Plan Review Details - Permit 14110356
Plan Review Stops For Permit 14110356
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-13 Cont ID  
Sent By tklarge Date 2014-11-13 Time 07:51 Rev Time 0.00
Received By tklarge Date 2014-11-10 Time 06:44 Sent To  
Notes
2014-11-07 13:43:53<5000 PLUMB

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-13 Cont ID  
Sent By tklarge Date 2014-11-13 Time 07:50 Rev Time 0.00
Received By tklarge Date 2014-11-12 Time 08:03 Sent To  
Notes
2014-11-12 08:18:411) A MINIMUM OF A DOUBLE CHECK VALVE ASSEMBLY IS
 REQUIRED ON THE WATER LINE PER CITY OF WPB ORD. SEC.
 90-33 AND THE CITY'S CROSS CONNECTION CONTROL MANUAL.
 THE N36 AND THE SWING CHECK VALVE DOES NOT MEET THIS
 REQUIREMENT.
 2) SUBMIT DOCUMENTATION ON THE TYPE OF BACKFLOW DEVICE
 TO BE INSTALLED ON THE 1" FRESH WATER FILL LINE TO THE
 COLLECTOR TANK.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  