Plan Review Details - Permit 14110854
Plan Review Stops For Permit 14110854
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-05 Cont ID  
Sent By jwitmer Date 2015-03-05 Time 07:46 Rev Time 0.00
Received By jwitmer Date 2015-03-05 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-30 Cont ID  
Sent By jwitmer Date 2015-01-30 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2015-01-30 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-09 Cont ID  
Sent By jwitmer Date 2014-12-09 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2014-12-09 Time 14:06 Sent To  
Notes
2014-12-09 15:17:01BUILDING PLAN REVIEW
 PERMIT: 14110854
 ADD: 5335 N. MILITARY TRAIL
 CONT: TO BE DETERMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 09/ 2014
 ACTION: DENIED
  
 1) BOTH SHEETS EG1.0 & A1.0 BOTH INDICATE THE TENANT
 SEPARATION WALL TO BE A 1 HOUR TENANT SEPARATION WALL.
 THE PLANS FAIL TO IDENTIFY WHAT TYPE OF OCCUPANCY IS ON
 BOTH SIDES OF THE A3 OCCUPANCY. 2010 FBC-B TABLE 508.4
  
 2) THE COVERSHEET T.1.0 INDICATES THIS SPACE TO BE FIRE
 SPRINKLERED, BUT NO PLANS WERE SUBMITTED. UNDER THE
 2010 FBC-B TABLE 508.2.5 INCIDENTAL ACCESSORY
 OCCUPANCIES LAUNDRY ROOMS OVER 100 SQ. FT. HAVE TO BE
 EITHER 1 HOUR FIRE RATED OR FIRE SPRINKLERED. TO TAKE
 THE CREDIT THE CODE GIVES FOR FIRE SPRINKLERS PLANS
 HAVE TO BE SUBMITTED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: (5.) FIRE SUPPRESSION
 SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE SPRINKLERS
  
 3) SHEET A1.0 INDICATES IN THE LOCKER ROOMS ACCESSIBLE
 LOCKERS, SHEET A5.0 SHOWS DETAILS FOR ACCESSIBLE
 BENCHES, THEY ARE MISSING ON THE A1.0 LOCKER ROOM
 DETAILS. SEE 2010 FBC-ACCESSIBILITY CODE 903.1-4 .
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-10 Cont ID  
Sent By rlecky Date 2015-02-10 Time 11:46 Rev Time 0.00
Received By rlecky Date 2015-02-10 Time 10:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-08 Cont ID  
Sent By dhayes Date 2015-01-08 Time 13:52 Rev Time 0.00
Received By rlecky Date 2015-01-08 Time 11:54 Sent To  
Notes
2015-01-08 13:53:23 
 14110854
 5335 N. MILITARY TRAIL #19
 PLANET FITNESS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. ALL COMMENTS BASED ON THE 2008 NEC.
  
 PROVIDE AN ELECTRICAL RISER PLAN FOR THE ELECTRICAL
 SERVICE FEEDING THIS BUILDING SHOWING LOCATION OF ALL
 METERS AND MAIN DISCONNECTS. VERIFY THE ELECTRICAL
 SERVICE MAINS SERVING THIS BUILDING INCLUDING UNIT #19
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. INDICATE
 THE REQUIRED FAULT CURRENT RATING FOR ALL NEW
 EQUIPMENT. NEC 110.9, 110.10, 215.5, 230.71,
  
 THE MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTOR FOR 1200
 AMPERE IS 3/0. VERIFY THE INTENDED USE AND PROPOSED
 TERMINATION POINT FOR THE 2/0 EQUIPMENT GROUND ROUTED
 WITH THE SERVICE CONDUCTORS. NEC T. 250.122
  
 INDICATE THE SIZE AND TYPE OF GROUNDING ELECTRODE
 PROPOSED FOR THIS SERVICE. NEC 250.32, 250.52
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22
  
 PROVIDE DEDICATED SPACE FOR THE ELECTRICAL DISCONNECTS
 AND PANEL BOARDS. NEC 110.26, 240.24(D)
  
 ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING
 AND SIGN CIRCUIT. PROVIDE SHOW WINDOW LIGHTING OUTLETS.
 NEC 210.62, 408.4, 600.5
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A STRUCTURAL DETAIL FOR HANGING THE TWO LARGE
 CEILING FANS. FBC 1604.1
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
2015-01-08 11:53:59 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2015-02-26 Cont ID  
Sent By wjolin Date 2015-02-26 Time 16:22 Rev Time 0.00
Received By wjolin Date 2015-02-26 Time 16:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-10 Cont ID  
Sent By wjolin Date 2015-02-10 Time 15:34 Rev Time 0.00
Received By wjolin Date 2015-02-10 Time 15:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-12-03 Cont ID  
Sent By wjolin Date 2014-12-03 Time 16:43 Rev Time 0.00
Received By wjolin Date 2014-12-03 Time 12:35 Sent To  
Notes
2014-12-03 13:17:515335 NORTH MILITARY TRAIL #19
 PERMIT #14110854
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
 SHEET T1.0: CODE SECTION INCORRECTLY REFERENCES CHAPTER
 36 (NEW MERCANTILE) IN LIEU OF CHAPTER 12 (NEW
 ASSEMBLY) OF THE LIFE SAFETY CODE.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET A1.0: INDICATE THE EXISTING OCCUPANCY TYPES FOR
 THE TENANTS LOCATED ON BOTH SIDES OF THE NEW ASSEMBLY
 OCCUPANCY. INDICATE IF THE TENANT SEPARATION WALL HAS A
 FIRE RATED BARRIER.
  
 SHEET A1.0: PER SECTION12.3.2.1.2, LAUNDRY AREAS
 (JANITOR #110) SHALL BE SEPARATED FROM ADJACENT AREAS
 WITH A 1-HOUR FIRE BARRIER AND AUTOMATIC SPRINKLERS.
 PROTECT ALL OPENINGS AND PENETRATIONS. PROVIDE FIRE
 DAMPERS FOR DUCTWORK (SHEET M1.0).
  
 SHEET A1.2: RUBBER FLOORING - PER SECTION 10.2.7.2,
 FLOOR COVERINGS, OTHER THAN CARPET, SHALL HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 SHEET A3.0: NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET E1.1 & SHEET A2.0: ARCHITECT SHOWS FIRE ALARM
 DEVICES FOR REFERENCE ONLY. PROVIDE VISUAL NOTIFICATION
 COVERAGE IN ALL PUBLIC AND COMMON USE SPACES SUCH AS
 TANNING AND MASSAGE. FIRE ALARM NOTIFICATION LACKING IN
 WORKOUT #101. A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 FIRE SPRINKLER DESIGN/MODIFICATION: FOR ISSUANCE OF A
 GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE
 FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 NOTE - FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-13 Cont ID  
Sent By cpuell Date 2015-03-16 Time 09:01 Rev Time 0.00
Received By cpuell Date 2015-02-18 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-18 Cont ID  
Sent By cpuell Date 2015-02-18 Time 13:43 Rev Time 0.00
Received By cpuell Date 2015-01-21 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-08 Cont ID  
Sent By cpuell Date 2015-01-08 Time 13:27 Rev Time 0.00
Received By cpuell Date 2014-11-26 Time 14:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2015-03-05 Cont ID  
Sent By jwitmer Date 2015-03-05 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2015-03-05 Time 07:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-01-30 Cont ID  
Sent By jwitmer Date 2015-01-30 Time 08:34 Rev Time 0.00
Received By jwitmer Date 2015-01-30 Time 08:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-01-08 Cont ID  
Sent By skennedy Date 2015-01-08 Time 13:22 Rev Time 0.00
Received By skennedy Date 2015-01-08 Time 13:22 Sent To  
Notes
2015-01-08 13:25:481ST REVIEW: FBC 2010
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. PROVIDE A SET OF PAPER PLANS AND TAKE THAT
 OFFICE FOR REVIEW. PLEASE RETURNED STAMPED WITH A COPY
 OF RECEIPT AS APPLICABLE.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By hmoser Date 2015-02-17 Time 14:47 Rev Time 0.00
Received By hmoser Date 2015-02-17 Time 13:04 Sent To  
Notes
2015-02-17 14:47:11PLAN PASS
 REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE 2010
 REFER TO SECTION 603.5 NONMETALLIC DUCT
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-03 Cont ID  
Sent By hmoser Date 2015-01-03 Time 11:08 Rev Time 0.00
Received By hmoser Date 2015-01-03 Time 09:38 Sent To  
Notes
2015-01-03 11:08:41PLAN DENIED
 1) REFER TO SECTION 304.1 GENERAL AND
 606.2.1 SUPPLY AIR SYSTEMS FBC (M) 2010
 FOR RTU 1,2,3,4 AND 8
 2) SHOW TERMINATION OF ALL EXHAUST REFER TO
 SECTION501.2 EXHAUST DISCHARGE 2010 FBC (M)
 3) PROVIDE A DETAIL FROM THE ENGINEER FOR
 CURB TO ROOF TIE DOWN AND RTU TO CURB TIE DOWN
 301.12 WIND RESISTANCE
 4) REFER TO SECTION 1509.7 MECHANICAL UNITS
 2010 FBC
 5) DRYER BOOSTER FANS ARE NOT PERMITTED IN THE
 CITY OF WEST PALM BEACH PER FIRE DEPARTMENT.
 6) REFER TO SECTION 601.4 BALANCED RETURN AIR
 2010 FBC (M)
 7) REFER TO SECTION 603.5 NONMETALLIC DUCT
 2010 FBC (M).
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-02-19 Cont ID  
Sent By tklarge Date 2015-02-19 Time 14:04 Rev Time 0.00
Received By tklarge Date 2015-02-19 Time 14:04 Sent To  
Notes
2015-02-19 14:06:03PROVISO: 2 HANDICAP ACCESSIBLE DRINKING FOUNTAINS ARE
 REQUIRED PER THE 2010 FAC SEC. 211.2.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-26 Cont ID  
Sent By tklarge Date 2015-01-26 Time 06:33 Rev Time 0.00
Received By tklarge Date 2015-01-25 Time 09:43 Sent To  
Notes
2015-01-25 09:43:441) SHT. A5.0- THE ACCESSIBLE DETAILS FOR THE DRINKING
 FOUNTAINS ARE COMPLETELY MISSING FROM THE SHEET.
 PROVIDE FULL DETAILS .COMPLY W/ 2010 FBC, ACCESSIBILITY
