Plan Review Details - Permit 14110720
Plan Review Stops For Permit 14110720
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-12-29 Cont ID  
Sent By shill Date 2014-12-29 Time 15:49 Rev Time 0.00
Received By shill Date 2014-12-29 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-12-20 Cont ID  
Sent By shill Date 2014-12-20 Time 10:11 Rev Time 0.00
Received By shill Date 2014-12-20 Time 10:11 Sent To  
Notes
2014-12-20 10:17:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE HAVE THE QUALIFIER CALL ME. THE INSTALLATION
 SCHEDULE MAY BE REDLINED FOR ISSUANCE (2ND REQUEST).
  
 PLEASE SEE COMMENTS FROM REVIEWS 2 AND 4. THE SAME
 INSTALLATION SCHEDULE WAS SUBMITTED EXCEPT THAT THE
 COLUMN "SHUTTER INSTALLED VERTICAL/HORIZONTAL" WAS
 CHANGED FROM "V" TO "H". THIS IS NOT CORRECT -
 ACCORDION SHUTTERS ARE INSTALLED VERTICALLY.
  
 SINCE THE SAME INSTALLATION SCHEDULE WAS SUBMITTED, THE
 SAME COMMENTS APPLY. PLEASE HAVE THE QUALIFIER CONTACT
 ME. DO NOT RESUBMIT THE SAME DOCUMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-12-18 Cont ID  
Sent By shill Date 2014-12-18 Time 07:32 Rev Time 0.00
Received By shill Date 2014-12-18 Time 07:24 Sent To  
Notes
2014-12-18 07:31:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE HAVE THE QUALIFIER CALL ME. THE INSTALLATION
 SCHEDULE MAY BE REDLINED FOR ISSUANCE.
  
 RESUBMITTAL SHEET STATES THAT "A DATED BUT OTHERWISE
 UNCHANGED INSTALLATION SCHEDULE ARE ATTACHED." THIS
 INSTALLATION SCHEDULE HAD COMMENTS, SEE REVIEW #2.
  
 TO RECAP - REVIEW 1 DID NOT INCLUDE AN INSTALLATION
 SCHEDULE.
  
 REVIEW 2 - INSTALLATION SCHEDULE SUBMITTED BUT HAD
 CORRECTIONS.
  
 REVIEW 3 - A MARKED PRODUCT APPROVAL WAS SUBMITTED, BUT
 A NEW INSTALLATION SCHEDULE WAS NOT PROVIDED.
  
 REVIEW 4 - THE SAME INSTALLATION SCHEDULE AS REVIEW 2
 WAS SUBMITTED.
  
 AS EXPEDITED PLAN REVIEW HAS BEEN REQUESTED, IT APPEARS
 THAT THERE IS SOME URGENCY FOR THIS PROJECT. PLEASE
 HAVE THE QUALIFIER CONTACT ME IF HE WOULD LIKE TO
 DISCUSS A REDLINED PLAN FOR ISSUANCE. IF THE QUALIFIER
 DOES NOT WISH TO CALL ME, PLEASE SEE COMMENTS FROM
 REVIEW #2 AND REVISE THE INSTALLATION SCHEDULE
 ACCORDINGLY AND RESUBMIT.
  
 FOR YOUR CONVENIENCE, COMMENTS FROM REVIEW #2 ARE:
  
  
 1. FBC 2010 RESIDENTIAL 301, FASTENING PROPOSED DOES
 NOT MEET THE REQUIREMENTS OF THE PRODUCT APPROVAL.
  
 "SHUTTER CONNECTION MOUNTING TYPE" COLUMN ON THE
 INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE NAMING
 CONVENTION IN THE PRODUCT APPROVAL. SEE SHEETS 14 AND
 15. "WALL MOUNT" IS PROPOSED. ON SHEETS 14 AND 15,
 CONNECTION TYPES "H" AND "K" ARE CIRCLED. PLEASE REVISE
 THIS COLUMN TO CORRELATE WITH THE PRODUCT APPROVAL.
  
 2. CONNECTION TYPE K IS A FLOOR MOUNT AND REQUIRES A
 CONCRETE SUBSTRATE. "CONCRETE BLOCK" IS STATED AS THE
 SUBSTRATE ON THE INSTALLATION SCHEDULE. A FLOOR IS
 TYPICALLY FORMED AND POURED CONCRETE. PLEASE CLARIFY,
 OR REVISE EITHER CONNECTION TYPE AND/OR SUBSTRATE.
  
 3. THE ITEMS CIRCLED ON THE PRODUCT APPROVAL APPEAR TO
 INDICATE CONNECTION TYPE "H" WITH 10" SPACING CIRCLED
 AT THE TOP, BUT THIS IS A FLOOR CONNECTION (CAN ONLY BE
 USED AT THE FLOOR).
  
 "K" IS ALSO CIRCLED WITH 7" SPACING, APPEARS TO BE THE
 BOTTOM CONNECTION TYPE, SEE ITEM 2 REGARDING SUBSTRATE.
  
 PROPOSED INSTALLATION IS NOT CLEAR; COMPLIANCE CANNOT
 BE DETERMINED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-12 Cont ID  
Sent By shill Date 2014-12-12 Time 07:40 Rev Time 0.00
Received By shill Date 2014-12-12 Time 07:36 Sent To  
Notes
2014-12-12 07:38:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PLAN REVIEW #1:
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 PLAN REVIEW #1 DID NOT INCLUDE INSTALLATION SCHEDULE.
  
 PLAN REVIEW #2 INCLUDED AN INSTALLATION SCHEDULE BUT
 DID NOT COMPLY WITH THE REQUIREMENTS OF THE PRODUCT
 APPROVAL.
  
 THIS REVIEW (PLAN REVIEW #3) INCLUDES A NEW MARKED
 PRODUCT APPROVAL BUT A NEW INSTALLATION SCHEDULE WAS
 NOT PROVIDED. THE INSTALLATION SCHEDULE IS REQUIRED FOR
 BOTH PLAN REVIEW AND INSPECTIONS. PLEASE COMPLETE A NEW
 INSTALLATION SCHEDULE. INCLUDE A DATE ON THE
 INSTALLATION SCHEDULE,.
  
 2. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS OF DOCUMENTS FOR PERMIT ISSUANCE. MARK OLD SHEETS
 "VOID."
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-04 Cont ID  
Sent By shill Date 2014-12-04 Time 18:27 Rev Time 0.00
Received By shill Date 2014-12-04 Time 18:13 Sent To  
Notes
2014-12-04 18:37:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. FBC 2010 RESIDENTIAL 301, FASTENING PROPOSED DOES
 NOT MEET THE REQUIREMENTS OF THE PRODUCT APPROVAL.
  
 "SHUTTER CONNECTION MOUNTING TYPE" COLUMN ON THE
 INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE NAMING
 CONVENTION IN THE PRODUCT APPROVAL. SEE SHEETS 14 AND
 15. "WALL MOUNT" IS PROPOSED. ON SHEETS 14 AND 15,
 CONNECTION TYPES "H" AND "K" ARE CIRCLED. PLEASE REVISE
 THIS COLUMN TO CORRELATE WITH THE PRODUCT APPROVAL.
  
 2. CONNECTION TYPE K IS A FLOOR MOUNT AND REQUIRES A
 CONCRETE SUBSTRATE. "CONCRETE BLOCK" IS STATED AS THE
 SUBSTRATE ON THE INSTALLATION SCHEDULE. A FLOOR IS
 TYPICALLY FORMED AND POURED CONCRETE. PLEASE CLARIFY,
 OR REVISE EITHER CONNECTION TYPE AND/OR SUBSTRATE.
  
 3. THE ITEMS CIRCLED ON THE PRODUCT APPROVAL APPEAR TO
 INDICATE CONNECTION TYPE "H" WITH 10" SPACING CIRCLED
 AT THE TOP, BUT THIS IS A FLOOR CONNECTION (CAN ONLY BE
 USED AT THE FLOOR).
  
 "K" IS ALSO CIRCLED WITH 7" SPACING, APPEARS TO BE THE
 BOTTOM CONNECTION TYPE, SEE ITEM 2 REGARDING SUBSTRATE.
  
 PROPOSED INSTALLATION IS NOT CLEAR; COMPLIANCE CANNOT
 BE DETERMINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 14:04 Rev Time 0.00
Received By shill Date 2014-12-01 Time 14:04 Sent To  
Notes
2014-12-01 14:04:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-12-29 Cont ID  
Sent By shill Date 2014-12-29 Time 15:49 Rev Time 0.00
Received By shill Date 2014-12-29 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-12-20 Cont ID  
Sent By shill Date 2014-12-20 Time 10:17 Rev Time 0.00
Received By shill Date 2014-12-19 Time 10:10 Sent To  
Notes
2014-12-20 10:11:05****EXPEDITED****
  
 TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-18 Cont ID  
Sent By shill Date 2014-12-18 Time 07:32 Rev Time 0.00
Received By shill Date 2014-12-17 Time 16:01 Sent To B
Notes
2014-12-17 16:02:09TO S.HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-12 Cont ID  
Sent By shill Date 2014-12-12 Time 07:40 Rev Time 0.00
Received By shill Date 2014-12-11 Time 16:29 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-04 Cont ID  
Sent By shill Date 2014-12-04 Time 18:37 Rev Time 0.00
Received By shill Date 2014-12-03 Time 18:41 Sent To  
Notes
2014-12-03 18:41:53SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 14:04 Rev Time 0.00
Received By shill Date 2014-11-19 Time 12:36 Sent To  
Notes
2014-11-19 12:36:35ROUTED TO BUILDING $5000 & UNDER