Plan Review Details - Permit 14110915
Plan Review Stops For Permit 14110915
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-12-04 Cont ID  
Sent By jwitmer Date 2014-12-04 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-13 Cont ID  
Sent By dhayes Date 2015-01-13 Time 12:29 Rev Time 0.00
Received By dhayes Date 2015-01-13 Time 07:53 Sent To  
Notes
2015-01-13 12:29:1901/13/2015
 PROJECT: TANNING SALON
 PERMIT#: 14110915
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) VERIFY EQUIPMENT GROUND FROM THE 80AMP OCPD
 INDICATED IN PANEL ?A? 14,16,18, TO FEED THE CHILLI
 POWER BED VIA PTR 39 BOOST TRANSFORMER IS UNDERSIZED.
 NEC 250.122.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) REFER TO MANUFACTURER PRODUCT SPECIFICATIONS
 INDICATING THE NRTL LISTING, VOLTAGE AND KW LOAD AND
 INSTALLATION REQUIREMENTS FOR EACH PIECE OF EQUIPMENT.
 NEC 110.3(B)
  
 4) VERIFY GROUNDING OF THE BUCK BOOST TRANSFORMERS.
 PROVIDE A DETAIL INDICATING HOW TO CONNECT THE BUCK
 BOOST TRANSFORMER'S GROUNDING ELECTRODE BACK TO THE
 MAIN GROUNDING ELECTRODE SYSTEM VIA EQUIPMENT GROUND
 SIZED IN ACCORDANCE WITH THE NEC 250.122
  
 5) OUTLETS INDICATED IN THE FIRE RATED TENANT
 SEPARATION WALL SHALL BE SEPARATED BY A MINIMUM OF 24"
 FROM ANY OUTLETS IN THE ADJACENT TENANT SPACE OR BE
 PROTECTED BY A FIRE RATED MATERIAL APPROVED FOR THAT
 USE.
 FBC 713.3.1.2.
  
 6) ONE 15 OR 20AMP GFI RECEPTACLE OUTLET SHALL BE
 INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING
 OF HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS. NEC 210.63 SEE
 210.8(A)(3), VERIFY THE REQUIRED OUTLETS ARE EXISTING
 OR INDICATE NEW OUTLETS INCLUDING THE CIRCUIT IN THE
 CORRESPONDING PANELBOARD.
  
 7) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR NETWORK, DATA, AND, COMMUNICATION
 INSTALLATIONS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By dhayes Date 2014-12-16 Time 16:28 Rev Time 0.00
Received By dhayes Date 2014-12-16 Time 14:10 Sent To  
Notes
2014-12-16 16:28:4412/16/2014
 PROJECT: TANNING SALON
 PERMIT#: 14110915
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO INDICATE THE SIZE OF THE
 EXISTING FEEDERS TO PANEL A AND PANEL B. NEC 215.5
  
 2) PROVIDE A SITE PLAN THAT INCLUDES THE LOCATION OF
 BAY#2505, THE LOCATION OF THE EXISTING SERVICE AND THE
 LOCATION OF THE NEW SERVICE TO SHOW COMPLIANCE WITH THE
 NEC 230.72 "GROUPING OF DISCONNECTS,"
  
 3) INDICATE THE ROUTING OF THE NEW SERVICE FEEDER TO
 INDICATE COMPLIANCE WITH NEC 230.3 "ONE BUILDING OR
 OTHER STRUCTURE NOT TO BE SUPPLIED THROUGH ANOTHER."
  
 4) PROVIDE REASONING FOR THE NEW SERVICE TO INDICATE
 COMPLIANCE WITH NEC 230.2 " NUMBER OF SERVICES" .
  
 5) PROVIDE A COMPLETE LOAD CALCULATION OF THE
 ELECTRICAL SERVICE INCLUDING THE EXISTING AND NEW
 PANELS INDICATING THE TOTAL CONNECTED LOAD AFTER THE
 ADDITION OF NEW CIRCUITS. BASED ON PART II AND III OF
 THE NEC 220
  
 6) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 7) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 8) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS
 INDICATING THE NRTL LISTING, VOLTAGE AND KW LOAD FOR
 EACH PEICE OF EQUIPMENT. NEC 110.3(B)
  
 9) REVISE THE PLANS TO CLARIFY GROUNDING OF THE BUCK
 BOOST TRANSFORMERS. PROVIDE A DETAIL INDICATING HOW TO
 CONNECT THE BUCK BOOST TRANSFORMER'S GROUNDING
 ELECTRODE BACK TO THE MAIN GROUNDING ELECTRODE SYSTEM
 VIA EQUIPMENT GROUND SIZED IN ACCORDANCE WITH THE NEC
 250.122
  
 10) REVISE THE FLOOR PLAN TO INDICATE THE LOCATIONS OF
 THE BUCK BOOST TRANSFORMER WHERE REQUIRED. FBC-WPB
 AMENDMENTS 107.3.5
  
 11) REVISE THE PLAN TO INDICATE THE REQUIRED CLEARANCE
 AND DEDICATED WORKING SPACE ABOUT ELECTRICAL EQUIPMENT
 INCLUDING THE SERVICE EQUIPMENT, SERVICE PANELS, BUCK
 BOOST TRANSFORMERS AND DISCONNECTS FOR TANNING
 EQUIPMENT. NEC110.26
  
 12) REVISE THE PLAN TO INDIACTE THE LOCATION OF THE
 LIGHTING CONTACTOR(S) AND PROVIDE ADDITIONAL DETAIL TO
 INDICATE COMPLIANCE WITH FBC-E 505.2 LIGHTING CONTROLS
 (MANDATORY) LIGHTING SYSTEMS SHALL BE PROVIDED WITH
 CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2,
 505.2.3 AND 505.2.4.
  
 13) THE BRANCH CIRCUIT FEEDING THE EXIT AND EMERGENCY
 LIGHTING EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 700.12(F)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-09 Cont ID  
Sent By pleduc Date 2014-12-09 Time   Rev Time 0.00
Received By pleduc Date 2014-12-09 Time 10:01 Sent To  
Notes
2014-12-09 10:47:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 ADD A REAR HALLWAY EXIT SIGN, AS INDICATED ON THE LIFE
 SAFETY PLAN.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-13 Cont ID  
Sent By dhayes Date 2015-01-13 Time 12:29 Rev Time 0.00
Received By dhayes Date 2015-01-12 Time 12:57 Sent To  
Notes
2015-01-12 12:58:29SENT TO DHAYES DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-30 Cont ID  
Sent By hmoser Date 2014-12-30 Time 08:42 Rev Time 0.00
Received By hmoser Date 2014-11-25 Time 09:55 Sent To  
Notes
2014-11-26 09:56:24INCOMING SENT TO B07 . JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-30 Cont ID  
Sent By hmoser Date 2014-12-30 Time 08:41 Rev Time 0.00
Received By hmoser Date 2014-12-30 Time 08:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-28 Cont ID  
Sent By tklarge Date 2014-11-28 Time 07:57 Rev Time 0.00
Received By tklarge Date 2014-11-28 Time 07:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-02 Cont ID  
Sent By llouie Date 2014-12-02 Time 09:07 Rev Time 0.00
Received By llouie Date 2014-12-02 Time 09:07 Sent To  
Notes
2014-12-02 09:09:16NOTES: INTERIOR MODIFICATIONS ONLY. CATEOGRY: PERSONAL
 SERVICES - PERMITTED IN GC ZONE.