Plan Review Details - Permit 14110596
Plan Review Stops For Permit 14110596
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-02-06 Cont ID  
Sent By rmcdouga Date 2015-02-06 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2015-02-06 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-01-27 Cont ID  
Sent By rmcdouga Date 2015-01-27 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2015-01-27 Time 15:38 Sent To  
Notes
2015-01-27 16:36:29PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT
 CLEAR AND APPEARS TO BE INCORRECT.
 A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF
 AREAS APPEAR TO BE INCORRECT FOR A STRUCTURE LOCATED IN
 EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN
 ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE
 DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1
 AND ASCE 7-10 CHAPTER 30.
  
 B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE
 THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER
 ROOF AREAS. FBC 107.2.1.3
  
 C) FOR EACH OF THE THREE ROOF ZONES. SPECIFY THE
 FASTENER SPACING AT THE 3" LAP AND IN THE (TWO OR MORE
 IF REQUIRED) STAGGERED ROWS IN THE CENTER OF THE
 SHEETS.
  
 2) RAS 117 SECTION 8.1 STATES THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4 INCHES ON CENTER.
 THE DOCUMENT FROM JOHN D. BUEROSSE, P.E. STATES THAT
 THE LAPS SHOULD BE NAILED AT 3" APART IN ZONE 3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-16 Cont ID  
Sent By rmcdouga Date 2014-12-16 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2014-12-16 Time 07:12 Sent To  
Notes
2014-12-16 09:00:04PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT
 CLEAR AND APPEARS TO BE INCORRECT.
 A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF
 AREAS APPPEAR TO BE TOO LOW FOR A STRUCTURE LOCATED IN
 EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN
 ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE
 DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1
 AND ASCE 7-10 CHAPTER 30.
  
 B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE
 THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER
 ROOF AREAS. FBC 107.2.1.3
  
 C) FOR EACH OF THE THREE ROOF ZONES. SPECIFY THE
 FASTENER SPACING AT THE 3" LAP AND IN THE TWO STAGGERED
 ROWS IN THE CENTER OF THE SHEETS. THE FASTENER SPACING
 THAT IS SPECIFIED IN THE NOA IS SUFFICIENT FOR THE
 FIELD ROOF AREA (ROOF ZONE 1).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By rmcdouga Date 2014-11-18 Time 19:07 Rev Time 0.00
Received By rmcdouga Date 2014-11-18 Time 18:43 Sent To  
Notes
2014-11-19 10:45:02PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT
 CLEAR AND APPEARS TO BE INCORRECT.
 A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF
 AREAS APPPEAR TO BE TOO LOW FOR A STRUCTURE LOCATED IN
 EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN
 ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE
 DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1
 AND ASCE 7-10 CHAPTER 30.
  
 B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE
 THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER
 ROOF AREAS. FBC 107.2.1.3
  
 C) SPECIFY THE DIMENSIONS OF THE PERIMETER AND CORNER
 ROOF AREAS. SHOW THE CALCULATIONS THAT WERE USED TO
 DETERMINE THEM. FBC 107.2.1.3
  
 2) THE VALUE FOR THE WORK OF $11,500.00 IS LOW AND HAS
 BEEN INCREASED TO $15,900.00 BASED ON MARSHALL & SWIFT
 VALUATION. FBC 109.3
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-06 Cont ID  
Sent By rmcdouga Date 2015-02-06 Time 14:15 Rev Time 0.00
Received By rmcdouga Date 2015-02-03 Time 12:03 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-27 Cont ID  
Sent By rmcdouga Date 2015-01-27 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2015-01-27 Time 15:38 Sent To  
Notes
2015-01-27 15:38:37SENT TO R MCDOUGAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-16 Cont ID  
Sent By rmcdouga Date 2014-12-16 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2014-12-15 Time 16:06 Sent To  
Notes
2014-12-15 16:06:44SENT TO R MCDOUGAL