By jwitmer Date 2015-12-30 Time 15:10 Rev Time 0.00
Received By jwitmer Date 2015-12-30 Time 11:02 Sent To  
Notes
2015-12-30 15:10:07BUILDING PLAN REVIEW
 PERMIT: 14120093
 ADD: 809 6TH ST.
 CONT: MIJO CONSTRUCTION
 TEL: (561)246-0411
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. DEC. 30/2015
 ACTION: DENIED
  
 1) COVER SHEET:
 1A-D) COMPLIED.
  
 1E) 3RD REQUEST. PLEASE REVIEW 2010 FBC-B 903.2.8 AN
 AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH
 903.3 SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A
 GROUP R FIRE AREA.
 SEE 2010 FBC-B 903.3.1.2 NFPA 13 R SPRINKLER SYSTEMS.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA COMMERCIAL BUILDING.
 .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 2) COMPLIED.
  
 3) 3RD REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.8 MINIMUM
 PLAN REVIEW CRITERIA COMMERCIAL BUILDING.
 .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS PROVIDE THE WIND DESIGN CRITERIA,
 BUILDING ENVELOPE/ PRODUCT APPROVALS
  
 STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG.
 CODE LEVEL III 807.4. 1 THRU 3. LIVE LOADS FBC-B TABLE
 1607.1.
 FLOOR SYSTEMS PROVIDE FLOOR LOADING
 STAIR SYSTEMS
 HANDRAILS
  
 4) COMPLIED.
 5) 3RD REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.11.
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) SEE
 2010 FBC-B TABLE 803.9.
  
  
 6) FL. ENERGY CODE:
 6A) COMPLIED.
  
 6B)(1) SHEET D-1 THE 1ST FLOOR IS MISSING FLOOR
 INSULATION UNDER THE FIRST FLOOR. 2010 FBC-ENERGY CODE
 402.4.1, 402.2.6 .
  
 6B)(2) A) 3RD REQUEST. FBC-B 2010 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 B)3RD REQUEST. FBC-B 2010 1207.2 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) 3RD REQUEST. FLAME SPREAD- FBC-B 2010 603.1.2
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
  
  
 6)(3) COMPLIED.
  
 6C) 3RD REQUEST. SHEET D-1 COMMON WALL DETAIL INDICATES
 CODE COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE
 SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE.
  
 6D) 3RD REQUEST. SHEET D-1 TENANT WALL/ FLOOR DETAIL
 INDICATES THE USE OF 3 INCH ATTEN. BATT R-30 BATT
 INSULATION, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6E-F) COMPLIED.
  
 7-12) COMPLIED.
  
 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND
 FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING& TENANT
 WALL SEPARATION WILL BE MADE CODE COMPLIANT WITH FBC-B
 709.4 OR EXCEPTIONS.
  
 14)COMPLIED. ROOF: FIBERGLASS SHINGLES.
  
 15) DEFERRED SUBMITTAL: PLEASE PROVIDE THE PRODUCT
 APPROVAL ON ICYNENE, WITHIN THE ICC REPORT CIRCLE WHICH
 SUB-SYSTEM YOU INTEND ON USING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. PLEASE ALSO SEE 2010 FBC-B
 2603.4.1.6 IGNITION BARRIER REQUIREMENT, DIFFERENT FROM
 THE THERMAL BARRIER REQUIREMENTS.
  
 16) 3RD REQUEST. SHEET D-1 INTERIOR FINISHES, WITH THE
 DESIGNER NOT LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE
 COMPLIANCE WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE
 SPRINKLERED OR NOT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.11.
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) SEE
 2010 FBC-B TABLE 803.9.
  
 17) 3RD REQUEST. 2010 EXISTING BUILDING CODE, LEVEL III
 ALTERATION PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED
 IN ALL WORK AREAS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. THE FIRE SPRINKLER PLANS NEED
 TO BE SUBMITTED PROVIDE THE HYDRAULIC CALCS FOR THE
 FIRE SPRINKLERS AND A SCHEMATIC LAYOUT. THE FIRE
 SPRINKLER SHOP DRAWINGS WILL BE SUBMITTED UNDER
 SEPARATE PERMIT.
  
 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA.
  
 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS.
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH
 903.3.6.
  
 18) COMPLIED. SHEET A3 PRESSURES FOR WINDOWS AND DOORS.
  
 19) COMPLIED. EGRESS WINDOWS.
  
 20-22) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
  
 21)COMPLIED. ROOFING EXISTING NOT REPLACING
  
 22) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By jwitmer Date 2015-06-23 Time 06:51 Rev Time 0.00
Received By jwitmer Date 2015-06-22 Time 13:46 Sent To  
Notes
2015-06-23 06:51:05BUILDING PLAN REVIEW
 PERMIT: 14120093
 ADD: 809 6TH ST.
 CONT: MIJO CONSTRUCTION
 TEL: (561)246-0411
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON- TUES. JUNE 22-23/2015
 ACTION: DENIED
  
 1) COVER SHEET:
 1A) SEMI- COMPLIED. THE COVERSHEET UNDER THE HEADING
 BUILDING CODE ANALYSIS OCCUPANCY CLASSIFICATION AS A
 BUSINESS OCCUPANCY, R2 PER CHAPTER 3, SECTION
 304.1.THIS WILL CREATE A MIXED USE OCCUPANCY, WHERE IS
 THE BUSINESS OCCUPANCY? SECTION 304.1 DOES PROVIDE A
 LIST OF SERVICES THAT ARE BUSINESS OCCUPANCIES WHICH
 NONE ARE REPRESENTED ON THIS PLAN?
  
 THE CODE TABULATION NEEDS TO BE CLARIFIED. THE DESIGNER
 OF RECORD WILL NEED TO CLARIFY IF THE 1ST FLOOR HAS (5)
 INDIVIDUAL SLEEPING ROOMS OR THIS IS A SINGLE DWELLING
 UNIT. PROVIDE A BREAKDOWN OF SLEEPING UNITS AND
 DWELLING UNITS. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.
 3.5.1.2 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING.
  
  
 1B) SEMI-COMPLIED. THE COVERSHEET WILL NEED TO PROVIDE
 IF TRANSIENT OR NON-TRANSIENT, THIS WILL AFFECT IF
 ACCESSIBILITY BECOMES AN ISSUE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.2 MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDING. 2010 FBC-B 310.1.
  
 1C) COMPLIED. MINIMUM BUILDING TYPE.
  
 1D)SEMI-COMPLIED. UNKNOWN IF THE 1ST FLOOR IS (5)
 INDIVIDUAL SLEEPING ROOMS REQUIRING 1 HOUR FIRE
 SEPARATION BETWEEN THEM OR A SINGLE DWELLING UNIT FOR A
 FAMILY.
  
 1ST REVIEW COMMENT. THE COVERSHEET ALSO FAILS TO
 IDENTIFY (DESIGN CRITERIA) 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.4 MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDING.
 .4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS PROVIDE ACTUAL UL LISTINGS
 OR GYPSUM ASSOC. LISTINGS, VERIFY ICYENE IS PART OF THE
 RATED FLOOR/ CEILING ASSEMBLY
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 1E) THE RESPONSE STATEMENT STATES NO FIRE SPRINKLERS
 REQUIRED. COVERSHEET PROJECT DATA NOTE 2010 FBC-B
 907.2.9.1 FIRE SPRINKLERS NOT REQUIRED IN A R-2
 DWELLING UNIT LESS THAN 2 STORIES. NOTE 907.2.9.1 DEALS
 WITH FIRE ALARMS NOT FIRE SPRINKLERS. PLEASE REVIEW
 2010 FBC-B 903.2.8 AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 903.3 SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS WITH A GROUP R FIRE AREA.
 SEE 2010 FBC-B 903.3.1.2 NFPA 13 R SPRINKLER SYSTEMS.
  
 1ST REVIEW COMMENT. THE COVERSHEET ALSO FAILS TO
 IDENTIFY (DESIGN CRITERIA) IF THIS OCCUPANCY IS FIRE
 SPRINKLERED OR NOT? 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107. 3.5.1.1 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING.
 .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 2) 2ND REQUEST, THE LIFE SAFETY SHEET STILL SHOWS 4
 UNITS. SHEETS A1 & A2 FAILS TO IDENTIFY (DESIGN
 CRITERIA) EGRESS COMPONENTS, 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.7 MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDING.
 . 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE
 IN A LIFE SAFETY PLAN:
 OCCUPANCY LOAD FOUND ON THE COVERSHEET, THEY NEED TO BE
 ROUNDED UP TO THE NEXT WHOLE OCCUPANTS.
  
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 3) 2ND REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.8 MINIMUM
 PLAN REVIEW CRITERIA COMMERCIAL BUILDING.
 .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS PROVIDE THE WIND DESIGN CRITERIA,
 BUILDING ENVELOPE/ PRODUCT APPROVALS
  
 STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG
 CODE LEVEL III 807.4. 1 THRU 3.
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 STAIR SYSTEMS & HANDRAILS
  
 4)SEMI ?COMPLIED. DEPENDING IF THE 1ST FLOOR IS
 TRANSIENT SLEEPING ROOMS THEN ACCESSIBILITY WILL NEED
 TO BE REVIEWED.
 SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.10
 WHEN THIS STRUCTURE WAS BUILT, IF FAIR HOUSING AND OR
 FL. ACCESSIBILITY APPLY AND ALL APPLICABLE CODE
 SECTIONS.
  
 5) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.11
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
  
 6) FL. ENERGY CODE:
 6A) SEMI- COMPLIED.ENERGY CALCULATIONS FOR UNITS 1 & 2
 NONE FOR UNIT 3.
  
 6B)(1) PROVIDE THE MANUFACTURES SPECIFICATIONS AND
 REPORT FOR THE USE OF ICYENE. SHEET D-1 THE 2 STORY
 EXTERIOR WALL DETAIL IS MISSING THE FLOOR INSULATION
 UNDER THE FIRST FLOOR. 2010 FBC-ENERGY CODE 402.4.1,
 402.2.6 .
  
