2014-11-25 11:37:10 | BUILDING PLAN REVIEW |
| PERMIT: 14110470 |
| ADD: 4847 FRED GLADSTONE DRIVE |
| CONT: THE WINDOW GUYS OF FLORIDA |
| TEL: (561)598-6295 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. NOV. 25/ 2014 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THIS IS UNDER A |
| MASTER/ PRIME PERMIT. PERMIT # 12050519 IS A OPEN |
| PERMIT THAT HAS NOT RECEIVED A CERTIFICATE OF |
| OCCUPANCY, OR A CERTIFICATE OF COMPLETION. IN AS SUCH |
| ANY CHANGES TO THE APPROVED PLANS WILL NEED TO BE |
| REVIEWED BY THE DESIGNER OF RECORD. NOTE IF THE PERMIT |
| SET OF ISSUED PLANS SHOWS A OPEN PORTE COCHERE, THEN |
| THE DESIGNER OF RECORD WILL NEED TO SUBMIT A REVISION |
| SHOWING THE ENCLOSING OF THIS SPACE. THE SPACE IS NO |
| LONGER CONSIDERED A OPEN STRUCTURE IT WILL BE |
| CONSIDERED ENCLOSED WITH NEW WIND LOADS AGAINST THE |
| SIDES OF THE STRUCTURE, THE STRUCTURE WILL NEED TO BE |
| EVALUATED BY THE DESIGN PROFESSIONALS FOR THE |
| ADDITIONAL LOADS TO BE IMPOSED. |
| |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: A FLOOR PLAN; SITE PLAN; ALL FENESTRATION |
| PENETRATIONS; AND ROUGH OPENING DIMENSIONS; AND ALL |
| EXTERIOR ELEVATIONS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| (1) SITE PLANS LOCATION OF STRUCTURE TO THE OVER ALL |
| SITE |
| (8) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| DESIGN LOADS |
| WIND REQUIREMENTS MISSING WIND DESIGN CRITERIA. |
| BUILDING ENVELOPE |
| |
| 2) TO BE REVIEWED BY THE DESIGNER OF RECORD BEFORE |
| SUBMITTAL TO THE BUILDING DEPARTMENT. FL 61G1-23.015 |
| (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| ETC... |
| |
| 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER |
| ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECT?S |
| OFFICE. |
| |
| WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| WHICH ARE REGULATED BY DCA RULE 9N-3 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 3) THE FLOOR PLANS SUBMITTED BY THE WINDOW GUY SHOWS |
| WINDOW TYPE A & B TOTALLY SURROUNDING THE PORT COCHERE, |
| HOW IS ENTRY TO BE GAINED THERE IS NO DOORWAY? |
| 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| TUS.ASPX FOR PERMIT STATUS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |