Plan Review Details - Permit 14120083
Plan Review Stops For Permit 14120083
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 11:36 Rev Time 0.00
Received By skennedy Date 2015-02-15 Time 11:36 Sent To  
Notes
2015-02-15 11:42:312ND REVIEW: FBC 2010;
  
 THE FOLLOWING ITEMS FROM THE FIRST REVIEW MAY BE
 DEFERED SUBMITTALS:
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 GUARDRAILS AND HANDRAILS TO SHOW COMPLIANCE WITH THE
 LOADS OF TABLE R301.5 AND THE SPECIFICATIONS OF SEC.
 R312 OF 2010 FBC-RESIDENTIAL.
  
 14- PROVIDE COMPLETE ENGINEERING PACKAGE (SIGNED AND
 SEALED) FOR THE EPICORE CONCRETE FLOOR SYSTEM SPECIFIED
 ON THE FRAMING PLANS. PACKAGE TO BE APPROVED BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL. SEC. 107.2.1.3
 CITY AMENDMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By jgomez Date 2014-12-29 Time 18:31 Rev Time 0.00
Received By jgomez Date 2014-12-29 Time 18:30 Sent To  
Notes
2014-12-29 18:32:44NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS, INCLUDING THE ATTIC LIVE LOADS REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL. NOTE: CONSIDER THE
 ATTIC WITH PULL DOWN STAIRS ON MOTHER'S IN LAW
 APARTMENT AND SEE ATTIC ACCESS SPECIFIED FOR THE MAIN
 HOUSE.
  
 3- SPECIFY SIZE AND LOCATION OF ATTIC ACCESS FOR MAIN
 HOUSE. SEC. R807 OF 2010 FBC-RESIDENTIAL.
  
 4- PRECAST LINTEL NOA 01-0209.03 SPECIFIED ON THE
 CAST-CRETE TABLE ON SHEET 5 OF 11 EXPIRED ON 5/21/06
 NOT 5/21/15. REVISE AS REQUIRED. DCA RULE 9N-3.
  
 5- WALL SECTION AT ENTRY PORCH ON SHEET 9 OF 11: REVISE
 THE RISER HEIGHT DIMENSION TO COMPLY WITH SEC. R311.7.4
 OF 2010 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 GUARDRAILS AND HANDRAILS TO SHOW COMPLIANCE WITH THE
 LOADS OF TABLE R301.5 AND THE SPECIFICATIONS OF SEC.
 R312 OF 2010 FBC-RESIDENTIAL.
  
 7- WALL SECTIONS ON SHEET 10 OF 11: E.I.F.S W/ STUCCO
 FINISH NEED TO COMPLY WITH SEC. R703.9.4 AND SEC. R704
 OF 2010 FBC-RESIDENTIAL.
  
 8- WALL SECTIONS ON SHEET 11 OF 11: PROVIDE
 FIREBLOCKING SPECIFICATIONS INCLUDING AREA BETWEEN
 GARAGE AND SECOND FLOOR AS REQUIRED BY SEC. R302.11 OF
 2010 FBC-RESIDENTIAL.
  
 9- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR FOR
 WINDOWS AND DOORS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 (***NOTE: THIS IS ONLY REQUESTED WHEN THE ENERGY
 CALCULATIONS USE OTHER FACTORS OTHER THAN THE DEFAULT
 FACTORS SET FOR DOORS AND WINDOWS).
  
 10- ENERGY CALCULATIONS: A) PROVIDE THE OWNER'S
 INFORMATION. B) REVISE THE PERMIT OFFICE. THIS IS CITY
 OF WEST PALM BEACH NOT PALM BEACH COUNTY. C) REVISE THE
 JURISDICTION NUMBER. D) REVISE THE ROOF TYPE ON PAGE 2
 OF 6 TO MATCH PLANS. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) OVERHEAD GARAGE DOOR SIZE AS SHOWN ON PLANS. NOA
 12-0110.08 SUBMITTED IS FOR 16'-2" WIDE DOORS.
  
 B) ARCHED ENTRY DOORS SIZE AS SHOWN ON PLANS AND
 ELEVATIONS.
  
 C) HARDIE PLANK SIDING SPECIFIED ON PLANS.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS.. NOTE: PROVIDE ONLY THE COVER SHEET
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGNER OF
 RECORD TO WRITE DOWN THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO THE SPECIFIED CONNECTOR.
  
 F) ROOF SHINGLES.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS.
  
 13- CLARIFY WHERE ARE THE OPAQUE FIBERGLASS DOORS
 FL15037.4 SUBMITTED GOING TO BE INSTALLED?. PLANS AND
 ELEVATIONS DON'T SPECIFY ANY FIBER GLASS DOORS. SEC.
 107.2.1 CITY AMENDMENTS.
 ***NOTE: DESIGN PRESSURES OF FL15037.4 DON'T MEET THE
 CALCULATED DESIGN PRESSURES ON SHEET 2 OF 11..
  
 14- PROVIDE COMPLETE ENGINEERING PACKAGE (SIGNED AND
 SEALED) FOR THE EPICORE CONCRETE FLOOR SYSTEM SPECIFIED
 ON THE FRAMING PLANS. PACKAGE TO BE APPROVED BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL. SEC. 107.2.1.3
 CITY AMENDMENTS.
  
 15- PROVIDE ICC EVALUATION REPORT (OR ANY OTHER AGENCY
 APPROVED REPORT) FOR THE CLOSED CELL ICYNENE INSULATION
 SPECIFIED ON PLANS.
  
 16- DESIGNER OF RECORD TO COORDINATE INFORMATION ON
 PLANS WITH INFORMATION GIVEN ON THE ENERGY
 CALCULATIONS. COORDINATE INSULATION VALUES FOR WALLS,
 CEILINGS, ETC. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 17- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATE TO $643,481. THE
 PERMIT FEE BALANCE IS $10,619.79.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 11:36 Rev Time 0.00
Received By skennedy Date 2015-02-15 Time 11:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-05 Cont ID  
Sent By sciard Date 2015-01-05 Time 07:16 Rev Time 0.00
Received By sciard Date 2015-01-05 Time 07:16 Sent To  
Notes
2015-01-05 07:23:081. N.E.C. 210.24(D). OVERCURRENT DEVICES IN CLOTHES
 CLOSET.
 2. AHU #3 O N PANEL SCHEDULE SHOWS 10KW ON MECHANICAL
 PLAN SHOWS 5KW.
 3. SERVICE ENTRANCE AND FEEDER CONDUCTORS FOR 100 AMP
 DISCONNECT AS SHOWN ON PLAN TO 8X8 WIREWAY.
 4. N.E.C. 210.52(C). RECEPTACLE SPACING COUNTERTOP BY 4
 GANG SWITCH IN KITCHEN ON REFRIGERATOR SIDE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 11:38 Rev Time 0.00
Received By skennedy Date 2015-01-28 Time 17:55 Sent To  
Notes
2015-01-28 18:09:04R26
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-05 Cont ID  
Sent By sciard Date 2015-01-05 Time 07:16 Rev Time  
Received By sciard Date 2014-12-02 Time   Sent To  
Notes
2014-12-03 06:48:09INCOMING SENT TO R22 .

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 11:35 Rev Time 0.00
Received By skennedy Date 2015-02-15 Time 11:35 Sent To  
Notes
2015-02-15 11:36:13SEE HOLD BY JG, NEED PAID RECEIPT FROM PBC IMPACT FEE
 OFFICE FOR $29.91.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By jgomez Date 2014-12-29 Time 18:32 Rev Time 0.00
Received By jgomez Date 2014-12-29 Time 18:32 Sent To  
Notes
2014-12-29 18:35:521- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 11:36 Rev Time 0.00
Received By skennedy Date 2015-02-15 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-30 Cont ID  
Sent By jgomez Date 2014-12-30 Time 16:31 Rev Time 0.00
Received By jgomez Date 2014-12-30 Time 12:23 Sent To  
Notes
2014-12-30 16:59:19NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- TRANSFER DUCT SIZE ON MASTER BEDROOM DOESN'T COMPLY
 WITH THE BALANCED RETURN AIR SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. ALL SUPPLY AIR TO THE MASTER BEDROOM
 (INCLUDING BATHROOM AND CLOSETS) NEEDS TO BE CONSIDERED
 FOR THE SIZE OF THE TRANSFER DUCT. SEE EXCEPTION #3 OF
 SEC M1602.4. REVISE AS REQUIRED TO COMPLY.
  
 2- THE CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT
 SHALL NOT BE LESS THAN THE CALCULATED LATENT LOAD. SEC.
 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION. EQUIPMENT
 FOR SYSTEM 1 ON THE EQUIPMENT SIZING CALCULATIONS
 SUBMITTED DON'T COMPLY WITH THIS SECTION.
  
 3- EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS AND EQUIPMENT LISTED ON A/C PLAN M1 DON'T
 MATCH. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-06 Time 09:05 Rev Time 0.00
Received By tklarge Date 2014-12-06 Time 08:41 Sent To  
Notes
2014-12-06 09:06:54****PROVISO****
 SUBMIT A REVISED SANITARY RISER FOR REVIEW PRIOR TO
 ROUGH PLUMBING INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 12:00 Rev Time 0.00
Received By skennedy Date 2015-02-15 Time 12:00 Sent To  
Notes
2015-02-15 12:00:43ROOFING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By sgraham Date 2015-02-17 Time 08:01 Rev Time 0.00
Received By sgraham Date 2015-02-10 Time 14:01 Sent To  
Notes
2015-02-10 14:02:542/10/15 ZONING APPROVED
  
 1. GUEST SUITE CAN NOT BE USED AS A RENTAL, ZONING,
 SF7- ONE FAMILY ON THE PROPERTY, NO KITCHEN IN THE
 UNIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-05 Cont ID  
Sent By sgraham Date 2014-12-05 Time 12:03 Rev Time 0.00
Received By sgraham Date 2014-12-05 Time 12:03 Sent To  
Notes
2014-12-05 12:08:0512/5/14 ZONING FAILED
  
 1. MOTHER-IN-LAW SUITE CAN NOT HAVE A KITCHEN. THE
 ZONING FOR THE DISTRICT IS SF7, MEANING ONE FAMILY PER
 PROPERTY, YOU WILL BE ALLOWED THE BEDROOM, BATH AND
 SITTING ROOM NO COMPLETE KITCHEN.THE UNIT
 CAN NOT BE USED AS A RENTAL.
 2. ROOF HEIGHT ON THE MAIN HOUSE IS OVER THE 30' MAX,
 YOU MUST MEASURE FROM THE GRADE NOT THE FINISH FLOOR.
 3. WALL LOCATED IN THE FRONT SETBACK MUST BE 4' IN
 HEIGHT NOT 6'.
 4. PROVIDE A LANDSCAPE PLAN, THE PERMIT FOR THE
 LANDSCAPING IS NOT COVERED BY THE PRIMARY PERMIT.