Plan Review Details - Permit 14120085
Plan Review Stops For Permit 14120085
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-27 Cont ID  
Sent By skennedy Date 2015-01-27 Time 15:59 Rev Time 0.00
Received By skennedy Date 2015-01-27 Time 15:59 Sent To  
Notes
2015-01-27 16:23:08PROVISO:
  
 EVIDENCE OF EXISTING OPENING PROTECTION OR A REVISION
 OR SEPARATE PERMIT IS REQUIRED PER THE FOLLOWING
 SECTION TO PROVIDE:
 FBC - R301.2.1.2 PROTECTION OF OPENINGS.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
 GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE
 DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED
 IMPACT RESISTING STANDARD OR ANSI/DASMA 115.
  
 ADDITIONALLY, THE APPLICANT WAS UNABLE TO PROVIDE A
 PLAN OF BETTER QUALITY AND CLARITY. IN THE EVENT THE
 PLANS ARE INSUFFICIENT FOR THE USE OF THE INSPECTOR,
 THE INSPACTOR MAY REQUIRE ADDITIONAL REVISIONS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By skennedy Date 2014-12-19 Time 15:29 Rev Time 0.00
Received By skennedy Date 2014-12-19 Time 15:28 Sent To  
Notes
2014-12-19 15:54:541ST REVIEW: FBC 2010
  
 THE SUBMITTED PLANS LACK CLARITY AND REQUIRED DETAIL.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 FBC 107- PROVIDE WALL SECTIONS DEMONSTRATING PROPOSED
 MATERIALS AND DIMENSIONS OF THE PROPOSED NEW WALL
 CONFIGURATION.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE A WINDOW SUBMITTAL FOR THE NEW
 WINDOWS.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-27 Cont ID  
Sent By skennedy Date 2015-01-27 Time 16:00 Rev Time 0.00
Received By skennedy Date 2015-01-27 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-01-16 Cont ID  
Sent By skennedy Date 2015-01-16 Time 14:36 Rev Time 0.00
Received By skennedy Date 2015-01-16 Time 14:36 Sent To HIST
Notes
2015-01-16 14:45:152ND REVIEW
 FBC 2010
  
 SEE FIRST REVIEW COMMENTS. THE NEWLY SUBMITTED 24 X 36
 PLAN LACKS IN CLARITY AND DETAIL. APPLICANT STATES ONLY
 A BATHROOM IAND BEDROOM S BEING ADDED. ELECTRICIAN DID
 NOT SIGN HIS DESIGN AND INDICATES THE BATH CIRCUITS IN
 THE PERMIT DESCRIPTION BUT ALSO A NEW FEED FOR A/C
 UNIT. THE ELECTRICAL DESIGN SHOULD SHOW PER FBC-
 107.3.5.3 ? SMOKE DETECTORS PURSUANT TO FBC-R 314.3.1
 AS REQUIRED FOR NEW DWELLINGS. IF A ROOM IS BEING
 CONVERTED TO A BEDROOM THEN: PER NEC 406.11- PROVIDE
 TAMPER RESISTANT RECEPTACLES & PER NEC 210.12B -
 OUTLETS TO BE AFCI PROTECTED IN CONVERTED AREA .
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By skennedy Date 2014-12-19 Time 15:29 Rev Time 0.00
Received By skennedy Date 2014-12-19 Time 15:28 Sent To  
Notes
2014-12-19 16:03:411ST REVIEW: FBC 2010
  
 THE PLANS ARE NOT SUFFICIENT.
  
 SEE BUILDING PLAN REVIEW FOR PLAN QUALITY COMMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-01-22 Cont ID  
Sent By fmittner Date 2015-01-22 Time 16:39 Rev Time 0.00
Received By fmittner Date 2015-01-22 Time 16:39 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By fmittner Date 2014-12-11 Time 16:40 Rev Time 0.00
Received By fmittner Date 2014-12-11 Time 16:40 Sent To B
Notes
2014-12-11 16:40:49REQUIRES WINDOW PRODUCT APPROVALS AND ELEVATIONS/PHOTOS
 TO SEE EXISTING VS PROPOSED. QUESTIONS CONTACT
 FRIEDERIKE MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-27 Cont ID  
Sent By skennedy Date 2015-01-27 Time 16:00 Rev Time 0.00
Received By skennedy Date 2014-12-30 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-19 Cont ID  
Sent By skennedy Date 2014-12-19 Time 16:06 Rev Time  
Received By skennedy Date 2014-12-02 Time   Sent To  
Notes
2014-12-03 06:03:32INCOMING SENT TO R20 .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-01-27 Cont ID  
Sent By skennedy Date 2015-01-27 Time 16:00 Rev Time 0.00
Received By skennedy Date 2015-01-27 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-01-16 Cont ID  
Sent By skennedy Date 2015-01-16 Time 15:11 Rev Time 0.00
Received By skennedy Date 2015-01-16 Time 15:10 Sent To  
Notes
2015-01-16 15:35:332ND REVIEW FBC 2100
  
 SEE THE FIRST REVIEW COMMENTS; APPLICANT STATES THERE
 ARE NO MECHANICAL IMPROVEMENTS, HOWEVER, THE
 RECONFIGURATION OF SPACE TO PROVIDE A NEW BATHROOM &
 BEDROOM. CALLS FOR AN ADDED DUCT AND MEHANICAL
 VENTILATION. PROVIDE A MECHANICAL PLAN TO DEMONSTRATE
 COMPLIANCE WITH:
 FBC 107 - MINIMUM PLAN REVIEW CRITERIA, SHOW DUCT
 SYSTEM, INCLUDE BALANCED AIR RETURNS.
 FBCR- M1507.1 GENERAL.
 WHERE TOILET ROOMS AND BATHROOMS ARE MECHANICALLY
 VENTILATED, THE VENTILATION EQUIPMENT SHALL BE
 INSTALLED IN ACCORDANCE WITH THIS SECTION.
 M1507.2 RECIRCULATION OF AIR.
 EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT
 BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER
 DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS
 SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE OR OTHER
 AREAS INSIDE THE BUILDING.
 M1507.3 VENTILATION RATE.
 VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE
 DETERMINED IN ACCORDANCE WITH TABLE M1507.3.
 TABLE M1507.3
 MINIMUM REQUIRED EXHAUST RATES FOR ONE- AND TWO-FAMILY
 DWELLINGS; BATHROOMS?TOILET ROOMS MECHANICAL EXHAUST
 CAPACITY OF 50 CFM INTERMITTENT OR 20 CFM
 CONTINUOUS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By skennedy Date 2014-12-19 Time 16:05 Rev Time 0.00
Received By skennedy Date 2014-12-19 Time 16:05 Sent To  
Notes
2014-12-19 16:06:391ST REVIEW: FBC 2010
  
 THE PLANS ARE NOT SUFFICIENT.
  
 DESCRIBE THE PROPOSED HVAC IMPROVENTS.
  
 SEE BUILDING PLAN REVIEW FOR PLAN QUALITY COMMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-16 Cont ID  
Sent By tklarge Date 2015-01-16 Time 14:02 Rev Time 0.00
Received By tklarge Date 2015-01-16 Time 14:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By tklarge Date 2014-12-13 Time 05:05 Rev Time 0.00
Received By tklarge Date 2014-12-13 Time 04:51 Sent To  
Notes
2014-12-13 05:05:051) SUBMIT TWO COPIES OF A A SANITARY AND WATER RISER
 FOR REVIEW.WPB AMEND. TO 2010 FBC SEC.107.3.5.3 (11)
 2) SHOW THE INTERIOR DIMENSIONS OF THE NEW BATHROOM AND
 SHOW THE PLUMBING FIXTURE CLEARANCES PER THE 2010 FBC,
 RESIDENTIAL,SEC.P2705.
 3) IS A TUB OR SHOWER BEING INSTALLED IN THE NEW
 BATH?IF IT IS A SHOWER SHOW THE DIMENSIONS (L X W).
 COMPLY W/ FBC, RESIDENTIAL, SEC. P2708.1.
 4) INDICATE ON THE PLANS THE TYPE OF WALL MATERIAL
 BEING INSTALLED IN THE TUB/SHOWER WET AREA. THE
 MATERIAL SHALL COMPLY W/2010 FBCR, SEC.R702.3.8 &
 R702.3.8.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  