Plan Review Details - Permit 14110421
Plan Review Stops For Permit 14110421
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-01-07 Cont ID  
Sent By jwitmer Date 2015-01-07 Time 10:09 Rev Time 0.00
Received By jwitmer Date 2015-01-07 Time 08:04 Sent To  
Notes
2015-01-07 10:09:11BUILDING PLAN REVIEW
 PERMIT: 14110421
 ADD: 2711 EXCHANGE CT
 CONT: TO BE DETERMINED
 TEL: (561)358-5080
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 07/ 2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1) SITE REQUIREMENTS:
 PARKING: THE 2 ACCESSIBLE PARKING SPACES THAT ARE SIDE
 BY SIDE DOES NOT HAVE A 5'-0" WIDE ACCESS AISLE. SEE
 2010 FBC-ACCESSIBILITY CODE 502.3
 THE 2ND ISSUE IS THAT THESE SAME 2 ACCESSIBLE PARKING
 SPACES AS DEPICTED REQUIRES THE OCCUPANT TO WHEEL
 BEHIND PARKED CARS OWNED BY OTHERS. PLEASE REVIEW
 FBC-ACCESSIBLITY 502.3 GRAY BOX, FL. SPECIFIC.
  
 2) OCCUPANCY GROUP PRIOR AND NEW OCCUPANCY WAS THIS A
 DAY CARE OR IS THIS A CHANGE OF OCCUPANCY? PERMIT
 03070117 IT APPEARS THE USE WAS EITHER A BUSINESS OR
 MERCANTILE. THE SHEET LIST THIS AS A LEVEL II
 ALTERATION, IT WOULD APPEAR A CHANGE OF OCCUPANCY WILL
 OCCUR AND CHAPTER 9 OF THE EXISTING BUILDING CODE
 SECTION 901.3 SHALL APPLY. 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).SHEET A2 INDICATES THIS IS BUILT AAS
 BUILDING TYPE IV OR HEAVY TIMBER?
  
 4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 2010 FBC-B 436.1(2) STORAGE ROOMS 1 HR FIRE RATED /
 TABLE 715.4 3/4 HR OPENING PROTECTIVES.
  
 5.COMPLIED NO FIRE SPRINKLERS. FIRE SUPPRESSION SYSTEMS
 SHALL INCLUDE: FIRE SPRINKLERS OR NOT
 SCHEMATIC FIRE SPRINKLERS
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD, MISSING OCCUPANT LOADS IN SECURITY &
 STORAGE ROOM, BREAK ROOM, ART & MUSIC CENTER, COMPUTER
 ROOM, FIRST AID ROOM, FILE ROOM, RECEPTION, CONFERENCE
 ROOM, FAMILY & CHILDREN ROOM, ADULT READING AND
 RESEARCH ROOM & ADMINISTRATORS OFFICE.
 GROSS
 NET
 MEANS OF EGRESS;
 EXIT ACCESS PLANS FAIL TO IDENTIFY FIRE RATED CORRIDORS
 FOR A DAYCARE OCCUPANCY :
 2010 FBC-B 1037.2.2
 WHERE THE TWO EXIT ACCESSES FROM A DAY CARE OCCUPANCY
 IN AN APARTMENT BUILDING ENTER THE SAME CORRIDOR AS THE
 APARTMENT OCCUPANCY, THE EXIT ACCESSES SHALL BE
 SEPARATED IN THE CORRIDOR BY A SMOKE BARRIER HAVING NOT
 LESS THAN A 1-HOUR FIRE-RESISTANCE RATING CONSTRUCTED
 IN ACCORDANCE WITH SECTION 710. THE SMOKE BARRIER SHALL
 BE LOCATED SO THAT IT HAS AN EXIT ON EACH SIDE.
 1037.2.3
 DOORS DESIGNED TO BE NORMALLY CLOSED SHALL COMPLY WITH
 SECTION 715.4.8.
  
 EXIT
 EXIT DISCHARGE
 DOORS SEE 2010 FBC-B 1037.1 PANIC & FIRE EXIT HARDWARE
 OCCUPANT LOAD WILL BE OVER 100.
 NOTE DOOR SIZES ARE NOT PROVIDED: 2010 FBC-B 1008.1.1/
 FBC-ACCESS. CODE 404.2.3.
  
 EMERGENCY LIGHTING AND EXIT SIGNS:
 1037.4 ILLUMINATION AND MARKING OF MEANS OF EGRESS.
 ILLUMINATION AND MARKING OF MEANS OF EGRESS SHALL
 COMPLY WITH SECTION 1006.
 2010 FBC-B 1037.5 EMERGENCY LIGHTING.
 EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 1006.2
 SHALL BE PROVIDED IN THE FOLLOWING AREAS:
 1. INTERIOR STAIRS AND CORRIDORS.
 2. NORMALLY OCCUPIED SPACES.
  
 SPECIFIC OCCUPANCY REQUIREMENTS: SEE COMMENT #5
 COMPLIANCE WITH 2010 FBC-B 1037.6.
  
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS SEE COMMENT # 1
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS : NOT SHOWN SHOW COMPLIANCE WITH
 2010 FBC-ACCESS. 211.2.
  
 3) 2010 EXISTING BUILDING CODE CHANGE IN OCCUPANCY 01.3
 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 4) 2010 FBC-B COMPLY WITH THIS CHAPTER. DAY CARE
 OCCUPANCIES WILL ALSO NEED TO COMPLY WITH THE 2010
 FBC-B CHAPTER 436.
  
 4A) SHOW COMPLIANCE. 436.2 CLOSET DOORS. EVERY CLOSET
 DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR
 FROM INSIDE THE CLOSET.
  
 4B) SHOW COMPLIANCE. 436.3 BATHROOM DOORS. EVERY
 BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT OPENING
 OF THE LOCKED DOOR FROM THE OUTSIDE IN AN EMERGENCY.
 THE OPENING DEVICE SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 4C) SHOW COMPLIANCE 436.4 DOOR CLOSURE. FOR THE NEWLY
 RATED CORRIDOORS. ANY EXIT DOOR DESIGNED TO BE NORMALLY
 CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY WITH
 SECTION 715.3.
  
 5) THE PLEASE PROVIDE THE ACTUAL WINDOW SIZE AND TYPE
 OF WINDOW, SINLGE HUNG, CASEMENT OR STOREFRONT.
 2010 FBC-B EMERGENCY ESCAPE AND RESCUE
 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET (0.53 M2).
 1029.4.1
 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2
 M2) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR
 OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO
 STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY
 SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN
 GROUP D OCCUPANCIES SHALL HAVE NOT LESS THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 6) 2010 EXST. BLDG. CODE 912.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS THAT REQUIRES A FIRE ALARM AND
 DETECTION SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS. EXISTING ALARM NOTIFICATION APPLIANCES SHALL BE
 AUTOMATICALLY ACTIVATED THROUGHOUT THE BUILDING. WHERE
 THE BUILDING IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM,
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 FBC-B 436.7.2 DETECTION.
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN
 THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY.
  
 7) PLEASE NOTE THIS IS A DAYCARE OCCUPANCY, WITH PRE-K
 4 YEAR OLDS, WHEN ANY EDUCATIONAL ACTIVITIES SUSH AS
 TEACHING THE ALPHABET THIS WILL TRIGGER THE
 REQUIREMENTS FOR EDUCATIONALS OCCUPANCY AND CORRIDOR
 WIDTHS OF 72 INCHES FOR 100 OCCUPANTS OR MORE. 2010
 FBC-B 1018.2. THEN THE SECOND ISSUE IS OCCUPANCY
 SEPARATION BETWEEN OCCUPANCIES, SEPARATED OR NOT?
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 15:51 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 15:25 Sent To  
Notes
2014-11-26 15:51:53BUILDING PLAN REVIEW
 PERMIT: 14110421
 ADD: 2711 EXCHANGE CT
 CONT: TO BE DETERMINED
 TEL: (561)358-5080
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 26/ 2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE A GOOD BASE FOR THE DESIGN
 PROFESSIONAL TO TAKE DIMENSIONS FROM AND LAYOUT OF THE
 TENANT SPACE. THE PLANS ARE COPIES, COPYRIGHT LAWS WILL
 NOT ALLOW THE ASSUMED WORK OF A DESIGN PROFESSIONAL.
 THE PLANS DO NOT MEET THE MINIMUM SCALE REQUIREMENTS
 FOR RECORD RETENSION.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.4 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1) SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 2) OCCUPANCY GROUP PRIOR AND NEW OCCUPANCY
 3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: FIRE
 SPRINKLERS OR NOT
 SCHEMATIC FIRE SPRINKLERS
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 3) 2010 EXISTING BUILDING CODE CHANGE IN OCCUPANCY 01.3
 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 4) 2010 FBC-B COMPLY WITH THIS CHAPTER. DAY CARE
 OCCUPANCIES WILL ALSO NEED TO COMPLY WITH THE 2010
 FBC-B CHAPTER 436.
  
 5) 2010 FBC-B EMERGENCY ESCAPE AND RESCUE
 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET (0.53 M2).
 1029.4.1
 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2
 M2) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR
 OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO
 STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY
 SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN
 GROUP D OCCUPANCIES SHALL HAVE NOT LESS THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-01-07 Cont ID  
Sent By dhayes Date 2015-01-07 Time 13:44 Rev Time 0.00
Received By dhayes Date 2015-01-07 Time 13:44 Sent To  
Notes
2015-01-07 13:44:291/7/2015
 PROJECT: CHANGE OF COCCUPANCY TO DAY CARE
 PERMIT#: 14110421
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS:
  
 1) FL SS 471, 668.001-668.006, FBC, WPB AMENDMENTS
 107.2.1
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-WPB AMENDMENTS 107.3.5.1.2
 NO ELECTRICAL PLANS HAVE BEEN SUBMITTED. THE MINIMUM
 PLAN REVIEW CRITERIA FOR ELECTRICAL INCLUDES THE
 FOLLOWING:
 A.) AN ELECTRICAL SERVICE RISER, AND LOAD CALCULATION.
 NEC 215.5
 B.) THE ELECTRICAL PANEL CIRCUIT DIRECTORIES, NEC 408.4
 C.) A FLOOR PLAN WITH CIRCUIT NUMBERS TO COINCIDE WITH
 THE PANEL CIRCUIT DIRECTORY. FBC-WPB AMENDMENTS 107.3.5
 D.) A LIGHTING FIXTURE SCHEDULE AND LIGHTING PLAN,
 FBC-WPB AMENDMENTS 107.3.5
 E.) THE EXIT AND EMERGENCY LIGHTING PLAN PROVIDING AN
 ILLUMINATED MEANS OF EGRESS. NEC700.12
 F.) A SIGN CIRCUIT. NEC 600.5
 G.) WIRING METHODS SUITABLE FOR THE ENVIRONMENT.
 "ASSEMBLY OCCUPANCY".
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 09:14 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 09:12 Sent To  
Notes
2014-12-19 09:37:1012/19/2014
 PROJECT: CHANGE OF COCCUPANCY TO DAY CARE
 PERMIT#: 14110421
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FL SS 471, 668.001-668.006, FBC, WPB AMENDMENTS
 107.2.1
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-WPB AMENDMENTS 107.3.5.1.2
 NO ELECTRICAL PLANS HAVE BEEN SUBMITTED. THE MINIMUM
 PLAN REVIEW CRITERIA FOR ELECTRICAL INCLUDES THE
 FOLLOWING:
 A.) AN ELECTRICAL SERVICE RISER, AND LOAD CALCULATION.
 NEC 215.5
 B.) THE ELECTRICAL PANEL CIRCUIT DIRECTORIES, NEC 408.4
 C.) A FLOOR PLAN WITH CIRCUIT NUMBERS TO COINCIDE WITH
 THE PANEL CIRCUIT DIRECTORY. FBC-WPB AMENDMENTS 107.3.5
 D.) A LIGHTING FIXTURE SCHEDULE AND LIGHTING PLAN,
 FBC-WPB AMENDMENTS 107.3.5
 E.) THE EXIT AND EMERGENCY LIGHTING PLAN PROVIDING AN
 ILLUMINATED MEANS OF EGRESS. NEC700.12
 F.) A SIGN CIRCUIT. NEC 600.5
 G.) WIRING METHODS SUITABLE FOR THE ENVIRONMENT.
 "ASSEMBLY OCCUPANCY".
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-12-31 Cont ID  
Sent By pleduc Date 2014-12-31 Time   Rev Time 0.00
Received By pleduc Date 2014-12-31 Time 13:49 Sent To  
Notes
2014-12-31 16:55:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 USE OF THE BUILDING AS A DAY-CARE IS NOT APPROVED AT
 THIS TIME OR AT ANY TIME UNTIL ALL CONCERNS ARE
 ADDRESSED AND PROPERLY INSPECTED AND APPROVED FOR
 OCCUPANCY. CHILDREN SHALL NOT OCCUPY THIS BUILDING. IF
 IT IS FOUND THAT THIS BUILDING IS OPERATING AS A
 DAYCARE WITHOUT PROPER PERMITTING AND APPROVAL,
 IMMEDIATE ACTION SHALL BE TAKEN TO CEASE OPERATIONS.
  
 THE FOLLOWING COMMENTS REFLECT THE MAIN CONCERNS WITH
 THIS CHANGE OF OCCUPANCY. THIS OCCUPANY SHALL COMPLY
 WITH NFPA 1, CHAPTER 20.3.4, DAY CARE OCCUPANCIES; NFPA
 101 FLORIDA EDITION, CHAPTER 16, NEW DAY-CARE
 OCCUPANCIES; F.S., CHAPTER 402.305; FL RULE 69A-36 AND
 ASSOCIATED CODES AND STANDARDS FOR DAY-CARE
 OCCUPANCUES.
  
 IF THIS OCCUPANCY IS PRIMARILY EDUCATIONAL IT SHALL
 COMPLY WITH NFPA 101, CHAPTER 14, NEW EDUCATIONAL
 OCCUPANCIES.
  
 A MONITORED FIRE ALARM WITH AUTOMATIC SMOKE DETECTION
 IS REQUIRED.
  
 THE INDICATED OCCUPANCY LOAD DOES NOT MATCH THE SQUARE
 FOOTAGE CALCULATION FOR THIS OCCUPANCY. OCCUPANCY
 COUNTS WERE NOT INCLUDED IN SOME ROOMS INCLUDING THE
 ART, COMPUTER, BREAK, LOBBY, OFFICES, CONFERENCE, FIRST
 AID, SECURITY, FAMILY ZONE, ADULT READING, AND
 RECEPTION. PLEASE PROVIDE JUSTIFICATION AND A SEATING
 AND EQUIPMENT PLAN.
  
 THE WINDOWS LABELED ESCAPE ARE NOT APPROVED UNDER THIS
 PERMIT UNTIL THEY ARE FIELD VERIFIED.
 ESCAPE/RESCUE WINDOWS
 (1) SUCH WINDOWS SHALL BE OPERABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20-INCHES IN WIDTH, 24-INCHES
 IN HEIGHT, AND 5.7
 SQ.FT. IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44-INCHES ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 SQ.FT. OPENING AND A DEPTH OF NOT LESS
 THAN 20-INCHES
 TO PASS FULLY THROUGH THE OPENING.
  
 PROVIDE A LIFE SAFETY PLAN INCLUDING, EXIT TRAVEL,
 COMMON PATH OF TRAVEL, EXITS, EXIT SIGNS, EMERGENCY
 LIGHTS, FIRE EXTINGUISHER LOCATIONS, AND EXIT DOOR
 HARDWARE. EACH EXIT SHALL LEAD TO PUBLIC WAY. EXITS
 THAT LEAD INTO THE PLAY AREA MUST HAVE AN EXIT LEADING
 TO A PUBLIC WAY.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
  
 A DOOR SCHEDULE SHALL BE PROVIDED. PANIC HARDWARE IS
 REQUIRED ON ALL EXITS.
  
 EVERY INTERIOR CORRIDOR SHALL BE CONSTRUCTED OF WALLS
 HAVING NOT LESS THAN 1-HOUR FIRE RESISTANCE RATING
 INCLUDING DOORS AND WINDOWS. WHERE THE CORRIDOR CEILING
 IS AN ASSEMBLY HAVING A 1-HOUR FIRE RESISTANCE RATING
 WHERE TESTED AS A WALL, THE CORRIDOR WALLS SHALL BE
 PERMITTED TO TERMINATE AT THE CORRIDOR CEILING,
 OTHERWISE THE WALLS SHALL EXTEND TO UNDERSIDE OF THE
 ROOF.
  
 EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 NO COOKING SHALL BE PREPARED IN THE BREAKROOM. A STOVE
 OR RANGE SHALL NOT BE PERMITTED. ANY COOKING EQUIPMENT
 SHALL BE PERMITTED AND INSTALLED UNDER SEPARATE PERMIT
 IN COMPLIANCE WITH NFPA 96, STANDARD FOR VENTILATION
 AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS.
  
 FURTHER COMMENT IS RESERVED AS THE PLANS ARE UPDATED
 AND RESUBMITTED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-12-01 Cont ID  
Sent By pleduc Date 2014-12-01 Time   Rev Time 0.00
Received By pleduc Date 2014-12-01 Time 11:22 Sent To  
Notes
2014-12-01 11:38:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A LIFE SAFETY PLAN SHALL BE SUBMITTED THAT INCLUDES,
 THE PROPOSED HOURS OF OPERATION, NUMBER OF CHILDREN,
 AGES OF CHILDREN, NUMBER OF STAFF, ALL LIFE SAFETY
 SYSTEMS (FIRE ALARM, FIRE SPRINKLER), EXIT PATHS OF
 TRAVEL, EXITS, EXIT SIGNS, EXIT DOOR HARDWARE,
 EMERGENCY LIGHTING, SMOKE DETECTORS, ETC.
  
 A TOTAL SITE PLAN THAT SHOWS SURROUNDING AREAS
 DETAILING WHERE THE EXITS LEAD. ALL EXITS SHALL LEAD TO
 A PUBLIC WAY.
  
 THE RESUBMITTED PLAN WILL BE REVIEWED FOR COMPLIANCE
 WITH THE REQUIREMENTS OF A NEW DAYCARE WITHIN THE
 FLORIDA LIFE SAFETY CODE AND ALL ASSOCIATED AND
 APPLICABLE NFPA CODES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-15 Cont ID  
Sent By skennedy Date 2015-01-15 Time 17:37 Rev Time 0.00
Received By skennedy Date 2014-12-29 Time 11:34 Sent To  
Notes
2014-12-29 11:36:22INCOMING SENT TO B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 09:46 Rev Time 0.00
Received By dhayes Date 2014-11-10 Time 10:21 Sent To  
Notes
2014-11-26 10:21:51INCOMING SENT TO B22 . JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-01-07 Cont ID  
Sent By jwitmer Date 2015-01-07 Time 10:09 Rev Time 0.00
Received By jwitmer Date 2015-01-07 Time 10:09 Sent To  
Notes
2015-01-07 10:09:59BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 15:26 Sent To  
Notes
2014-11-26 15:26:34BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 13:59 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 13:58 Sent To  
Notes
2015-01-14 14:00:21NO MECHANICAL PLANS SUBMITTED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-08 Cont ID  
Sent By skennedy Date 2014-12-03 Time   Rev Time 0.20
Received By skennedy Date 2014-12-03 Time   Sent To  
Notes
2014-12-08 09:38:02REVIEW BY RBERGSMA.
2014-12-03 14:54:26NEED COMPLETE SET OF MECHANICAL DRAWINGS

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-04 Cont ID  
Sent By tklarge Date 2015-01-04 Time 08:26 Rev Time 0.00
Received By tklarge Date 2015-01-04 Time 07:38 Sent To  
Notes
2015-01-04 07:37:201) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED PER
 THE FL. ACCESSIBILITY CODE SEC. 211.2. SINCE THIS IS A
 CHANGE OF OCCUPANCY FULL COMPLIANCE WITH THE FL.
 ACCESSIBILITY CODE IS REQUIRED.
 2) A MINIMUM OF ONE SINK IN EACH OF THE 2 YEAR OLD'S
 ROOMS SHALL COMPLY WITH THE FL. ACCESSIBILITY CODE
 SECS. 212.2, AND 606. SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE FIXZTURE ON THE FLOOR PLAN.
 3) SUBMIT A SANITARY AND WATER RISER FOR THE
 ADDITIONS/ALTERATIONS THAT ARE GOING TO BE MADE TO THE
 PLUMBING SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-28 Cont ID  
Sent By tklarge Date 2014-11-28 Time 06:00 Rev Time 0.00
Received By tklarge Date 2014-11-28 Time 05:18 Sent To  
Notes
2014-11-28 05:39:281) PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE PER
 THE WPB AMEND. TO 2010 FBC SEC.107.2.1.4.
 2) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL OF RECORD PER THE F.A.C. RULE
 61G15-23.001 & 61G15-23.002.
 3) SUBMIT PLANS FOR A "D" OCCUPANCY ( DAYCARE) PER THE
 2010 FBC SEC. 313.1.
 4) THE SUBMITTED PLANS REFERENCE THE 2001 FBC. THE 2010
 EDITION OF THE FBC IS THE CODE IN EFFECT. ALL PLANS
 SHALL BE DESIGNED IN ACCORDANCE WITH THE 2010 FBC.
 5) THE PLANS SHALL INDICATE THE DAYCARE
 SUBCLASSIFICATION IN ACCORDANCE WITH THE 2010 FBC
 SEC.313.2.
 6) DAYCARE OCCUPANCIES SHALL COMPLY WITH 2010 FBC SEC.
 436.
 7) THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
 SHALL COMPLY WITH 2010 FPC TABLE 403.1.
 8) A CHANGE OF OCCUPANCY SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF CHAPTER 9 OF THE 2010 FLORIDA EXISTING
 BUILDING CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-30 Cont ID  
Sent By sgraham Date 2014-12-30 Time 08:25 Rev Time 0.00
Received By sgraham Date 2014-12-30 Time 08:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-01 Cont ID  
Sent By sgraham Date 2014-12-01 Time 16:18 Rev Time 0.00
Received By sgraham Date 2014-12-01 Time 16:18 Sent To  
Notes
2014-12-01 16:20:4312/1/14 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS
 2. PROVIDE TWO SITE PLANS SHOWING THE PARKING LOT WITH
 DROP AREA AND THE LANDSCAPING.
2014-12-01 13:51:0212/1/14