Plan Review Details - Permit 14110637
Plan Review Stops For Permit 14110637
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-30 Cont ID  
Sent By jwitmer Date 2015-01-30 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2015-01-30 Time 08:32 Sent To  
Notes
2015-01-28 07:42:44NEW DRAWINGS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-16 Cont ID  
Sent By JWITMER Date 2015-01-16 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2015-01-16 Time 07:31 Sent To  
Notes
2015-01-16 08:58:15BUILDING PLAN REVIEW
 PERMIT: 14110637
 ADD: 477 S. ROSEMARY # 302-328
 CONT: FASTRACK
 TEL: (561)722-8848 / JOHN LESH
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JAN. 16/ 2015
 ACTION: BUILDING PROVISO:
  
 1) SHEET A-3 DETAIL # 2 INDICATES THE USE OF ARMSTRONG
 SERPENTINA WAVE SYSTEM DROPPED CEILINGS, NOTE INDICATES
 TO PROVIDE MANUFACTURER SPECS.
 PLEASE SUBMIT THE MANUFACTURED SPECS FOR THIS PROJECT.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-21 Cont ID  
Sent By jwitmer Date 2014-11-21 Time 08:33 Rev Time 0.00
Received By jwitmer Date 2014-11-21 Time 06:22 Sent To  
Notes
2014-11-21 08:33:22BUILDING PLAN REVIEW
 PERMIT: 14110637
 ADD: 477 S. ROSEMARY # 302-328
 CONT: FASTRACK
 TEL: (561)722-8848 / JOHN LESH
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 21/ 2014
 ACTION: DENIED
  
 1) SHEET CS-1 PROJECT DATA, PLEASE PROVIDE THE BUILDING
 TYPE OF CONSTRUCTION, THIS MAY EFFECT THE TYPE OF
 MATERIALS TO BE PLACED WITHIN THE BUILDING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS
 (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 2A) SHEET A1.1 INDICATES ROOMS 324 A BUSINESS LOUNGE &
 ROOM 325 KITCHEN, PLEASE PROVIDE THE SQ. FT. AREA OF
 EACH AND THE PROPOSED OCCUPANT LOAD.
 THIS USAGE AREA APPEARS TO BE AN ASSEMBLY AREA PLEASE
 PROVIDE THE SQ. FT AREA OF WHAT APPEARS TO BE AN
 ASSEMBLY USAGE TO DETERMINE IF THIS AREA IS TO BE
 CLASSIFIED AS AN ACCESSORY OCCUPANCY OR MIXED
 OCCUPANCY. PLEASE REVIEW THE 2010 FBC-B 508.2, &
 508.21.
  
 2B) IF THIS DOES BECOME A MIXED USE OCCUPANCY THE PLANS
 HAVE NOT DECLARED IF THE TENANCY WAS DESIGNED TO
 NONSEPARATED OCCUPANCIES (508.3) OR
 SEPARATED OCCUPANCIES (508.4).
  
 3A) THIS SHEET WITHIN THE KITCHEN SHOWS A STOVE BUT NO
 MENTION OF A HOOD IS INDICATED ON THE ARCHITECTURAL NOR
 M2.1A. SEE FBC-B 904.2 / 904.2.1 COMMERCIAL HOOD.
 PLEASE NOTE PERMIT 02081582 WAS A PERMIT RESIDENTIAL
 PERMIT THAT COMBINED UNIT# 326 & 328 TOGETHER. LATER
 PERMIT # 04080408 WAS FOR A COMMERCIAL INTERIOR BUILD
 OUT OF THIS SPACE EXPIRED!!!!!
  
 3B) PLEASE SHOW THE KITCHEN SINK IN ROOM # 325 IN
 CONFORMANCE WITH 2010 FBC- ACCESSIBILITY CODE 606.1-5.
  
 4) SHEET A-3:
 4A) DETAIL # 1 INDICATES VARIOUS DROP CEILINGS &
 SOFFITS, THERE ARE NO DETAILS FOR STUD THICKNESS/
 GAUGE,TYPE OF MATERIAL, SPACING, HOW THE DROPS ARE
 GOING TO BE ANCHORED TO THE STRUCTURAL MEMBERS AND WHAT
 TYPE OF FINISH AND THICKNESS WILL BE CLADDING THE
 STRUCTURES?
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: DROPPED
 CEILING & SOFFITS
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
  
 4B) DETAIL # 2 INDICATES THE USE OF ARMSTRON SERPENTINA
 WAVE SYSTEM DROPPED CEILINGS, NOTE INDICATES TO PROVIDE
 MANUFACTURER SPECS. 107.2.1.3 ADDITONAL INFORMATION IS
 REQUIRED. AGAIN WHAT TYPE OF STRUCTURAL MEMBERS ARE
 THESE ELEMENTS GOING TO BE SECURED AND WITH WHAT
 MATERIAL.
  
 4C) NOTE IN DETAIL INDICATES THE USE OF PLYWOOD
 BACKING, THIS MAY BE OF CONCEERN IF THIS BUILDING IS
 DECLARED EITHER A TYPE I OR II, NOT DECLAED, SEE
 COMMENT # 1.
  
 4D) SHEET A3 & A4 BOTH INDICATE THE WALL SYSTEMS ARE BY
 OTHERS, PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B
 803.1.1 INTERIOR WALL FINISHES & CEILING FINISHES CAN
 BE MET?
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 12:44 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 12:19 Sent To  
Notes
2014-11-21 12:45:18A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, ACCESS CONTROL SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-18 Cont ID  
Sent By pleduc Date 2014-11-18 Time   Rev Time 0.00
Received By pleduc Date 2014-11-18 Time 14:13 Sent To  
Notes
2014-11-18 14:29:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 SHEET A 1.1 INDICATES A KITCHEN AND A DRWING THAT
 APPEARS TO BE A STOVE TOP. ANY COOKING EQUIPMENT SHALL
 BE INSTALLED WITHIN THE REQUIREMENTS OF NFPA 96.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-09 Cont ID  
Sent By   Date 2015-02-09 Time   Rev Time 0.00
Received By jgomez Date 2015-01-26 Time 07:53 Sent To  
Notes
2015-01-28 07:54:20RE-SUBMITTAL SENT TO C16 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-24 Cont ID  
Sent By hmoser Date 2015-01-24 Time 08:11 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 11:55 Sent To  
Notes
2015-01-14 13:36:51C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-25 Cont ID  
Sent By hmoser Date 2014-11-25 Time 14:51 Rev Time 0.00
Received By hmoser Date 2014-11-17 Time 18:57 Sent To  
Notes
2014-11-17 18:59:18C16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-02-09 Cont ID  
Sent By hmoser Date 2015-02-09 Time 11:24 Rev Time 0.00
Received By hmoser Date 2015-02-09 Time 09:43 Sent To  
Notes
2015-02-09 11:14:58PASS PROVISO
 1) PROVIDE ENGINEER DETAIL ON CURB TO ROOF TIEDOWN
 SHOWING TYPE, SIZE AND SPACING OF ANCHORS.
 PER SECTION 301.12 WIND RESISTANCE FBC (M) 2010
 2) REFER TO SECTION 304.1 GENERAL PROVIDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS ON AIR CONDITIONING
 EQUIPMENT.
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-01-24 Cont ID  
Sent By HMOSER Date 2015-01-24 Time 08:10 Rev Time 0.00
Received By hmoser Date 2015-01-24 Time 07:46 Sent To  
Notes
2015-01-24 08:10:40PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER ON HOW
 THE RTU CURB IS ANCHORED TO THE ROOF PER
 SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 2) FRESH AIR CALCULATIONS PER TABLE 403.3
 MINIMUM VENTILATION RATES 2010 FBC (M)
 3) PROVIDE ENERGY CALCULATIONS PER SECTION
 503.2.1 CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By hmoser Date 2014-11-25 Time 14:51 Rev Time 0.00
Received By hmoser Date 2014-11-25 Time 14:30 Sent To  
Notes
2014-11-25 14:51:24PLAN DENIED
  
 1) FRESH AIR DAMPER REQUIRED AT EACH UNIT
 503.2.4.4 SHUT OFF DAMPER CONTROL 2010 FLORIDA ENERGY
 CODE
 2) REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING
 LOADS 2010 FLORIDA ENERGY CODE
 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLAN SECTION
 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-24 Cont ID  
Sent By TKLARGE Date 2015-01-24 Time 05:38 Rev Time 0.00
Received By tklarge Date 2015-01-24 Time 05:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 06:26 Rev Time 0.00
Received By tklarge Date 2014-11-22 Time 05:26 Sent To  
Notes
2014-11-22 06:23:281) SHT. A-5 - TOILET ELEVATION - 1/A-1 - THE TOP OF THE
 TOILET FROM THE FININSHED FLOOR TO THE SEAT SHALL BE
 17-19 INCHES MAXIMUM TO THE TOP OF THE SEAT PER 2010
 FAC SEC. 604.4 NOT 19-20 INCHES AS SHOWN.
 2) THE CLEAR KNEE SPACE UNDER THE LAVATORY SHALL BE 27
 INCHES PER FAC SEC.306.3. SHT. A-5.
 3) SHT. A-5 - THE TOILET PAPER DISPENSER SHALL BE 7-9
 INCHES IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER PER FAC SEC.604.7.
 4) SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 INSTANTANEOUS WATER HEATER.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) SHT.P2.1B - CLARIFY "EXISTING TUB TO BE REMOVED."
 THERE IS NO TUB SHOWN ON SHT. A-1.2.
 6) SUBMIT A SANITARY AND WATER RISER FOR ALL NEW WORK
 TO BE INSTALLED. WPB AMEND. TO 2010 FBC
 SEC.107.3.5.1.3.
 7) KITCHEN SINK/COUNTER SHALL COMPLY W/FAC SEC.212.3 &
 804.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-02-03 Cont ID  
Sent By eschneid Date 2015-02-03 Time 17:43 Rev Time 0.25
Received By eschneid Date 2015-02-03 Time 13:20 Sent To  
Notes
2015-01-28 07:44:30NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-01-23 Cont ID  
Sent By ESCHNEID Date 2015-01-23 Time 17:06 Rev Time 0.50
Received By eschneid Date 2015-01-23 Time 17:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-24 Cont ID  
Sent By eschneid Date 2014-11-24 Time 10:44 Rev Time 0.50
Received By eschneid Date 2014-11-24 Time 10:43 Sent To  
Notes
2014-11-24 11:37:43FAILED
  
 1) PLEASE PROVIDE VERIFICATION (CROSS SECTIONS,
 SIGHTLINE DRAWINGS, ETC.) THAT THE NEW ROOFTOP
 EQUIPMENT (RTUS, HPS, GVS, RVS) COMPLIES WITH THE
 CITYPLACE DRI ROOFTOP MECHANICAL EQUIPMENT SCREENING
 REQUIREMENTS.
  
 2) REMAINDER OF PLANS COMPLY WITH ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.