Plan Review Details - Permit 14110818
Plan Review Stops For Permit 14110818
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-01-06 Cont ID  
Sent By jwitmer Date 2015-01-06 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2015-01-06 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-08 Cont ID  
Sent By dhayes Date 2015-01-08 Time 14:35 Rev Time 0.00
Received By dhayes Date 2015-01-08 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-30 Cont ID  
Sent By wjolin Date 2014-12-30 Time 10:24 Rev Time 0.00
Received By wjolin Date 2014-12-30 Time 08:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 10:03 Rev Time 0.00
Received By tklarge Date 2015-03-10 Time 10:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-02-19 Cont ID  
Sent By tklarge Date 2015-02-19 Time 13:15 Rev Time 0.00
Received By tklarge Date 2015-02-19 Time 12:42 Sent To  
Notes
2015-02-19 13:20:56 
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-01-08 Cont ID  
Sent By tklarge Date 2015-01-08 Time 11:22 Rev Time 0.00
Received By tklarge Date 2014-12-21 Time 05:28 Sent To  
Notes
2014-12-21 06:23:18SHT.P306 -
 1) SHOW THE LINE SIZE DOWNSTREAM OF THE 2 PSI PRESSURE
 REGULATOR AT THE MAIN INTO THE STRUCTURE THAT SUPPLIES
 6765 CFH OF GAS. IF THIS IS 2 " THE LINE IS UNDERSIZED
 FOR THE BTU LOAD AND A TOTAL DISTANCE OF 255 FT. ( THE
 300 FEE TCOLUMN WILL GOVERN ). PER THE 2010 FLORIDA GAS
 CODE TABLE 402.4 (3) THE MINIMUM SIZE SHALL BE 2 1/2 "
 TO SUPPLY THE 6765 BTU LOAD.
 2) GENERAL NOTE # 1 REFERS TO THE SIZING EQUATION FROM
 THE FGC. IF THE EQUATIONS WERE USED IN THE SIZING OF
 THIS GAS SYSTEM, SUBMIT THE CALCULATIONS TO SUPPORT THE
 PIPE SIZING. WPB AMEND. TO 2010 FBC SEC.107.2.1. & FGC
 SEC. 402.4.
 3) PLEASE REFERENCE ALL APPLICABLE TABLES FROM THE 2010
 FGC UTILIZED FOR THE SIZING OF THE SYSTEM IN THE
 GENERAL NOTES SECTION. FGC SEC.402.4.
 4) THE SECTION OF GAS LINE SUPPLYING 6215 BTU'S IS
 UNDERSIZED IF BASED ON TABLE 402.4 (3) OF THE GAS CODE.
 THE MAXIMUM ALLOWED BTU LOAD ON A 2 " PIPE AT 300 FT.
 IS 5600 CFH @ 2 PSI. THE LINE SHALL BE 2 1/2 ".
 5) THE 1 1/4" LINE SUPPLYING 2162 CFH IS UNDERSIZED.
 THE MAXIMUM ALLOWED BTU LOAD ON AN 1 1/4" PIPE AT 300
 FT. IS 1940 CFH @ 2PSI. THE LINE SHALL BE 1 1/2".
 6) LOWER KITCHEN # 135 GAS RISER - SHOW THE TOTAL
 DISTANCE FROM THE STEP DOWN REGULATOR TO THE MOST
 REMOTE OUTLET. AS DRAWN IT IS DIFFICULT TO DETERMINE
 WHERE EACH LENGTH APPLIES TO EACH SECTION. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SHOW THE TOTAL LENGTH OF THE 1 1/2" PIPE RUN FROM
 THE STEP DOWN REGULATOR TO THE GWH-1.
 8) SHOW THE TOTAL LENGTH OF THE 1 1/2" PIPE RUN FROM
 THE STEP DOWN GENERATOR TO THE GWH-2.
 9) THE 1" LINE SUPPLYING 1088 CFH IS UNDERSIZED.THE
 MAXIMUM ALLOWED BTU LOAD ON A 1" LINE AT 300 FT. IS 945
 CFH @ 2 PSI. THE LINE SHALL BE 1 1/4". TABLE 402.4 (3).
 10) THE 1 1/2" LINE SUPPLYING 2965 CFH IS UNDERSIZED..
 THE MAXIMUM ALLOWED BTU LOAD ON AN 1 1/2" LINE AT 300
 FT. IS 2910 CFH @ 2 PSI. THE LINE SHALL BE 2". TABLE
 402.4 (3).
 11) THE 1 1/4" GAS LINE SUPPLYING 2465 CFH IS
 UNDERSIZED. THE MAXIMUM ALLOWED BTU LOAD ON AN 1 1/4"
 LINE AT 300 FT. IS 1940 CFH @ 2 PSI. THE LINE SHALL BE
 1 1/2". TABLE 402.4 (3).
 12) GAS RISER # 1 KIT. #245 - SHOW THE TOTAL RUN OF
 PIPE FROM THE STEP DOWN REGULATOR TO THE MOST REMOTE
 OUTLET. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 13) GAS RISER #2 KIT.#245 - SHOW THE TOTAL RUN OF PIPE
 FROM THE STEP DOWN REGULATOR TO THE MOST REMOTE OUTLET.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) CLARIFY THE CONNECTION POINT OF THE BRANCH LINE FOR
 THE BUFFET SERVICE 2 - #266 GAS RISER TO THE MAIN. IT
 APPEARS TO BE CONNECTED TO THE LOW PRESSURE LINE BUT IT
 ALSO APPEARS TO BE INDICATED AS A MEDIUM PRESSURE (2
 PSI) LINE. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 10:04 Rev Time 0.00
Received By tklarge Date 2015-03-05 Time 12:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-19 Cont ID  
Sent By cpuell Date 2015-02-19 Time 13:50 Rev Time 0.00
Received By cpuell Date 2015-02-06 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-08 Cont ID  
Sent By cpuell Date 2015-01-08 Time 15:16 Rev Time 0.00
Received By cpuell Date 2014-12-04 Time 16:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-01-05 Cont ID  
Sent By hmoser Date 2015-01-05 Time 12:40 Rev Time 0.00
Received By hmoser Date 2015-01-05 Time 12:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 10:03 Rev Time 0.00
Received By tklarge Date 2015-03-10 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-02-19 Cont ID  
Sent By tklarge Date 2015-02-19 Time 12:42 Rev Time 0.00
Received By tklarge Date 2015-02-15 Time 06:31 Sent To  
Notes
2015-02-19 12:40:321) THE MATCH LINES ADDED ON SHEETS P201 THRU P206 HAVE
 NOT ACCOMPLISHED THE INTENT FOR CLARIFICATION.THE ADDED
 NOTE"SEE FLOOR PLAN 101 FOR CONTINUATION" REFERENCES
 THE CORRECT SHEET BUT SHEET 101 DOES NOT SHOW THE
 CONTINUATION OF THE PIPING FOR THE DIFFERENT AREAS.
 ALTHOUGH I APPLAUD THE EFFORT TO CLARIFY DETAILS, THE
 CHANGES HAVE CAUSED ADDITIONAL CONFUSION. SHT. P101
 SHOWS VERY LITTLE PIPNG, AND ROOMS/AREAS ARE NOT
 NUMBERED, SO IT IS VERY DIFFICULT TO LOCATE THE
 CONTINUATION OF PIPNG FROM ONE SHEET OR AREA TO THE
 NEXT. THE MATCH LINES ARE NOT IDENTIFIED WITH A LETTER
 OR NUMBER SO IT IS VERY DIFFICULT TO FOLLOW THE PIPING
 SYSTEMS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT.P3.04 - IN MY PREVIOUS PLAN REVIEW, COMMENT #
 11, I REQUESTED TO SHOW THE CONTINUATION / CONNECTION
 POINTS OF THE 2" & 3" VENTS ON THE GREASY WASTE
 SYSTEM.THE NOTE "SEE PLANS FOR CONTINUATION" DOES NOT
 PROVIDE MUCH HELP.IF THE SPECIFIC PLAN COULD BE
 IDENTIFIED FOR WHERE THESE VENTS CONNECT I COULD LOCATE
 & REVIEW THESE ITEMS MUCH QUICKER.
 3) SHT. P3.04 - THERE IS A SECTION OF VENT THAT GOES
 NOWHERE. IT APPEARS TO BE A TYPO ERROR.
  
 PLEASE CONTACT ME SO WE CAN SET UP A MEETING TO DISCUSS
 THESE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-21 Cont ID  
Sent By tklarge Date 2014-12-21 Time 05:28 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 12:55 Sent To  
Notes
2014-12-20 13:34:261)SHT. GI 101 - PLUMBING FIXTURE COUNT - THE CHART
 SHOWS "0"REQUIRED URINALS FOR THE ASSEMBLY AND BUSINESS
 OCCUPANCIES BUT ALSO SHOWS 11 PROVIDED. CLARIFY.THE
 TABLE READS THAT 67% MAXIMUM SUBSTITUTION FOR THE
 BUSINESS OCCUPANCY. THE BOX SHOULD READ 50%
 SUBSTITUTION TO CORRELATE WITH NOTE #2 AND THE FL.
 PLUMBING CODE SEC.419.2.
 2) SHT. P1.02 - 4" STORM RISER UP TO THE DECK DRAIN -
 THE MAXIMUM SQUARE FOOTAGE A HORIZONTAL 4" STORM DRAIN
 CAN ACCOMMODATE IS 1504 SQUARE FEET AT AN 1/8" SLOPE
 PER TABLE 1106.3 OF THE 2010 FL. PLBG. CODE. INDCATE
 THE SLOPE OF THE STORM DRAIN.
 3) SHT.P1.03 - SHOW THE SQUARE FOOTAGE DRAINING INTO
 EACH STORM RISER AND ALSO THE SQUARE FOOTAGE THAT THE
 6" & 8" HORIZONTAL STORM DRAINS ARE CARRYING. COMPLY
 WITH TABLE 1106.3 OF THE FPC.
 4) SUBMIT MANUFACTURER SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SENSING SUMP PUMP. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 5) THERE IS NOLOWER LEVEL NORTH PLUMBING PLAN IN THIS
 REVISION SUBMITTAL. CLARIFY.
 6 )SHT. P2.02 - PROVIDE A MATCH LINE ON THE LEFT SIDE
 (SW SIDE) OF THE PLAN FOR THE CONTINUATION OF THE
 PLUMBING SYSTEM. DO THE SAME FOR ALL SHEETS.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SHT. P2.02 - REFERS TO AN ENLARGED PLAN #2 ON SHT.
 P.206 FOR CONTINUATION OF PLUMBING WATER LINES. THE
 ENLARGED PLAN #2 ON P2.06 DOES NOT CORRELATE WITH THE
 AREA ON P2.02. THE ENLARGED PLAN #2 IS FOR CAFETERIA
 #137 AND P2.02 IS FOR THE MAIN KITCHEM #135.
 8) SHT. P2.04 - THE BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED WITH VACUUM RELIEF VALVES PER 2010 FPC SEC.
 504.2.
 9) SHT. P2.06 - REFERS TO SHT. P2.02 FOR THE
 CONTINUATION OF PLUMBING FOR THE EMPLOYEE CAFETERIA
 #137.THIS AREA IS NOT SHOWN ON SHT.P2.02. CLARIFY.
 10) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE
 CONTINUATION OF SERVICE LINES FOR THE PLUMBING. WILL
 THESE REVISIONS TO THE PLUMBING / GAS SYSTEMS AFFECT
 THEIR LOCATIONS SHOWN ON THE CIVIL DRAWINGS? IF SO ,
 SUBMIT REVISED CIVIL DRAWINGS FOR REVIEW.
 11) SHT. P3.04 - SHOW THE CONTINUATION/ CONNECTION
 POINTS OF THE 2" & 3" VENTS ON THE GREASY WASTE SYSTEM.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 12) SHT.P3.04 - RISER "E" - THE FLOOR DRAINS APPEAR TO
 BE MORE THAN 12 FEET FROM A VENT/VENTED LINE. SEE TABLE
 906.1.2010 FPC. THERE ARE OTHER FIXTURE DRAINS THAT ARE
 ALSO IN VIOLATION.
 13) SHT.S 201 - ELEVATOR PIT SECTION DETAIL#14 - THE
 DEPTH OF THE SUMP PIT SHALL BE A MIN. OF 23 INCHES PER
 2010 FPC SEC.712.3.2.
 **NOTE** - IT WOULD BE MUCH EASIER TO LOCATE AND
 SPECIFY THE AREAS OF THE DEFICIENCIES ON THE ENLARGED
 PLANS IF ALL THE GRID LINES WERE IDENTIFIED ON THE
 PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By skennedy Date 2015-04-09 Time 12:00 Rev Time 0.00
Received By skennedy Date 2015-04-09 Time 12:00 Sent To  
Notes
***NONE***