Plan Review Details - Permit 14110574
Plan Review Stops For Permit 14110574
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-23 Cont ID  
Sent By jwitmer Date 2014-12-23 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2014-12-23 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 15:39 Sent To  
Notes
2014-12-02 16:32:26BUILDING PLAN REVIEW
 PERMIT: 14110574
 ADD: 3500 45TH ST
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 02/ 2014
 ACTION: DENIED
  
 1A) PLEASE SPECIFY WHAT TYPE OF STORAGE IS GOING TO
 OCCUPY THE BACK HALF OF THE TENANT SPACE S1 OR S2. IS
 THIS AREA GOING TO STORE VEHICLES REQUIRING FIRE RATED
 WALLS? 2010 FBC-B TABLE 508.4.
  
 1B) IF THE STORAGE OCCUPANCY IS GOING TO BE FOR
 VEHICLES THEN THE WALL TYPE BETWEEN THE BUSINESS & S2
 OCCUPANCY WILL REQUIRE A 1 HOUR FIRE RATED WALL TO THE
 ROOFTOP DECK. TABLE 508.4 & OPENING PROTECTIVES SEE
 TABLE 715.4.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 15:30 Rev Time 0.00
Received By skennedy Date 2014-12-12 Time 15:30 Sent To  
Notes
2014-12-12 15:30:48NO SHOWN ELECTRICAL SHOWN AT THIS TIME. DEMONSTRATE USE
 OF SPACE UPON RESUBMITTAL SO APPLICABLE ELECTRICAL
 CRITERIA MAY BE DETERMINED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-16 Cont ID  
Sent By pleduc Date 2014-12-16 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By pleduc Date 2014-12-01 Time   Rev Time 0.00
Received By pleduc Date 2014-12-01 Time 11:41 Sent To  
Notes
2014-12-01 11:52:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-23 Cont ID  
Sent By jwitmer Date 2014-12-23 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2014-12-12 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 15:41 Rev Time 0.00
Received By skennedy Date 2014-11-14 Time 15:41 Sent To  
Notes
2014-12-01 09:42:35B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-12-23 Cont ID  
Sent By jwitmer Date 2014-12-23 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2014-12-23 Time 06:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 15:39 Rev Time 0.00
Received By skennedy Date 2014-12-12 Time 15:39 Sent To  
Notes
2014-12-12 15:40:23DEMONSTRATE USE OF SPACE UPON RESUBMITTAL SO APPLICABLE
 IMPACT CRITERIA MAY BE DETERMINED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 15:31 Rev Time 0.00
Received By skennedy Date 2014-12-12 Time 15:30 Sent To  
Notes
2014-12-12 15:32:40NO SHOWN MECHANICAL SHOWN AT THIS TIME. DEMONSTRATE USE
 OF SPACE UPON RESUBMITTAL SO APPLICABLE MECHANICAL
 CRITERIA MAY BE DETERMINED.

Review Stop P PLUMBING
Rev No 2 Status N Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 10:02 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 15:36 Rev Time 0.00
Received By skennedy Date 2014-12-12 Time 15:35 Sent To  
Notes
2014-12-12 15:37:17NO PLUMBING SHOWN AT THIS TIME. DEMONSTRATE USE OF
 SPACE UPON RESUBMITTAL SO APPLICABLE PLUMBING CRITERIA
 MAY BE DETERMINED.