Plan Review Details - Permit 14110431
Plan Review Stops For Permit 14110431
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By jwitmer Date 2014-11-18 Time 07:52 Rev Time 0.00
Received By jwitmer Date 2014-11-18 Time 07:45 Sent To  
Notes
2014-11-18 07:48:43BUILDING PLAN REVIEW
 PERMIT: 14110431
 ADD: 1000 N DIXIE HWY
 CONT: TBD/ CHURCH OF GOD LIGHT HOUSE OF HOPE
 TEL: (561)460-8779
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 18/ 2014
 ACTION: DENIED
  
 1) SUBMITTED PLANS ARE COPIES OF ARCHITECTURAL PLANS,
 FOR THE APPLICANTS USE AS REFERANCE ONLY. ARCHITECTURAL
 SHEETS ARE COPRIGHTED!!!
  
 2) FOR A CHANGE OF OCCUPANCY THE EXISTING BUILDING CODE
 CHAPTER 9 SEE SECTION 901.3.1 FOR A PARTIAL CHANGE OF
 OCCUPANCY OF A BUILDING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING;
 AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 PRE-ENGINEERED SYSTEMS
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 FLOOR SYSTEMS
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 09:51 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 09:51 Sent To  
Notes
2014-12-19 09:53:1412/19/2014
 PROJECT: PEARL PLACE
 PERMIT#: 14110431
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FL SS 471, 668.001-668.006, FBC, WPB AMENDMENTS
 107.2.1
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-WPB AMENDMENTS 107.3.5.1.2
 NO ELECTRICAL PLANS HAVE BEEN SUBMITTED. THE MINIMUM
 PLAN REVIEW CRITERIA FOR ELECTRICAL INCLUDES THE
 FOLLOWING:
 A.) AN ELECTRICAL SERVICE RISER, AND LOAD CALCULATION.
 NEC 215.5
 B.) THE ELECTRICAL PANEL CIRCUIT DIRECTORIES, NEC 408.4
 C.) A FLOOR PLAN WITH CIRCUIT NUMBERS TO COINCIDE WITH
 THE PANEL CIRCUIT DIRECTORY. FBC-WPB AMENDMENTS 107.3.5
 D.) A LIGHTING FIXTURE SCHEDULE AND LIGHTING PLAN,
 FBC-WPB AMENDMENTS 107.3.5
 E.) THE EXIT AND EMERGENCY LIGHTING PLAN PROVIDING AN
 ILLUMINATED MEANS OF EGRESS. NEC700.12
 F.) A SIGN CIRCUIT. NEC 600.5
 G.) WIRING METHODS SUITABLE FOR THE ENVIRONMENT.
 ASSEMBLY OCCUPANCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-12 Cont ID  
Sent By pleduc Date 2014-11-12 Time   Rev Time 0.00
Received By pleduc Date 2014-11-12 Time 10:58 Sent To  
Notes
2014-11-12 16:43:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT INFORMATION PROVIDED TO DETERMINE
 AN APPOVAL OF A CHANGE OF OCCUPANCY.
  
 WHAT IS THE EXISTING OCCUPANCY?
  
 WHAT IS THE PROPOSED CHANGE?
  
 BASED ON THE CHANGE, PLEASE PROVIDE A LIFE SAFETY PLAN
 INCLUDING, BUT NOT LIMITED TO, ROOM/SPACE DESIGNATION,
 OCCUPANCY LOADS, EXIT PATHS, TRAVEL DISTANCES,
 EMERGENCY LIGHTING, EXITS, EXITS SIGNS, FIRE WALLS, AND
 ENGINEERED LIFE SAFETY SYSTEMS (FIRE ALARM, FIRE
 SPRINKLER).

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 09:53 Rev Time 0.00
Received By dhayes Date 2014-11-10 Time 16:42 Sent To  
Notes
2014-11-10 16:42:32INCOMING SENT TO B24 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By jwitmer Date 2014-11-18 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2014-11-18 Time 07:52 Sent To  
Notes
2014-11-18 07:53:27BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-03 Cont ID  
Sent By rbergsma Date 2014-12-03 Time   Rev Time 0.33
Received By rbergsma Date   Time   Sent To  
Notes
2014-12-03 12:46:26CURRENT USE WITH ALL IMPROVMENTS ADDRESSED MUST BE
 PRESENTED FOR REVIEW

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-24 Cont ID  
Sent By tklarge Date 2014-11-24 Time 06:11 Rev Time 0.00
Received By tklarge Date 2014-11-24 Time 05:58 Sent To  
Notes
2014-11-24 06:11:05WPB AMENDMENTS TO 2010 FBC SEC. 107.2.1.
 1) THE SUBMITTED PLANS ARE FROM 1989 AND ARE COPIES OF
 AN ARCHITECT'S PLANS. SUBMIT A CURRENT SET OF PLANS
 THAT REFLECT ALL THE RENOVATIONS THAT ARE TO BE DONE IN
 THE BUILDING. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) COMPLY WITH WPB AMEND. TO 2010 FBC SEC 107.3.5.1.3.
 FOR MINIMUM PLUMBING PLAN REVIEW REQUIREMENTS.
 3) INDICATE THE PREVIOUS OCCUPANCY.
 4) INDICATE THE OCCUPANT LOAD OF THE NEW OCCUPANCY IN
 ACCORDANCE WITH TABLE 1004.1.1 OF THE 2010 FBC.
 5) CHANGES OF OCCUPANCY SHALL COMPLY WITH CHAPTER 9 OF
 THE 2010 FL. EXISTING BUILDING CODE.
 6) THE CHURCH IS NAMED AS THE CONTRACTOR ON THE
 APPLICATION. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By aaponte Date 2014-12-11 Time 14:01 Rev Time 0.00
Received By aaponte Date 2014-12-11 Time 14:01 Sent To  
Notes
2014-12-11 14:01:55SUBMITTED PLANS DO NOT INDICATE WHAT IS THE NEW USE FOR
 THE SPACE.