Plan Review Details - Permit 14110539
Plan Review Stops For Permit 14110539
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-15 Cont ID  
Sent By rmcdouga Date 2014-11-15 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2014-11-15 Time 06:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2014-11-13 Time 17:21 Sent To  
Notes
2014-11-13 17:36:44PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED
 BITUMEN ROOF SYSTEM NOA NO. 13-0416.05 HAS BEEN
 SUPERSEDED. SUBMIT TWO COPIES OF THE CURRENT NOA AS
 REQUIRED BY DCA RULE 9N-3.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE THAT
 IS BEING RE-ROOFED. FBC-R 301.1
  
 3) SPECIFY THE APPROVED ASSEMBLY AND THE MAXIMUM DESIGN
 OF THE SYSTEM THAT WILL BE INSTALLED. THE STRUCTURE IS
 LOCATED IN EXPOSURE C WITH A 170 MPH WIND-SPEED. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AT PERIMETER AND CORNER ROOF AREAS
 AS INDICATED IN LIMITATION NUMBER 7 ON PAGE 32 OF THE
 NOA. FBC-R 301.1

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2014-11-13 Cont ID  
Sent By swurafti Date 2014-11-13 Time 14:48 Rev Time 0.00
Received By swurafti Date 2014-11-13 Time 14:47 Sent To  
Notes
2014-11-13 14:48:41NOT REQUIRED PER FMITTNER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-15 Cont ID  
Sent By rmcdouga Date 2014-11-15 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2014-11-14 Time 06:58 Sent To  
Notes
2014-11-15 06:59:19SENT TO R MCDOUGAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved