Plan Review Details - Permit 14110618
Plan Review Stops For Permit 14110618
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-20 Cont ID  
Sent By jwitmer Date 2014-11-20 Time 17:42 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 17:01 Sent To  
Notes
2014-11-20 17:32:32BUILDING PROVISO:
 2010 FBC-B 1006.3.9 EXIT LIGHTING. SIGNS INSTALLED
 AS PROJECTIONS FROM A WALL OR CEILING WITHIN THE MEANS
 OF EGRESS SHALL PROVIDE VERTICAL CLEARANCE NO LESS THAN
 80 INCHES (2134 MM) FROM THE WALKING SURFACE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 11:13 Rev Time 0.00
Received By dhayes Date 2014-12-02 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-19 Cont ID  
Sent By pleduc Date 2014-11-19 Time   Rev Time 0.00
Received By pleduc Date 2014-11-18 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-13 Cont ID  
Sent By hmoser Date 2014-12-13 Time 08:49 Rev Time 0.00
Received By hmoser Date 2014-12-12 Time 17:07 Sent To  
Notes
2014-12-12 17:07:55TO HM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 11:13 Rev Time 0.00
Received By dhayes Date 2014-11-17 Time 06:42 Sent To  
Notes
2014-11-18 06:50:25B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-11-20 Cont ID  
Sent By jwitmer Date 2014-11-20 Time 17:33 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 17:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-12-13 Cont ID  
Sent By hmoser Date 2014-12-13 Time 08:22 Rev Time 0.00
Received By hmoser Date 2014-12-13 Time 08:08 Sent To  
Notes
2014-12-13 08:22:33LINED METAL DUCT CAN BE PAINTED.
 FIBERGLASS OR FLEX CAN NOT BE PAINTED.
 REFER TO SECTION 603.5 NONMETALLIC
 DUCT. 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-01 Cont ID  
Sent By rbergsma Date 2014-12-01 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-01 Time   Sent To  
Notes
2014-12-01 10:59:26PROVIDE PAINTED DUCT WRAP ACCEPTANCE (WARRANTY) FROM
 DUCT WRAP MANUFACTURER.