Plan Review Details - Permit 14110707
Plan Review Stops For Permit 14110707
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-26 Cont ID  
Sent By jgomez Date 2014-11-26 Time 13:32 Rev Time 0.00
Received By jgomez Date 2014-11-26 Time 13:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-20 Cont ID  
Sent By jgomez Date 2014-11-20 Time 18:03 Rev Time 0.00
Received By jgomez Date 2014-11-20 Time 17:56 Sent To  
Notes
2014-11-20 18:13:47RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- MODIFIED BITUMEN NOA 13-0424.14 SUBMITTED EXPIRED ON
 11/06/14. NEED TO PROVIDE 2 CURRENT NOA'S.
 REQUIRED BY DCA RULE 9N-3.
  
 2- ENGINEER DOING THE RAS 117 CALCULATIONS TO REVISE
 INFORMATION. NEED TO REFER TO THE CURRENT NOA AS
 REQUIRED BY ITEM #1 ABOVE. PROVIDE 2 SIGNED AND SEALED
 COPIES OF THE REVISED CALCULATIONS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-26 Cont ID  
Sent By jgomez Date 2014-11-26 Time 13:22 Rev Time 0.00
Received By jgomez Date 2014-11-24 Time 16:50 Sent To  
Notes
2014-11-24 16:50:49INCOMING SENT TO J. GOMEZ'S DESK. JW