Plan Review Details - Permit 14110339
Plan Review Stops For Permit 14110339
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-07-24 Cont ID  
Sent By skennedy Date 2015-07-24 Time 12:29 Rev Time 0.00
Received By skennedy Date 2015-07-24 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-06-26 Cont ID  
Sent By skennedy Date 2015-06-26 Time 10:03 Rev Time 0.00
Received By skennedy Date 2015-06-26 Time 10:03 Sent To  
Notes
2015-06-26 10:04:203RD REVIEW: FBC 2010
  
 THE FOLLOWING ITEMS ARE REPEAT COMMENTS FROM THE FIRST
 AND SECOND REVIEW:
  
 FBC 107.3.5.3 PROVIDE A MORE ACCURATE SITE PLAN OR
 SURVEY TO DEMONSTRATE BUILDING SEPARATION AND PROPOSED
 ELEVATION.
 4/26/15 THE SITE PLAN HAS A PROFESSIONAL DESIGNERS
 TITLE BLOCK AND THERRFORE MUST BE SIGNED AND SEALED PER
 FS 481. THE PLAN IS TOO SMALL TO BE LEGIBLE AND FOR
 RECORD RETENTION.
  
 SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR
 THE BUILDING FOUNDATION. PLEASE SELECT A SPECIFIC
 FOUNDATION DESIGN FOR THIS SITE AND PROVIDE ADDITIONAL
 DETIAL TO DEMONSTRATE COMPLIACNE WITH THE FOLLOWING FBC
 SECTIONS:
  
 1808.7.4 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 1809.4 DEPTH AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM).
 4/26/15 THE REVISED SHEET S-5 DOES NOT ADEQUATELY
 ADDRESS THE OBJECTIONS ABOVE.
  
 THE VALUE OF $2,600.00 APPEARS UNDERVALUED. PLEASE
 UPDATE ACCORDING TO THE SECTION BELOW:
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE REVISE AND RE-SUBMIT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-26 Cont ID  
Sent By skennedy Date 2015-04-26 Time 11:36 Rev Time 0.00
Received By skennedy Date 2015-04-26 Time 11:36 Sent To  
Notes
2015-04-26 11:43:322ND REVIEW: FBC 2010
  
 THE FOLLOWING ITEMS ARE REPEAT COMMENTS FROM THE FIRST
 REVIEW:
  
 FBC 107.3.5.3 PROVIDE A MORE ACCURATE SITE PLAN OR
 SURVEY TO DEMONSTRATE BUILDING SEPARATION AND PROPOSED
 ELEVATION.
 4/26/15 THE SITE PLAN HAS A PROFESSIONAL DESIGNERS
 TITLE BLOCK AND THERRFORE MUST BE SIGNED AND SEALED PER
 FS 481. THE PLAN IS TOO SMALL TO BE LEGIBLE AND FOR
 RECORD RETENTION.
  
 SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR
 THE BUILDING FOUNDATION. PLEASE SELECT A SPECIFIC
 FOUNDATION DESIGN FOR THIS SITE AND PROVIDE ADDITIONAL
 DETIAL TO DEMONSTRATE COMPLIACNE WITH THE FOLLOWING FBC
 SECTIONS:
  
 1808.7.4 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 1809.4 DEPTH AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM).
 4/26/15 THE REVISED SHEET S-5 DOES NOT ADEQUATELY
 ADDRESS THE OBJECTIONS ABOVE.
  
 THE VALUE OF $2,600.00 APPEARS UNDERVALUED. PLEASE
 UPDATE ACCORDING TO THE SECTION BELOW:
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE REVISE AND RE-SUBMIT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-10 Cont ID  
Sent By skennedy Date 2014-12-10 Time 07:22 Rev Time 0.00
Received By skennedy Date 2014-12-10 Time 07:22 Sent To  
Notes
2014-12-10 07:56:471ST REVIEW: FBC 2010
  
 FBC 107.3.5.3 PROVIDE A MORE ACCURATE SITE PLAN OR
 SURVEY TO DEMONSTRATE BUILDING SEPARATION AND PROPOSED
 ELEVATION.
  
 SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR
 THE BUILDING ROOF DESIGN. PLEASE SPECIFY THE PROPOSED
 ROOF DESIGN.
  
 SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR
 THE BUILDING FOUNDATION. PLEASE SELECT A SPECIFIC
 FOUNDATION DESIGN FOR THIS SITE AND PROVIDE ADDITIONAL
 DETIAL TO DEMONSTRATE COMPLIACNE WITH THE FOLLOWING FBC
 SECTIONS:
  
 1808.7.4 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 1809.4 DEPTH AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM).
  
 2304.11.2.1 JOISTS, GIRDERS AND SUBFLOOR.
 WHERE WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL
 FLOOR WITHOUT JOISTS ARE CLOSER THAN 18 INCHES (457
 MM), OR WOOD GIRDERS ARE CLOSER THAN 12 INCHES (305 MM)
 TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED
 AREAS LOCATED WITHIN THE PERIMETER OF THE BUILDING
 FOUNDATION, THE FLOOR CONSTRUCTION (INCLUDING POSTS,
 GIRDERS, JOISTS AND SUBFLOOR) SHALL BE OF NATURALLY
 DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 THE VALUE OF $2,600.00 APPEARS UNDERVALUED. PLEASE
 UPDATE ACCORDING TO THE SECTION BELOW:
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-24 Cont ID  
Sent By skennedy Date 2015-07-24 Time 12:30 Rev Time 0.00
Received By skennedy Date 2015-06-30 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-26 Cont ID  
Sent By skennedy Date 2015-06-26 Time 10:05 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 10:31 Sent To  
Notes
2015-06-23 10:32:06RE-SUBMITTAL SENT TO STEVE KENNEDY FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-26 Cont ID  
Sent By skennedy Date 2015-04-26 Time 11:45 Rev Time 0.00
Received By skennedy Date 2015-04-03 Time 07:18 Sent To  
Notes
2015-04-03 07:18:37TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-10 Cont ID  
Sent By skennedy Date 2014-12-10 Time 08:26 Rev Time 0.00
Received By skennedy Date 2014-11-07 Time 18:51 Sent To  
Notes
2014-11-07 18:51:45SENT TO ZONING

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2015-07-24 Cont ID  
Sent By skennedy Date 2015-07-24 Time 12:29 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-07-24 12:30:25ROOF IS FACTORY INSTALLED

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2015-06-26 Cont ID  
Sent By skennedy Date 2015-06-26 Time 10:04 Rev Time 0.00
Received By skennedy Date 2015-06-26 Time 10:04 Sent To  
Notes
2015-06-26 10:05:143RD REVIEW: FBC 2010
  
 THE COMMENTS FROM THE FIRST AND SECOND REVIEW BELOW,
 WERE NOT ADDRESSED IN THE RESUBMITTAL.
  
 PLEASE BE ADVISED THAT A SEPARATE PERMIT IS REQUIRED
 FOR ROOFING. PLEASE PROVIDE TWO COPIES OF THE ROOFING
 PRODUCT APPROVAL SPECIFIED ON SHEET S-3.
  
 PLEASE RE-SUBMIT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-04-26 Cont ID  
Sent By skennedy Date 2015-04-26 Time 11:43 Rev Time 0.00
Received By skennedy Date 2015-04-26 Time 11:43 Sent To  
Notes
2015-04-26 11:45:032ND REVIEW: FBC 2010
  
 THE COMMENTS FROM THE FIRST REVIEW BELOW, WERE NOT
 ADDRESSED IN THE RESUBMITTAL.
  
 PLEASE BE ADVISED THAT A SEPARATE PERMIT IS REQUIRED
 FOR ROOFING. PLEASE PROVIDE TWO COPIES OF THE ROOFING
 PRODUCT APPROVAL SPECIFIED ON SHEET S-3.
  
 PLEASE RE-SUBMIT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-12-10 Cont ID  
Sent By skennedy Date 2014-12-10 Time 07:57 Rev Time 0.00
Received By skennedy Date 2014-12-10 Time 07:57 Sent To  
Notes
2014-12-10 07:59:361ST REVIEW: FBC 2010
  
 PLEASE BE ADVISED THAT A SEPARATE PERMIT IS REQUIRED
 FOR ROOFING. PLEASE PROVIDE TWO COPIES OF THE ROOFING
 PRODUCT APPROVAL SPECIFIED ON SHEET S-3.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-20 Cont ID  
Sent By eschneid Date 2015-04-20 Time 16:33 Rev Time 0.50
Received By eschneid Date 2015-04-20 Time 16:33 Sent To B
Notes
2015-04-20 16:33:44PASSED
  
 LANDSCAPE PERMIT 14030648 SHALL BE REVISED TO SHOW THE
 NEW AND RELOCATED LANDSCAPE INCLUDED WITH THE GAZEBO
 PROJECT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-04 Cont ID  
Sent By eschneid Date 2014-12-04 Time 08:17 Rev Time 0.75
Received By eschneid Date 2014-12-04 Time 08:17 Sent To B
Notes
2014-12-03 15:51:39FAILED
  
 1) THE ADDITION OF A NEW STRUCTURE ON THE PROPERTY
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT TO THE SITE PLAN BY THE PLANNING DIVISION.
 PLEASE CONTACT THE PLANNING DIVISION AT (561) 822-1446
 FOR THE APPLICATION.
  
 2) THE LOCATION OF THE PROPOSED GAZEBO CONFLICTS WITH
 THE LOCATION OF A REQUIRED TREE. IF THE TREE IS
 CURRENTLY INSTALLED, THEN A TREE ALTERATION PERMIT FROM
 THE PLANNING DIVISION IS REQUIRED PRIOR TO THE
 RELOCATION OF THE TREE ON-SITE. THE CHANGE TO THE
 APPROVED LANDSCAPE PLAN SHALL BE INCLUDED WITH THE
 MINOR PLANNED DEVELOPMENT AMENDMENT.
  
 3) THE NEW GAZEBO STRUCTURE REQUIRES FOUNDATION
 PLANTING.
  
 4) LANDSCAPE PERMIT 14030648 SHALL BE REVISED TO SHOW
 THE NEW AND RELOCATED LANDSCAPE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.