Plan Review Details - Permit 14110892
Plan Review Stops For Permit 14110892
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-02 Cont ID  
Sent By jwitmer Date 2015-02-02 Time 14:44 Rev Time 0.00
Received By jwitmer Date 2015-02-02 Time 07:30 Sent To  
Notes
2015-02-02 14:42:16BUILDING PLAN REVIEW
 PERMIT: 14110892
 ADD: 7300 S. DIXIE HWY.
 CONT: TO BE DETERMINED
 TEL: (901)495-8701
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. FEB. 02/ 2015
 ACTION: BUILDING PROVISO
  
 1) THE DESIGNER OF RECORD HAS ASKED (SHEET A-0) THE
 COMPONENT & CLADDING PRODUCT APPROVALS TO BE DEFERRED
 SUBMITTALS:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31)(A) EXTERIOR DOORS, SWING AND GARAGE OR OVERHEAD
 TYPE DOORS
 (B) WINDOWS
 D) ROOFING ASSEMBLIES
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 07:27 Sent To  
Notes
2014-12-02 09:58:11BUILDING PLAN REVIEW
 PERMIT: 14110892
 ADD: 7300 S. DIXIE HWY.
 CONT: TO BE DETERMINED
 TEL: (901)495-8701
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 02/ 2014
 ACTION: DENIED
  
 1) THE STRUCTURAL SHEETS0 PARAPET PRESSURES INDICATE A
 62.5 FOR END ZONES. FOR COMPONENTS AND CLADDING FOR
 ROOFING @ 10 SQ FT / EXP. C, FOR ELEVATION 20 FT A
 -67.8 FOR ROOF ZONES # 2. NOT THE -62.5. 2010 FBC-B
 1609.1.5/ 1609.1.2.3.1.
  
 2) THE STRUCTURAL SHEETS0 FOR WINDOW AND DOOR PRESSURES
 ARE ALSO LOW IT APPEARS THEY MAY BE TAKEN FOR EVEN FOR
 A ELEVATION OF 15 FT. THE PARPET HEIGHT OF 21'-6" EXP.
 C @ 20 SQ FT.ZONE 4 38.6/ -42 AND ZONE # 5 38.6/ -50.4.
 APPROX. 2010 FBC-B 1609.1.5/ 1609.1.2.3.1
  
 3) THE COVERSHEET LIST THE ROOFING PRODUCT APPROVAL FL
 3443-R3 A SINGLE PLY SYSTEM, NO APPROVALS WAS SUBMITTED
 AT THIS TIME, PLEASE ALSO NOTE MANY ROOFING PRODUCT
 APPROVALS HAVE SPAN LIMITATIONS FOR THE JOIST SPACING,
 THE BAR JOIST ARE SPACED AT 7'-0" O. C. ALSO NOTE THE
 PRODUCT APPROVAL SPECIFIED NEEDS TO BE THE MOST CURRENT
 APPROVAL. THIS PRODUCT APPROVAL IS ON REVISION # 12 NOT
 R3.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES.
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: PLEASE IDENTIFY
 SUB-SYSTEMS BY CIRCLING THE SYSTEM TO BE INSTALLED.
  
 4) NO WINDOW PRODUCT APPROVALS WERE SUBMITTED, THE
 COVER SHEET LIST A FL 16314 R-1.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31)(31)(B) WINDOWS
  
 5) THE PRODUCT APPROVAL FL 11241-R3 BERRIDGE METAL
 ROOFING WAS SUBMITTED WITH THE DESIGNERS SHOP DRAWING
 STAMP OF APPROVAL BUT NOT FOUND ON THE COVERSHEET LIST
 OF PRODUCT APPROVALS, WHERE IS IT GOING TO BE
 INSTALLED? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-30 Cont ID  
Sent By dhayes Date 2015-01-30 Time 11:53 Rev Time 0.00
Received By dhayes Date 2015-01-30 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By dhayes Date 2014-12-15 Time 12:41 Rev Time 0.00
Received By dhayes Date 2014-12-15 Time 12:40 Sent To  
Notes
2014-12-15 14:03:1912/15/2014
 PROJECT: AUTOZONE 1261
 PERMIT#: 14110892
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE RISER DIAGRAM WITH REPECT TO THE FOLLOWING:
 A) THE SERVICE ENTRANCE CONDUCTOR SET IS INDICATED AS
 TWO SETS OF 4, 250MCM ON THE LINE SIDE COMING IN AND
 THE AFTER THE CT'S IS INDICATED AS TWO SETS OF 4, 3/0.
 THIS IS CONFLICTING. DETERMINE THE ACTUAL METERING
 MEATHOD AND INDICATE THIS ACCUARATELY ON THE PLAN.
  
 2) INDICATE LOCATION FOR ALL PANELS AND IDENTIFY EACH
 ON THE FLOOR PLAN.
  
 3) PROVIDE A SIGN CIRCUIT NEC 600.5. INDICATE THE SIGN
 CIRCUIT ON THE PANEL SCHEDULE AND INDICATE COMPLIANCE
 WITH THE FBC-E 505.2
  
 4) INDICATE COMPLIANCE WITH THE FBC-E 505.2. LIGHTING
 SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN
 SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. PROVIDE
 SCHEDULE AND CONTROL DETAIL FOR LIGHTING CONTACTOR(S)
  
 5) IDENTIFY ALL SYMBOLS, AND CIRCUITS ON FLOOR PLAN.
 ALL SYMBOLS TO COINCIDE WITH SYMBOLS LEGEND AND ALL
 CIRCUITS TO COINCIDE WITH PANEL SCEDULE(S).
  
 6) PROVIDE ALL PANEL SCHEDULES.
  
 7) A SEPARATE GROUND ROD AS PROPOSED MUST BE CONNECTED
 TO THE ELECTRICAL GROUNDING ELECTRODE SYSTEM TO AVOID
 ANY DIFFERENCE OF POTENTIAL.
  
 8) DRINK MACHINE OUTLET TO BE GFI PROTECTED. NEC 422.51
  
 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12(F)
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By cranford Date 2015-02-12 Time 13:30 Rev Time 0.00
Received By cranford Date 2015-02-12 Time 11:29 Sent To  
Notes
2015-02-12 13:30:05ALSO REVIEWED UNDER ENGINEERING APPLICATION E14100016

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By pleduc Date 2014-12-01 Time   Rev Time 0.00
Received By pleduc Date 2014-11-25 Time 14:47 Sent To  
Notes
2014-12-01 09:41:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A - 01 ALL FIRE EXTINGUISHERS IN THE NEW STORAGE
 FACILITY SHALL BE 4A 60BC.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-06 Cont ID  
Sent By jroach Date 2015-02-12 Time 13:30 Rev Time 0.00
Received By cranford Date 2015-01-26 Time 12:19 Sent To  
Notes
2015-01-27 12:18:49C29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-16 Cont ID  
Sent By hmoser Date 2014-12-16 Time 18:17 Rev Time 0.00
Received By hmoser Date 2014-11-24 Time 07:01 Sent To  
Notes
2014-11-25 07:01:55EXPEDITED, INCOMING SENT TO C25. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-02-02 Cont ID  
Sent By jwitmer Date 2015-02-02 Time 14:42 Rev Time 0.00
Received By jwitmer Date 2015-02-02 Time 14:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 13:43 Sent To  
Notes
2014-12-02 13:44:11BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-05 Cont ID  
Sent By hmoser Date 2015-02-05 Time 13:36 Rev Time 0.00
Received By hmoser Date 2015-02-05 Time 11:28 Sent To  
Notes
2015-02-05 13:36:15PASS PROVISO
 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO
 ROOF TIE DOWN
 SHOWING TYPE AND SIZE OF ANCHOR USED AND HOW FAR APART
 THE
 ANCHOR SHOULD BE.PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 2) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 3) DUCT SMOKE DETECTORS SHALL INITIATE GENERAL FIRE
 ALARM
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561- 805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By hmoser Date 2014-12-16 Time 18:17 Rev Time 0.00
Received By hmoser Date 2014-12-16 Time 17:43 Sent To  
Notes
2014-12-16 18:17:18PLAN DENIED
  
 1) PROVIDE A COMPLETE SET OF PLANS SHOWING
 DUCT SIZE AND CFM PER SECTION 107 FBC 2010
 2) PROVIDE ENGINEER DETAIL ON CURB TIE DOWN TO ROOF
 AND RTU TIE DOWN TO CURB PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 3) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER
 CONTROLS 2010 FLORIDA ENERGY CODE.
 4) SUBMIT ENERGY CALCULATIONS WITH THE PLAN
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-31 Cont ID  
Sent By tklarge Date 2015-01-31 Time 05:13 Rev Time 0.00
Received By tklarge Date 2015-01-31 Time 04:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-04 Cont ID  
Sent By tklarge Date 2014-12-04 Time 13:41 Rev Time 0.00
Received By tklarge Date 2014-12-04 Time 06:54 Sent To  
Notes
2014-12-04 13:17:201) SHT. A-3 - DETAIL #4 - THE DOWNSPOUT FOR THE ROOF
 DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE
 BUILDING WALL PER THE 2010 FLORIDA BUILDING CODE
 SEC.1503.7.
 2) SUBMIT A RISER DIAGRAM FOR THE STORM DRAIN
 COLLECTION SYSTEM. INDICATE ALL PIPE SIZES AND THE
 SQUARE FOOTAGE OF THE ROOF THAT IS DRAINED BY EACH
 INDIVIDUAL ROOF DRAIN.INCLUDE 1/2 OF THE AREA OF THE
 PARAPET WALL TO THE PROJECTED ROOF AREA CALCULATIONS.
 WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3.
 3) SHT.A-7 - ROOF PLAN - THERE IS A NOTE AT ONE OF THE
 ROOF DRAINS ON THE EXISTING ROOF THAT STATES "SEE NOTE
 10." THERE IS NO NOTE 10 ON THIS PGE.CLARIFY.
 4) THE PVC ON THE ROOF SHALL BE PROTECTED FROM UV RAYS
 PER MANUF. RECOMMENDATIONS AND ASTM REQS, FPC 303.2..
 5) SHT.P-1 - INDICATE THE SIZE OF THE DRAIN FROM THE
 NFHB ON THE ROOF.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-02-06 Cont ID  
Sent By jroach Date 2015-02-06 Time 13:09 Rev Time 0.00
Received By jroach Date 2015-02-06 Time 13:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-09 Cont ID  
Sent By jroach Date 2014-12-09 Time 15:48 Rev Time 0.00
Received By jroach Date 2014-12-09 Time 15:48 Sent To  
Notes
2014-12-09 15:48:21ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.09.2014
 PERMIT NO.: 14110892
 ADDRESS: 7300 SOUTH DIXIE HIGHWAY
 CONTRACTOR/CONTACT: WADE DAVIS
 TELEPHONE NO.: 901.268.1058
 SCOPE OF REVIEW: WAREHOUSE/STORAGE ADDITION TO EXISTING
 AUTO PARTS STORE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A UNITY
 OF TITLE SHALL BE RECORDED IN THE PUBLIC RECORDS OF
 PALM BEACH COUNTY. PLEASE CONTACT VINCE NOEL, CITY
 SURVEYOR AT 561.494.1096 OR [email protected] FOR AN
 APPLICATION. A COPY OF THE UNITY OF TITLE SHALL BE
 PROVIDED WITH THE BUILDING PERMIT PACKAGE.
  
 2. ALL APPLICABLE PERMITS (INCLUDING FDOT) SHALL BE
 OBTAINED FOR ANY WORK WITHIN THE RIGHT-OF-WAY.
  
 3. A SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 A LANDSCAPE PERMIT. THE PERMIT APPLICATION SHALL
 INCLUDE TWO (2) SETS OF SIGNED/SEALED LANDSCAPE PLANS,
 AS WELL AS A CERTIFIED COST ESTIMATE FOR THE LANDSCAPE
 WORK (MATERIAL + LABOR).
  
 4. ALL TREES PROPOSED ALONG THE EAST PROPERTY LINE
 SHALL BE PLANTED OUTSIDE OF THE THREE (3) FOOT PLATTED
 UTILITY EASEMENT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-12-01 11:37:5212/1/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved