Plan Review Details - Permit 14110935
Plan Review Stops For Permit 14110935
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-14 Cont ID  
Sent By jgomez Date 2015-01-13 Time 18:03 Rev Time 0.00
Received By jgomez Date 2015-01-13 Time 18:03 Sent To  
Notes
2015-01-13 18:11:331) SLIDING GLASS DOORS NOA 12-0130.13.
 2) FRENCH DOORS NOA 11-1013.24,
 3) SINGLE HUNG WINDOWS NOA 14-0908.12.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By JGomez Date 2014-12-11 Time 11:10 Rev Time 0.00
Received By jgomez Date 2014-12-11 Time 10:31 Sent To  
Notes
2014-12-11 11:11:15REVISION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) NEW GARAGE DOUBLE HUNG WINDOW SHOWN ON PLANS.
  
 B) NEW GARAGE FRENCH DOOR SHOWN ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.2
 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-67`12
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-22 Cont ID  
Sent By dhayes Date 2015-01-22 Time 12:41 Rev Time 0.00
Received By dhayes Date 2015-01-22 Time 12:41 Sent To  
Notes
2015-01-22 12:42:16ROUTED TO HISTORIC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By DHayes Date 2014-12-15 Time 08:33 Rev Time 0.00
Received By dhayes Date 2014-12-15 Time 07:32 Sent To  
Notes
2014-12-15 08:33:4712/15/2014
 PROJECT: 285 BARCELONA
 PERMIT#: 14080586
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW FOR REVISION TRACKING#14110935
 ACTION: DENIED.
  
 1) E-1
 REVISE NOTES: THERE ARE A COUPLE OF SMALL NOTES AT THE
 BOTTOM OF THE SYMBOLS LEGEND NEXT TO THE RECESSED
 LIGHTS AND SMOKE DETECTOR SYMBOLS AND THEN THERE ARE A
 FEW LARGER NOTES ON THE TOP CENTER OF THE SHEET.
 COMBINE ALL NOTES FOR CLARITY AND ADD:
 A.) ALL NEW 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. (1)BATHROOMS, (2)GARAGES, (3)OUTDOORS,
 (4)CRAWL SPACES, (5)UNFINISHED BASEMENTS, (6)KITCHES,
 (6)LAUNDRY ROOMS, (7)AND (8)BOATHOUSES. NEC 210.8
 B.) ALL LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 2) E-2
 REVISE RISER DIAGRAM TO TO INCLUDE WIRE AND CONDUIT
 SIZES AND TYPE BETWEEN METER AND MAIN DISCONNECT, AND
 BETWEEN THE GUTTER AND PANEL B.
  
 AN ELECTRICAL APPLICATION IS REQUIRED FOR THIS SCOPE.
 NONE ON FILE AT THIS TIME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-01-30 Cont ID  
Sent By fmittner Date 2015-01-30 Time 10:37 Rev Time 0.00
Received By fmittner Date 2015-01-30 Time 10:37 Sent To I
Notes
2015-01-30 10:39:21WINDOW IN GARAGE ON WEST ELEVATION SHALL BE A SLIDER OR
 CASEMENT NOT A 6/6 SINGLE HUNG AS PROPOSED AND NO GRID
 PATTERN ON SINGLE GLASS DOOR LEADING INTO GARAGE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-31 Cont ID  
Sent By skennedy Date 2015-01-31 Time 09:20 Rev Time 0.00
Received By skennedy Date 2015-01-05 Time 14:34 Sent To  
Notes
2015-01-05 14:34:56R13
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-15 Cont ID  
Sent By dhayes Date 2014-12-15 Time 08:33 Rev Time  
Received By dhayes Date 2014-11-25 Time   Sent To  
Notes
2014-11-26 10:30:21INCOMING SENT TO R10 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By TKLarge Date 2014-12-01 Time 10:03 Rev Time 0.00
Received By tklarge Date 2014-12-01 Time 09:10 Sent To  
Notes
***NONE***