Plan Review Details - Permit 14110550
Plan Review Stops For Permit 14110550
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-28 Cont ID  
Sent By JWITMER Date 2015-01-28 Time 16:06 Rev Time 0.00
Received By jwitmer Date 2015-01-27 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-15 Cont ID  
Sent By jwitmer Date 2014-11-15 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2014-11-15 Time 12:30 Sent To  
Notes
2014-11-15 14:09:06BUILDING PLAN REVIEW
 PERMIT: 14110550
 ADD: 1855 PALM BEACH LAKES SUITE # B-09
 CONT: FINE LINE CONSTRUCTION
 TEL: (561)582-7880 X 306
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 15/ 2014
 ACTION: DENIED
  
 NOTE: BEFORE PLAAN SUBMITTAL TO THE BUILDING
 DEPARTMENT, THE PLANS ARE SUPPOSE TO HAVE THE STAMPED
 LANDLORD APPROVAL BY NEW ENGLAND DEVELOPMNT PALM BEACH
 OUTLETS SKE GROUP TENANT COORDINATOR.
  
 1) THE COVERSHEET:
  
 1A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 (3.) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503). THE SHELL PERMIT FOR BUILDING B2 IS A
 BUILDING TYPE IIB.
  
 1B) THE CLASSIFICATION OF THIS WORK IS SHOWN AS UNDER
 THE 2010 FL. EXST, BLDG CODE, AS A LEVEL II. PLEASE
 NOTE THERE HAS ONLY BEEN PROVIDED A CERTIFICATE OF
 COMPLETION UNDER THE SHELL PERMIT. THIS BEING THE FIRST
 TENANCY OF THIS SPACE WILL RECEIVE A CERTIFICATE OF
 OCCUPANCY AND UNDER THE
 2010 FBC-B FOR NEW BUILDINGS.
 111.4 CERTIFICATE OF COMPLETION.
  
 2) PLEASE SEE SHEET S2.0 NOTE MEZZANINE FRAMING NOTE M3
 INDICATES THE USE OF 2 LAYERS OF 3/4 INCH TYPE X
 PLYWOOD. PLEASE REVIEW FBC-B 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3.
  
 3A) SHEET A1.0 & A2.0 NOTE # 28 BOTH SHEETS INDICATE
 WOOD FRAME STAIRS, SEE STAIR DETAIL DRAWINGS. NONE
 FOUND. SHEET S2.0 NOTE INDICATES THE STAIRS ARE TO BE
 PRE-ENGINEERED WOOD STAIRS. NO DETAILS, NO DESIGN
 CRITERIA PROVIDED FOR LIVE LOADS FBC-B TABLE 1607.
 SHEET A1.3 SHOWS A PROPOSED DTAIL # 8/ A3.1, NO SUCH
 SHEET IN PLANS.
  
 1009.6 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL BE
 BUILT OF MATERIALS CONSISTENT WITH THE TYPES PERMITTED
 FOR THE TYPE OF CONSTRUCTION OF THE BUILDING, EXCEPT
 THAT WOOD HANDRAILS SHALL BE PERMITTED FOR ALL TYPES OF
 CONSTRUCTION. TYPE IIB CONSTRUCTION.
  
 3B) THERE IS NO DESIGN INFORMATION AS WELL FOR THE
 HANDRAIL SYSTEM AS REQUIRED BY FBC-B 1012.
  
 3C) ARE THESE STAIRS GOING TO HAVE A CLOSED OR SOLID
 RISER FBC-B 1009.4.5.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 07:46 Rev Time 0.00
Received By dhayes Date 2014-12-31 Time 07:15 Sent To  
Notes
2014-12-31 07:47:54SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR HOOD EXHAUST, FIRE ALARM, ACCESS
 CONTROL SYSTEM, SECURITY, CCTV, NETWORK, DATA, AND,
 COMMUNICATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-26 Cont ID  
Sent By SCALDERO Date 2015-01-26 Time 15:19 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-24 Cont ID  
Sent By scaldero Date 2014-11-24 Time 15:57 Rev Time 0.00
Received By scaldero Date 2014-11-24 Time 15:57 Sent To  
Notes
2014-11-24 16:10:18PERMIT # 14110550
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
 COMPLY WITH ALL BUILDING PLAN REVIEWER NOTES.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR. IF THERE ARE DOUBLE DOORS, BOTH
 DOORS REQUIRE INDICATORS.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 ALL TENANT SPACES AT THE MARKETPLACE MUST BE TIED INTO
 THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH
 TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION
 OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE
 THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A
 TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE"
 FUNCTIONS DEACTIVED. RESET AND SILENCE OF AN ALARM IS
 LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY
 ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN.
 SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE
 PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR
 "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY
 REQUIRE THAT THE TENANT FACP BE REMOVED.
 PER APPROVED MASTER PLANS: MAIN FACP FOR THIS BUILDING
 IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE DEPARMENT.
 NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS OF TENANT
 WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL
 ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN
 ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII",
 OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO
 MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM
 SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED
 MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO
 THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-04 Cont ID  
Sent By skennedy Date 2015-02-04 Time 07:38 Rev Time 0.00
Received By skennedy Date 2015-01-23 Time 14:27 Sent To  
Notes
2015-01-23 14:26:35C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 07:48 Rev Time 0.00
Received By dhayes Date 2014-11-14 Time 09:23 Sent To  
Notes
2014-11-15 09:25:34C11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-11-15 Cont ID  
Sent By jwitmer Date 2014-11-15 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2014-11-15 Time 12:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-03 Cont ID  
Sent By rbergsma Date 2014-12-03 Time   Rev Time 0.75
Received By rbergsma Date 2014-12-03 Time   Sent To  
Notes
2014-12-03 09:06:21ALL PAGES APPROVED AS NOTED

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-30 Cont ID  
Sent By TKLARGE Date 2015-01-30 Time 04:59 Rev Time 0.00
Received By tklarge Date 2015-01-29 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By tklarge Date 2014-11-25 Time 13:20 Rev Time 0.00
Received By tklarge Date 2014-11-25 Time 10:51 Sent To  
Notes
2014-11-25 13:20:341) SUBMIT A SITE PLAN SHOWING THE LOCATION AND SIZE OF
 THE EXISTING GREASE TRAP. WPB AMEND. TO 2010 FPC SEC.
 107.2.1.
 2) SUBMIT CALCULATIONS THAT CONFIRM THAT THE EXISTING
 GREASE TRAP HAS THE CAPACITY FOR THIS OPERATION.
 3) THE WATER CLOSET IN THE WOMEN'S RESTROOM IS BEING
 WET VENTED AND A URINAL IS ON THE WET VENT WHICH IS IN
 VIOLATION OF THE 2010 FPC SEC.909.1.
 4) SHT. A1.3 REFERS TO DETAL A/A3.1. THERE IS NO SHT.
 A3.1 IN THE PLANS. CLARIFY.
 5) SHT. P0.2 - GAS DWG. - NOTES REFER TO GAS TABLE
 402.4 (20). THIS TABLE IS FOR PE PIPE AND THERE IS NO
 PE PIPE SHOWN ON THE DRAWING. CLARIFY.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By ESCHNEID Date 2015-02-03 Time 16:45 Rev Time 0.25
Received By eschneid Date 2015-02-03 Time 13:17 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By eschneid Date 2014-11-25 Time 16:44 Rev Time 0.50
Received By eschneid Date 2014-11-25 Time 16:44 Sent To  
Notes
2014-11-25 16:58:54FAILED
  
 1) THE PLANS DO NOT HAVE THE PB OUTLETS APPROVAL STAMP
 ON THEM.
  
 2) ALL ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED.
  
 3) PLANS COMPLY WITH ZONING.
  
  