Plan Review Details - Permit 14110465
Plan Review Stops For Permit 14110465
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-24 Cont ID  
Sent By jgomez Date 2014-11-24 Time 09:34 Rev Time 0.00
Received By jgomez Date 2014-11-19 Time 16:55 Sent To  
Notes
2014-11-24 09:35:27APPROVED BY HAROLD ON 11/20/14. JG.
2014-11-20 16:56:0111/20/14: RE-SUBMITTAL SENT TO HAROLD MOSER FOR REVIEW.
 JG.
2014-11-19 12:27:22ROUTED TO MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-17 Cont ID  
Sent By hmoser Date 2014-11-17 Time 13:15 Rev Time 0.00
Received By hmoser Date 2014-11-12 Time   Sent To  
Notes
2014-11-12 12:29:41<5000 MECH
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-11-24 Cont ID  
Sent By jgomez Date 2014-11-24 Time 09:35 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2014-11-24 09:36:14APPROVED BY HAROLD ON 11/20/14. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-17 Cont ID  
Sent By wlehnhar Date 2014-11-12 Time 12:31 Rev Time 0.00
Received By hmoser Date 2014-11-17 Time 12:42 Sent To  
Notes
2014-11-17 13:15:13PLAN DENIED
 1) PROVIDE CAN SIZE AND GRILL SIZE ON PLANS
 2) PROVIDE CFM ON ALL SUPPLY DROPS
 3) PROVIDE EQUIPMENT SCHEDULE ON THE
 PLAN SHOWING MODEL NUMBERS,VOLTAGE
 AND SEER ALONG WITH AHRI SHEETS IF
 EQUIPMENT IS BEING REPLACED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  
  
  
  
2014-11-12 12:32:23COULD NOT DELETE ACTIVITY (PLACED MY NAME AS REVIEWER
 IN ERROR) SEE NEW "M" STOP