 6B)(2)
 A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
  
  
 6)(3) THE ENERGY CALCULATION TAKES THIS STRUCTURE AS A
 SLAB ON GRADE, PLEASE CORRECT. 2010 FBC-ENERGY CODE
 402.4.1 & 402.2.6.
  
 6C) SHEET D-1 COMMON WALL DETAIL INDICATES CODE
 COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE
 SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE.
  
 6D) SHEET D-1 TENANT WALL/ FLOOR DETAIL INDICATES THE
 USE OF 3 INCH ATTEN. BATT R-30 BATT INSULATION, PLEASE
 PROVIDE COMPLIANCE WITH FBC-B 1207.3 STRUCTURE-BORNE
 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6E) THE ENERGY CALCULATIONS INDICATE A SHGC OF 0.5
 PLEASE PROVIDE DOCUMENTATION, FL ENERGY CODE TABLE
 402.1.1 GLAZED FENESTRATION 0.30.
  
 6F) NOTE SHEET A2 DOES NOT SHOW ATTIC ACCESS NOR
 COMPLIANCE WITH:
 2010 FBC-B 1209.2 ATTIC ACCESS.
 7) COMPLIED.
  
 8) COMPLIED. SHEET A1 STAIR # 3 ONLY SHOWS ONE SIDE OF
 THE STAIRWELL WITH A FIRE RATED WALL. FBC-B 1022.1
  
 9) SHEET A1 STAIR # 3 IS MISSING THE CEILING
 INFORMATION BELOW THE STAIR AND ENCLOSURES UNDER
 STAIRWAYS ARE TO COMPLY WITH FBC-B 1009.6.3.
  
 10) SHEET A1 STAIR # 3 ALSO DOES NOT INDICATE FIRE
 BLOCKING.
  
 11) SHEET D1 DETAIL FOR THE TENANT SEPARATION WALL
 SHOWS THE HORIZONTAL SEPARATION BETWEEN THE 1ST FLOOR
 UNITS & 2ND FLOOR UNITS THE EXTERIOR WALL DETAIL SHOWS
 A 2 LAYERS OF 5/8 TYPE X ON THE CEILING. PROVIDE EITHER
 A UL LISTING OR GYPSUM ASSOC . LISTING FOR THE FLOOR
 CEILING ASSEMBLY 2 HOURS WITH THE USE OF ICYENE
 INSULATION.
  
 WHAT BOTH DETAILS FAIL TO PROVIDE IS THROUGH THE
 CAVITIES IN THE FLOOR TRUSSES HOW THE FIRE PARTITION
 BETWEEN THE UPSTAIRS UNITS 2 & 3 OCCURS IN THE FLOOR
 TRUSS, TRUSS SYSTEM. 439.2 SEE SECTION 709.4
 CONTINUITY. IF THE PARTITIONS ARE NOT CONTINUOUS TO THE
 SHEATHING, DECK OR SLAB, AND WHERE CONSTRUCTED OF
 COMBUSTIBLE CONSTRUCTION, THE SPACE BETWEEN THE CEILING
 AND THE SHEATHING, DECK OR SLAB ABOVE SHALL BE
 FIREBLOCKED OR DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS
 717.2 AND 717.3 AT THE PARTITION LINE.
  
 12A) SHOW COMPLIANCE WITH 709.4 FIRE PARTITIONS EXTEND
 FROM THE TOP OF FOUNDATIONS THEN THERE SHOULD BE A
 SECTION THROUGH THE 1ST FLOOR SHOWING THE STEM WALL &
 FOOTER UNDER THE TENANT SEPARATION WALL. 2010 FBC-B
 709.4.
  
 12B) STEM WALL CONSTRUCTION THEN IN ONE OF THE TENANT
 SPACES A NEW ACCESS WILL ALSO BE REQUIRED TO THE SPACE
 BENEATH THE FLOOR SYSTEM.1203.3.
  
 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND
 FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING WILL BE
 MADE CODE COMPLIANT WITH FBC-B 709.4 OR EXCEPTIONS.
  
 14)COMPLIED. ROOF: FIBERGLASS SHINGLES.
  
 15) SEMI-COMPLIED RESPONSE INDICATES THE ATTIC IS TO BE
 ENCLOSED AND SPRAYED WITH ICYNENE INSULATION.
 PLEASE PROVIDE THE PRODUCT APPROVAL ON ICYNENE, WITHIN
 THE ICC REPORT CIRCLE WHICH SUB-SYSTEM YOU ENTEND ON
 USING IN ACCORDANCE WITH THE MANUFACTURERS
 INSTRUCTIONS. PLEASE ALSO SEE 2010 FBC-B 2603.4.1.6
 IGNITION BARRIER REQUIREMENT, DIFFERENT FROM THE
 THERMAL BARRIER REQUIREMENTS.
  
 16) 2ND REQUEST. SHEET D-1 INTERIOR FINISHES, WITH THE
 DESIGNER NOT LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE
 COMPLIANCE WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE
 SPRINKLERED OR NOT.
  
 17) 2ND REQUEST. 2010 EXISTING BUILDING CODE, LEVEL III
 ALTERATION PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED
 IN ALL WORK AREAS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA.
  
 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS.
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH
 903.3.6.
  
 18) COMPLIED. SHEET A3 PRESSURES FOR WINDOWS AND DOORS.
  
 19) COMPLIED. EGRESS WINDOWS.
  
 20-22) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
  
 21)COMPLIED. ROOFING EXISTING NOT REPLACING
  
 22) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-08 Cont ID  
Sent By jwitmer Date 2014-12-08 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2014-12-08 Time 06:29 Sent To  
Notes
2014-12-08 10:15:46BUILDING PLAN REVIEW
 PERMIT: 14120093
 ADD: 809 6TH ST.
 CONT: MIJO CONSTRUCTION
 TEL: (561)246-0411
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 08/2014
 ACTION: DENIED
  
 1) COVER SHEET:
 1A) THE DESIGNER OF RECORD FAILS TO IDENTIFY WHICH
 CODES THESE PLANS WERE DESIGNED UNDER(DESIGN CRITERIA)
 AND TO WHAT LEVEL THIS BUILDING IS BEING ALTERED? OR A
 CHANGE OF OCCUPANCY? 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107. 3.5.1.1 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING.
  
 1B) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN
 CRITERIA) THE OCCUPANCY TYPE AND IF TRANSIENT OR
 NON-TRANSIENT. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.
 3.5.1.2 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING. 2010 FBC-B 310.1.
  
 1C) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN
 CRITERIA) THE MINIMUM BUILDING TYPE THIS STRUCTURE CAN
 BE DESIGNED TO? 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.
 3.5.1.3 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING MINIMUM CONSTRUCTION TYPE.
  
 1D) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN
 CRITERIA) 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.
 3.5.1.4 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING.
 .4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 1E) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN
 CRITERIA) IF THIS OCCUPANCY IS FIRE SPRINKLERED OR NOT?
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA COMMERCIAL BUILDING.
 .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 2) SHEETS A1 & A2 FAILS TO IDENTIFY (DESIGN CRITERIA)
 EGRESS COMPONENTS, 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107. 3.5.1.7 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL
 BUILDING.
 . 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE
 IN A LIFE SAFETY PLAN:
 OCCUPANCY LOAD
 GROSS
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
  
 3) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.8 MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDING.
 .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG
 CODE LEVEL III 807.4. 1 THRU 3.
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 STAIR SYSTEMS & HANDRAILS
  
 4) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.10
 WHEN THIS STRUCTURE WAS BUILT, IF FAIR HOUSING AND OR
 FL. ACCESSIBILITY APPLY AND ALL APPLICABLE CODE
 SECTIONS.
  
 5) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.11
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
 TOTAL SQ. FT. PER SLEEPING ROOM & SQ. FT. PER KITCHEN &
 LIVING RM.
  
 6) FL. ENERGY CODE:
 6A) THERE ARE 4 DWELLING UNITS IN THIS BUILDING, UNITS
 1-4, ONLY CALCULATIONS FOR UNIT # 2 WERE SUBMITTED.
 PLEASE SUBMIT ENERGY CALCULATIONS FOR ALL UNITS.
  
 6B)(1) SHEET D-1 THE 2 STORY EXTERIOR WALL DETAIL IS
 MISSING THE FLOOR INSULATION UNDER THE FIRST FLOOR.
 2010 FBC-ENERGY CODE 402.4.1 & 402.2.6.
  
 6B)(2) THE SHEET A2, A3 OR D1 INDICATE THE USE OF FLOOR
 INSULATION UNDER THE FLOOR OF BEDROOM # 2 IN UNIT # 3.
 2010 FBC-ENERGY CODE 402.4.1 & 402.2.6.
  
 6)(3) THE ENERGY CALCULATION TAKES THIS STRUCTURE AS A
 SLAB ON GRADE, PLEASE CORRECT. 2010 FBC-ENERGY CODE
 402.4.1 & 402.2.6.
  
 6C) SHEET D-1 COMMON WALL DETAIL INDICATES CODE
 COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE
 SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE.
  
 6D) SHEET D-1 TENANT WALL/ FLOOR DETAIL INDICATES THE
 USE OF 3 INCH ATTEN. BATT R-30 BATT INSULATION, PLEASE
 PROVIDE COMPLIANCE WITH FBC-B 1207.3 STRUCTURE-BORNE
 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6E) THE ENERGY CALCULATIONS INDICATE A SHGC OF 0.5
 PLEASE PROVIDE DOCUMENTATION, FL ENERGY CODE TABLE
 402.1.1 GLAZED FENESTRATION 0.30.
  
 6F) NOTE SHEET A2 DOES NOT SHOW ATTIC ACCESS NOR
 COMPLIANCE WITH:
 2010 FBC-B 1209.2 ATTIC ACCESS.
 2010 FBC-ENERGY 402.2.3.
  
 7) SHEET A1 STAIR TO UNIT # 3 ON THE SECOND FLOOR, IT
 APPEARS THIS UNIT IS MISSING A FRONT DOOR TO THE UNIT,
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1. 7.
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:DOORS.
  
 8) SHEET A1 STAIR # 3 ONLY SHOWS ONE SIDE OF THE
 STAIRWELL WITH A FIRE RATED WALL. FBC-B 1022.1
  
 9) SHEET A1 STAIR # 3 IS MISSING THE CEILING
 INFORMATION BELOW THE STAIR AND ENCLOSURES UNDER
 STAIRWAYS ARE TO COMPLY WITH FBC-B 1009.6.3.
  
 10) SHEET A1 STAIR # 3 ALSO DOES NOT INDICATE FIRE
 BLOCKING.
  
 11) SHEET SHEET D1 DETAIL FOR THE TENANT SEPARATION
 WALL SHOWS THE HORIZONTAL SEPARATION BETWEEN THE 1ST
 FLOOR UNITS & 2ND FLOOR UNITS THE EXTERIOR WALL DETAIL
 SHOWS A 2 LAYERS OF 5/8 TYPE X ON THE CEILING. WHAT
 BOTH DETAILS FAIL TO PROVIDE IS THROUGH THE CAVITIES IN
 THE FLOOR TRUSSES HOW THE FIRE PARTITION BETWEEN THE
 UPSTAIRS UNITS 3 & 4 OCCURRS IN THE FLOOR TRUSS, TRUSS
 SYSTEM. 439.2 SEE SECTION 709.4 CONTINUITY. IF THE
 PARTITIONS ARE NOT CONTINUOUS TO THE SHEATHING, DECK OR
 SLAB, AND WHERE CONSTRUCTED OF COMBUSTIBLE
 CONSTRUCTION, THE SPACE BETWEEN THE CEILING AND THE
 SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR
 DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 717.2 AND
 717.3 AT THE PARTITION LINE.
  
 12A) SHEET D1 UPPER RIGHT CORNER OF PLANS INDICATES A
 CMU STEM WALL DETAIL. IF THIS DETAIL IS TO BE USED IN
 SHOWING CODE COMPLIANCE FOR 709.4 FIRE PARTIONS EXTEND
 FROM THE TOP OF FOUNDATIONS THEN THERE SHOULD BE A
 SECTION THROUGH THE 1ST FLOOR SHOWING THE STEMWALL &
 FOOTER UNDER THE TENANT SEPARATION WALL. 2010 FBC-B
 709.4.
  
 12B) IF THIS WILL REQUIRE A NEW STEM WALL CONSTRUCTION
 THEN IN ONE OF THE TENANT SPACES A NEW ACCESS WILL ALSO
 BE REQUIRED TO THE SPACE BENEATH THE FLOOR
 SYSTEM.1203.3.
  
 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND
 FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING WILL BE
 MADE CODE COMPLIANT WITH FBC-B 709.4 OR EXCEPTIONS.
  
 14) THE ENERGY CALCULATIONS , SHEETA2 & D1PLANS
 INDICATE THE USE OF CONCRETE ROOF TILE. IS THERE
 CURRENTLY CONCRETE ROOF TILE ON THE ROOF NOW OR IS
 THERE SHINGLES?
 IF THERE IS PRESENTLY SHINGLES THE ADDITIONAL LOADING
 DUE TO THE ROOF TILE WILL NEED TO BE REVIEWED BY THE
 ENGINEER OF RECORD TO DETERMINE IF THE EXISTING ROOF
 FRAMING SYSTEM WILL ACCEPT THE NEW LOADS WITH OUT ANY
 EXTRA BRACING. 2010 FBC-EXISTING DLDG. CODE 807.4.2
 SUBSTANTIAL STRUCTURAL ALTERATION.
 WHERE MORE THAN 30 PERCENT OF THE TOTAL FLOOR AND ROOF
 AREAS OF THE BUILDING OR STRUCTURE HAVE BEEN OR ARE
 PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN
 A 12-MONTH PERIOD, THE EVALUATION AND ANALYSIS SHALL
 DEMONSTRATE THAT THE ALTERED BUILDING OR STRUCTURE
 COMPLIES WITH THE FLORIDA BUILDING CODE, BUILDING FOR
 WIND LOADING.
  
 15) SHEET D1 EXTERIOR WALL DETAIL SHOWS A SOFFIT BUT
 DOES NOT INDICATE HOW THE ATTIC VENTILATION WILL BE
 COMPLIED WITH, NOTE THERE WILL NOT BE CROSS VENTILATION
 BECAUSE OF THE TENANT SEPARATION WALL OR DRAFTSTOPPING,
 WHICHEVER THE DESIGNER OF RECORD ELECTS TO USE. SEE
 2010 FBC-B A MINIMUM OF 1 INCH (25 MM) OF AIRSPACE
 SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF
 SHEATHING. THE NET FREE VENTILATING AREA SHALL NOT BE
 LESS THAN 1/300 OF THE AREA OF THE SPACE VENTILATED,
 WITH 50 PERCENT OF THE REQUIRED VENTILATING AREA
 PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF
 THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM)
 ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE
 REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 16) SHEET D-1 INTERIOR FINISHES, WITH THE DESIGNER NOT
 LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE COMPLIANCE
 WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE SPRINKLERED
 OR NOT.
  
 17) 2010 EXISTING BUILDING CODE, LEVEL III ALTERATION
 PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER SYSTEMS.
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN ALL
 WORK AREAS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA.
  
 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS.
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH
 903.3.6.
  
 18) SHEET A3 THE COMPONENTS AND CLADDING PRESSURES FOR
 THE WINDWOWS AND DOORS DOES NOT PROVIDE FOR WHAT SQ.
 FT. AREA THESE PRESSURES ARE RATED, 10 SQ. FT. OR 20
 SQ. FT.? BATHROOM WINDOWS ARE NOT 20 SQ. FT IN AREA,
 WHAT THE MEAN ROOF HEIGHT IS AND ADJUSTMENT FACTOR FOR
 THIS MEAN ROOF HEIGHT IS. FBC-B 1609.1.1/ TABLE
 1609.7(2).
  
 19) SHEET A3, PLEASE PROVIDE THE WINDOW SIZES IN INCHES
 NOT 25 SH, PLEASE PROVIDE CODE COMPLIANCE FOR 2010
 FBC-B :
  
 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR EMERGENCY
 ESCAPE AND RESCUE GRADE-FLOOR OPENINGS SHALL BE 5
 SQUARE FEET (0.46 M2).
  
 1029.2.1 MINIMUM DIMENSIONS.
 THE MINIMUM NET CLEAR OPENING HEIGHT DIMENSION SHALL BE
 24 INCHES (610 MM). THE MINIMUM NET CLEAR OPENING WIDTH
 DIMENSION SHALL BE 20 INCHES (508 MM). THE NET CLEAR
 OPENING DIMENSIONS SHALL BE THE RESULT OF NORMAL
 OPERATION OF THE OPENING.
  
 20) SHEET A1 LIST THERE ARE PRODUCT APPROVALS SUBMITTED
 WITH THESE PLANS. NO PRODUCT APPROVALS WERE SUBMITTED.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
  
 21) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 22) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-26 Cont ID  
Sent By rlecky Date 2016-01-26 Time 10:58 Rev Time 0.00
Received By rlecky Date 2016-01-25 Time 15:01 Sent To  
Notes
2016-01-26 11:41:15PROVISO:
  
 THIS BUILDING PLANS EXAMINER INDICATES THIS BUILDING
 REQUIRES A FIRE SPRINKLER SYSTEM. THE ELECTRIAL PLAN
 MUST BE REVISED TO PROVIDE A HOUSE PANEL TO ACCOMADATE
 ANY ELECTRICAL LOADS ASSOCIATED WITH THE FIRE SPRINKLER
 SYSTEM. RL

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By albarran Date 2015-08-25 Time 19:44 Rev Time 0.00
Received By albarran Date 2015-08-25 Time 16:17 Sent To  
Notes
2015-08-25 19:54:10PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THOUGH YOUR PANEL SCHEDULES REFLECTS A WATER HEATER
 IN THE DIRECTORIES AND LOAD CALCS IT IS NOT REFLECTED
 ON THE FLOOR PLANS OF EITHER UNIT.
 2. ALL CEILING LUMINARY OUTLETS SHALL BE LISTED TO
 SUPPORT 50 LBS.
 3. INDICATE THE APPLICABLE SCALE FOR THE DRAWINGS TO BE
 ABLE TO CONFIRM PROPER OUTLET PLACEMENT.
 4. UNIT 2 STAIRWAY IS MISSING THE DUAL CONTROL REQUIRED
 BY NEC 210.70 FOR THE LIGHTING
 5. VERIFY THE LOAD CALCS AS SUBMITTED.
 6. EACH A/C CONDENSING UNIT REQUIRES ITS OWN SERVICE
 GFI RECEPTACLE SERVED FROM ITS RESPECTIVE PANEL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-31 Cont ID  
Sent By albarran Date 2014-12-31 Time 15:57 Rev Time 0.00
Received By dhayes Date 2014-12-31 Time 15:57 Sent To  
Notes
2014-12-31 16:28:4512/31/2014
 PROJECT: 809
 PERMIT#: 14120093
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A COMPLETE ELECTRICAL LOAD CALCULATION FOR
 THE FEEDER FOR A MULTI FAMILY DWELLING. THE OVERHEAD
 SERVICE ENTRANCE CONDUCTORS ARE CURRENTLY INDICATED AS
 2/0 AND AS SUCH ARE ONLY RATED A MAXIMUM OF 175AMPS.
 INDICATE SERVICE ENTRANCE CONDUCTORS APPROVED TO
 SUPPORT THE TOTAL CONNECTED LOAD AS DETERMINED BY LOAD
 CALCULATION. NEC 310.16
  
 2) PROVIDE A GROUNDING ELECTRODE CONDUCTOR SIZED IN
 ACCORDANCE WITH NEC 250.66
  
 3) PROVIDE A COMPLETE PANEL DIRECTORY FOR EACH UNIT'S
 ELECTRICAL PANEL. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 4) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN IN
 ACCORDANCE WITH THE PANEL SCHEDULES. WPB AMENDMENTS FBC
 107.3.2
  
 5) PROVIDE SWITCHING FOR LIGHTING FROM BOTH LANDINGS
 FOR STAIRWAYS. NEC 210.70
  
 6) INDICATE LOACTION FOR THE ELECTRICAL PANELS IN EACH
 OF THE UNITS. WPB AMENDMENTS FBC 107.3.2
  
 7) PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21,
 FBC-R 302.4.2, FBC 713.3.2
  
 8) VERIFY RECEPTACLES SPACING SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET. NEC 210.52(A)(1) THROUGH (A)(3).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2015-11-25 Cont ID  
Sent By pleduc Date 2015-11-25 Time   Rev Time 0.00
Received By pleduc Date 2015-11-25 Time 09:47 Sent To  
Notes
2015-11-25 10:46:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. FIRE SPRINKLER DESIGN SCHEMATIC NOT PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-05 Cont ID  
Sent By pleduc Date 2015-06-05 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time 11:30 Sent To  
Notes
2015-06-05 11:39:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENT:
  
 THE EXITS SIGNS AND EMERGENCY LIGHTS ARE NOT REQUIRED
 IN EACH UNIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-03 Cont ID  
Sent By pleduc Date 2014-12-03 Time   Rev Time 0.00
Received By pleduc Date 2014-12-03 Time 11:54 Sent To  
Notes
2014-12-03 13:31:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE 2A - 10BC MINIMUM FIRE EXTINGUISHERS IS EACH
 UNIT; CERTIFIED AND TAGGED INSPECTED ANNUALLY.
  
 FAC 69A-60.0081 NOTICE IS REQUIRED FOR STRUCTURES WITH
 LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL,
 INDUSTRIAL, OR ANY MULTIUNIT RESIDENTIAL STRUCTURE OF
 THREE UNITS OR MORE WHICH USES HORIZONTAL OR VERTICAL
 LIGHT-FRAME TRUSS-TYPE CONSTRUCTION IN ANY PORTION
 SHALL BE MARKED WITH AN APPROVED SYMBOL. THE APPROVED
 SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO THE LEFT OF
 THE MAIN ENTRY DOOR.

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2015-12-22 Cont ID  
Sent By fmittner Date 2015-12-22 Time 15:29 Rev Time 0.00
Received By fmittner Date 2015-12-22 Time 15:29 Sent To  
Notes
2015-12-22 15:30:29FRONT ELEVATION SHOWS REMOVAL OF DOUBLE WINDOW.
 ORIGINAL OPENIGNS ON FROMT ELEVATIONS AHLL REMAIN THE
 SAME. QUESTIONS, CONTACT FRIEDERIKE MITTNER, CITY
 HSITORIC PRESERVATION PLANNER AT 822-1457.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-06-24 Cont ID  
Sent By fmittner Date 2015-06-24 Time 12:54 Rev Time 0.00
Received By fmittner Date 2015-06-24 Time 12:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By fmittner Date 2014-12-16 Time 10:32 Rev Time 0.00
Received By fmittner Date 2014-12-16 Time 10:32 Sent To  
Notes
2014-12-16 10:34:15REQUIRES COA SUBMITTAL. NO SURROUNDS PERMITTED AROUND
 WINDOWS, NO WINDOW SIZE CHANGES, KEEP ORIGINAL SILLS,
 SHALL RETAIN PORCH OPENINGS/WINDOWS AT FRONT. QUESTIONS
 CONTACT FRIEDERIKE MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-26 Cont ID  
Sent By rlecky Date 2016-01-26 Time 11:41 Rev Time 0.00
Received By rlecky Date 2015-11-23 Time 09:23 Sent To  
Notes
2015-11-24 09:23:41C30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-25 Cont ID  
Sent By albarran Date 2015-08-25 Time 19:54 Rev Time 0.00
Received By albarran Date 2015-06-03 Time 15:53 Sent To  
Notes
2015-08-25 19:57:388/25/15 - FAILED ELECTRICAL REVIEW AS WELL AS OTHER
 TRADES. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL
 DENIED BIN "M". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 16:29 Rev Time  
Received By dhayes Date 2014-12-02 Time   Sent To  
Notes
2014-12-03 06:16:31INCOMING SENT TO C19 .

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-01 Cont ID  
Sent By ccole Date 2015-12-01 Time 13:42 Rev Time 0.00
Received By ccole Date 2015-12-01 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-06-26 Cont ID  
Sent By ccole Date 2015-06-26 Time 10:19 Rev Time 0.00
Received By ccole Date 2015-06-26 Time 10:18 Sent To  
Notes
2015-06-26 11:02:082ND REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-1: THE RETURN AIR GRILLS IN EACH OF THE NEW
 AHU CLOSET DOORS 1ST AND 2ND FLOOR ARE UNDERSIZED PER
 SECTION 601.4 (EXCEPTION 2) FBC-10 MECHANICAL. A
 MINIMUM 24 X 24" FOR THE 3-TON SYSTEM, AND MINIMUM 20 X
 20" GRILLS ARE REQUIRED FOR THE 2-TON SYSTEMS: PLEASE
 CORRECT.
 2) M-1: THE 2ND FLOOR UNITS ARE MISLABELED UNITS #3 &
 #4: REFERENCE THE ARCHITECTURAL AND LIFE SAFETY PLAN
 SHEETS.
 3) M-1: THE FLOOR PLAN LAYOUTS AND ROOM IDENTIFICATIONS
 SHOWN ON THE 2ND FLOOR MECHANICAL PLAN DO NOT MATCH THE
 ARCHITECTURAL AND LIFE SAFETY PLAN LAYOUTS: PLEASE
 REVISE.
 4) M-1: SHOW THE DRYER IN THE 2ND FLOOR NORTH UNIT (SEE
 ARCH. SHEET 2) AND PROVIDE EXHAUST VENTILATION DETAILS
 INCLUDING THE TYPE AND SIZE OF DUCT, DUCT RUN, AND
 TERMINATION LOCATION. CLARIFY IF LAUNDRY WILL BE
 INSTALLED IN THE OTHER TWO UNITS AND PROVIDE DRYER
 EXHAUST DETAILS (IF APPLICABLE).
 5) PLEASE NOTE: ADDITIONAL COMMENTS MAY FOLLWO PENDING
 RE-SUBMITTAL OF CORRECTED PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-31 Cont ID  
Sent By hmoser Date 2014-12-31 Time 10:42 Rev Time 0.00
Received By hmoser Date 2014-12-31 Time 09:53 Sent To  
Notes
2014-12-31 10:42:36PLAN DENIED
  
 1) SHOW SIZE AND LOCATION OF RETURN AIR
 ON THE PLAN PER SECTION 107 FBC 2010
 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN.
 PER SECTION 107 FBC 2010
 3) SHOW TERMINATION OF BATHROOM EXHAUST
 PER SECTION 501.2 EXHAUST DISCHARGE.
 2010 FBC (M)
 4) REFER TO SECTION 602.2.1 MATERIALS WITHIN
 PLENUM'S NO COMBUSTIBLES IN RETURN
 AIR PLENUM INCLUDING DOOR
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-12-01 Cont ID  
Sent By tklarge Date 2015-12-01 Time 09:46 Rev Time 0.00
Received By tklarge Date 2015-12-01 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-30 Cont ID  
Sent By tklarge Date 2015-06-30 Time 07:31 Rev Time 0.00
Received By tklarge Date 2015-06-30 Time 07:04 Sent To  
Notes
2015-08-20 09:52:50MALBERRAN'S DESK
2015-06-30 07:07:01SUBMIT INFORMATION REGARDING WHETHER THE ROOMS ARE FOR
 TRANSIENT OR NON- TRANSIENT LODGING. REFER TO THE
 DEFINITION OF "TRANSIENT LODGING" IN THE 2010
 FBC-ACCESSIBILITY. INDICATE IF THE PROPRIETOR RESIDES
 ONSITE. COMPLY WITH THE BUILDING PLAN REVIEWER COMMENTS
 REGARDING ACCESSIBILITY. IF REQUIRED, ONE OF THE ROOMS
 SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-06 Time 06:13 Rev Time 0.00
Received By tklarge Date 2014-12-06 Time 05:25 Sent To  
Notes
2014-12-06 06:13:091) THE SANITARY RISER SHOWS A LAVATORY IN THE BATHROOM
 BY BEDROOM # 3 IN UNIT # 2 AND ALSO IN UNIT #4 BUT
 THERE IS NO LAVATORY SHOWN ON THE FLOOR PLAN. CLARIFY.
 2) TABLE 403.1 OF THE 2010 FL. PLUMBING CODE REQUIRES 1
 AUTOMATIC CLOTHES WASHER CONNECTION PER 20 DWELLING
 UNITS. SHOW THE LOCATION OF THIS CONNECTION ON THE
 FLOOR PLAN
 3) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAM DO
 NOT CORRELATE WITH THE FLOOR PLAN. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-12-22 Cont ID  
Sent By fmittner Date 2015-12-22 Time 15:29 Rev Time 0.00
Received By fmittner Date 2015-12-22 Time 15:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-24 Cont ID  
Sent By fmittner Date 2015-06-24 Time 12:53 Rev Time 0.00
Received By fmittner Date 2015-06-24 Time 12:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By fmittner Date 2014-12-16 Time 10:34 Rev Time 0.00
Received By fmittner Date 2014-12-16 Time 10:34 Sent To  
Notes
2014-12-16 10:34:53AWAITING DOCUMENTATION THAT THIS IS LEGALLY 4 UNITS.