 SECS. 211, 306,& 602.
 2) THE TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER STANDPIPE SHALL BE A MINIMUM OF 2 INCHES IN
 DIAMETER. THE CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM
 OF 3 INCHES PER THE 2010 FPC SEC. 406.3.THE RISER SHOWS
 2 1/2".
 3) THERE IS STILL A DISCEPANCY BETWEEN THE SHOWER STALL
 DIMENSIONS SHOWN ON SHT. A1.1 AND THE DIMENSIONS SHOWN
 IN THE PLUMBING FIXTURE SCHEDULE ON SHT.P1.0. CLEARLY
 SHOW THE INSIDE DIMENSIONS (L X W) OF THE SHOWER
 STALLS. THE PLANS SHOW DIMENSIONS OF INSIDE THE SHOWER
 TO THE EXTERIOR OF THE WALLS. THE MEP NARRATIVE STATES
 THE PLUMBING FIXTURE SCHEDULE HAS THE CORRECT STALL
 DIMENSIONS. IF THIS IS IN FACT CORRECT, ENSURE THAT THE
 DIMENSIONS ON THE ARCHITECTURAL PLAN CORRELATE WITH THE
 PLUMBING FIXTURE SCHEDULE. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 4) THE DEVELOPED LENGTH OF THE BRANCH VENT CONNECTING
 THE VENT STACKS TO THE VENT THROUGH THE ROOF EXCEEDS
 FORTY FEET IN DEVELOPED LENGTH AND SHALL BE INCREASED
 ONE PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF THE
 VENT PIPE PER THE 2010 FPC SEC.916.2, 916.4.1. THIS
 SHALL BEGIN AT THE VENT FOR THE ACCESSIBLE SHOWER IN
 THE WOMEN'S RESTROOM.
 5) THERE ARE STILL SECTIONS OF THE OF THE PLUMBING
 RISER ON SHT. P1.0 THAT ARE NOT SIZED. CHECK THE WET
 SECTIONS OF THE WASTE STACKS AND ALSO THE BUILDING
 DRAIN. TYPICAL SIZES CAN BE SHOWN AS SUCH. WPB AMEND.
 TO 2010 FBC SEC.107.2.1, TABLE 709.1.
 6) THE VENT FOR THE WASHING MACHINE SHALL BE A MINIMUM
 OF 2 INCHES, NOT 1 1/2 INCHES AS SHOWN PER THE 2010 FPC
 SEC.916.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-29 Cont ID  
Sent By tklarge Date 2014-11-29 Time 04:42 Rev Time 0.00
Received By tklarge Date 2014-11-28 Time 08:17 Sent To  
Notes
2014-11-29 05:02:011) SHT. A1.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR
 THE WATER CLOSET PER THE 2010 FL. ACCESSIBILITY CODE
 SEC. 604.3.
 2) SHT. A5.0 - THE MAXIMUM HEIGHT OF THE HAND DRYER
 ABOVE THE FINISH FLOOR SHALL BE 48 INCHES PER THE FAC
 SEC.308. THE PLAN SHOWS 48"-50".
 3) SHT. P1.0 - THE PLUMBING FIXTURE SCHEDULE SHOWS THE
 HANDICAP ACCESSIBLE SHOWER DIMENSIONS AS 38" X 37" AND
 THE STANDARD SHOWER AS 42" X 34" AND SHT. A1.1 SHOWS
 DIFFERENT DIMENSIONS FOR BOTH SHOWERS. CLARIFY.
 4) THE WASHER AND DRYER SHALL COMPLY W/2010 FAC
 SECS.611.1 - 611.4.
 5) SIZE ALL WET SECTIONS OF THE WASTE AND SOIL STACKS
 AND THE BUILDING DRAIN.COMPLY WITH FPC TABLE 710.1.(2).
 6) SIZE ALL SECTIONS OF THE VENT SYSTEM. COMPLY WITH
 FPC TABLE 916.1.
 7) SHT. P1.2 - FLOOR DRAIN DETAIL - DELETE THE
 REFERENCE TO BACKWATER VALVES. BACKWATER VALVES SHALL
 BE INSTALLED WHEN REQUIRED BY 2010 FPC SEC.715.
 8) SHT. P1.2 - WATER HEATER DETAIL - THE HOT WATER
 LINES ARE NON-CONTINUOUS AND IT IS DIFFICULT TO SEE
 WHERE THEY CONNECT TO EACH OTHER AND TO THE RECIRC
 SYSTEM AND OTHER POINTS. PROVIDE A CLEAR AND LEGIBLE
 DETAIL CLEARLY SHOWING THE CONNECTION POINTS.
 9) THE DEVELOPED LENGTH OF THE BRANCH VENT CONNECTING
 THE VENT STACKS TO THE VENT THROUGH THE ROOF EXCEEDS
 FORTY FEET IN DEVELOPED LENGTH AND SHALL BE INCREASED
 ONE PIPE SIZE PER THE 2010 FPC SEC.916.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-03-13 Cont ID  
Sent By skennedy Date 2015-03-13 Time 10:45 Rev Time 0.00
Received By skennedy Date 2015-03-12 Time 09:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-30 Cont ID  
Sent By sgraham Date 2014-12-30 Time 08:21 Rev Time 0.00
Received By sgraham Date 2014-12-30 Time 08:21 Sent To  
Notes
2014-12-30 08:22:3112/30/14 ZONING APPROVED, NEED SIGNATURE STAMP STEVE
 KENNEDY ORDERED.
2014-12-01 12:04:5012/1/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved