Plan Review Stops For Permit 14110339 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2015-07-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-07-24 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-07-24 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2015-06-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-06-26 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-06-26 |
Time |
10:03 |
Sent To |
|
|
Notes |
2015-06-26 10:04:20 | 3RD REVIEW: FBC 2010 | | | | THE FOLLOWING ITEMS ARE REPEAT COMMENTS FROM THE FIRST | | AND SECOND REVIEW: | | | | FBC 107.3.5.3 PROVIDE A MORE ACCURATE SITE PLAN OR | | SURVEY TO DEMONSTRATE BUILDING SEPARATION AND PROPOSED | | ELEVATION. | | 4/26/15 THE SITE PLAN HAS A PROFESSIONAL DESIGNERS | | TITLE BLOCK AND THERRFORE MUST BE SIGNED AND SEALED PER | | FS 481. THE PLAN IS TOO SMALL TO BE LEGIBLE AND FOR | | RECORD RETENTION. | | | | SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR | | THE BUILDING FOUNDATION. PLEASE SELECT A SPECIFIC | | FOUNDATION DESIGN FOR THIS SITE AND PROVIDE ADDITIONAL | | DETIAL TO DEMONSTRATE COMPLIACNE WITH THE FOLLOWING FBC | | SECTIONS: | | | | 1808.7.4 FOUNDATION ELEVATION. | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | ALL LOCATIONS ON THE SITE. | | | | 1809.4 DEPTH AND WIDTH OF FOOTINGS. | | THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED | | GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE | | APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL | | ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL | | BE 12 INCHES (305 MM). | | 4/26/15 THE REVISED SHEET S-5 DOES NOT ADEQUATELY | | ADDRESS THE OBJECTIONS ABOVE. | | | | THE VALUE OF $2,600.00 APPEARS UNDERVALUED. PLEASE | | UPDATE ACCORDING TO THE SECTION BELOW: | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | PLEASE REVISE AND RE-SUBMIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-04-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-04-26 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-04-26 |
Time |
11:36 |
Sent To |
|
|
Notes |
2015-04-26 11:43:32 | 2ND REVIEW: FBC 2010 | | | | THE FOLLOWING ITEMS ARE REPEAT COMMENTS FROM THE FIRST | | REVIEW: | | | | FBC 107.3.5.3 PROVIDE A MORE ACCURATE SITE PLAN OR | | SURVEY TO DEMONSTRATE BUILDING SEPARATION AND PROPOSED | | ELEVATION. | | 4/26/15 THE SITE PLAN HAS A PROFESSIONAL DESIGNERS | | TITLE BLOCK AND THERRFORE MUST BE SIGNED AND SEALED PER | | FS 481. THE PLAN IS TOO SMALL TO BE LEGIBLE AND FOR | | RECORD RETENTION. | | | | SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR | | THE BUILDING FOUNDATION. PLEASE SELECT A SPECIFIC | | FOUNDATION DESIGN FOR THIS SITE AND PROVIDE ADDITIONAL | | DETIAL TO DEMONSTRATE COMPLIACNE WITH THE FOLLOWING FBC | | SECTIONS: | | | | 1808.7.4 FOUNDATION ELEVATION. | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | ALL LOCATIONS ON THE SITE. | | | | 1809.4 DEPTH AND WIDTH OF FOOTINGS. | | THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED | | GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE | | APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL | | ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL | | BE 12 INCHES (305 MM). | | 4/26/15 THE REVISED SHEET S-5 DOES NOT ADEQUATELY | | ADDRESS THE OBJECTIONS ABOVE. | | | | THE VALUE OF $2,600.00 APPEARS UNDERVALUED. PLEASE | | UPDATE ACCORDING TO THE SECTION BELOW: | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | PLEASE REVISE AND RE-SUBMIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-12-10 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-12-10 |
Time |
07:22 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-12-10 |
Time |
07:22 |
Sent To |
|
|
Notes |
2014-12-10 07:56:47 | 1ST REVIEW: FBC 2010 | | | | FBC 107.3.5.3 PROVIDE A MORE ACCURATE SITE PLAN OR | | SURVEY TO DEMONSTRATE BUILDING SEPARATION AND PROPOSED | | ELEVATION. | | | | SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR | | THE BUILDING ROOF DESIGN. PLEASE SPECIFY THE PROPOSED | | ROOF DESIGN. | | | | SHEET S-5 CONTAINS ALTERNATE DETAILS AND OPTIONS FOR | | THE BUILDING FOUNDATION. PLEASE SELECT A SPECIFIC | | FOUNDATION DESIGN FOR THIS SITE AND PROVIDE ADDITIONAL | | DETIAL TO DEMONSTRATE COMPLIACNE WITH THE FOLLOWING FBC | | SECTIONS: | | | | 1808.7.4 FOUNDATION ELEVATION. | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | ALL LOCATIONS ON THE SITE. | | | | 1809.4 DEPTH AND WIDTH OF FOOTINGS. | | THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED | | GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE | | APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL | | ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL | | BE 12 INCHES (305 MM). | | | | 2304.11.2.1 JOISTS, GIRDERS AND SUBFLOOR. | | WHERE WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL | | FLOOR WITHOUT JOISTS ARE CLOSER THAN 18 INCHES (457 | | MM), OR WOOD GIRDERS ARE CLOSER THAN 12 INCHES (305 MM) | | TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED | | AREAS LOCATED WITHIN THE PERIMETER OF THE BUILDING | | FOUNDATION, THE FLOOR CONSTRUCTION (INCLUDING POSTS, | | GIRDERS, JOISTS AND SUBFLOOR) SHALL BE OF NATURALLY | | DURABLE OR PRESERVATIVE-TREATED WOOD. | | | | THE VALUE OF $2,600.00 APPEARS UNDERVALUED. PLEASE | | UPDATE ACCORDING TO THE SECTION BELOW: | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2015-07-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-07-24 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-06-30 |
Time |
10:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-06-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-06-26 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-06-22 |
Time |
10:31 |
Sent To |
|
|
Notes |
2015-06-23 10:32:06 | RE-SUBMITTAL SENT TO STEVE KENNEDY FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-04-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-04-26 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-04-03 |
Time |
07:18 |
Sent To |
|
|
Notes |
2015-04-03 07:18:37 | TO ZONING | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-12-10 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-12-10 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-11-07 |
Time |
18:51 |
Sent To |
|
|
Notes |
2014-11-07 18:51:45 | SENT TO ZONING |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
N |
Date |
2015-07-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-07-24 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-07-24 12:30:25 | ROOF IS FACTORY INSTALLED |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2015-06-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-06-26 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-06-26 |
Time |
10:04 |
Sent To |
|
|
Notes |
2015-06-26 10:05:14 | 3RD REVIEW: FBC 2010 | | | | THE COMMENTS FROM THE FIRST AND SECOND REVIEW BELOW, | | WERE NOT ADDRESSED IN THE RESUBMITTAL. | | | | PLEASE BE ADVISED THAT A SEPARATE PERMIT IS REQUIRED | | FOR ROOFING. PLEASE PROVIDE TWO COPIES OF THE ROOFING | | PRODUCT APPROVAL SPECIFIED ON SHEET S-3. | | | | PLEASE RE-SUBMIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2015-04-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-04-26 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-04-26 |
Time |
11:43 |
Sent To |
|
|
Notes |
2015-04-26 11:45:03 | 2ND REVIEW: FBC 2010 | | | | THE COMMENTS FROM THE FIRST REVIEW BELOW, WERE NOT | | ADDRESSED IN THE RESUBMITTAL. | | | | PLEASE BE ADVISED THAT A SEPARATE PERMIT IS REQUIRED | | FOR ROOFING. PLEASE PROVIDE TWO COPIES OF THE ROOFING | | PRODUCT APPROVAL SPECIFIED ON SHEET S-3. | | | | PLEASE RE-SUBMIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2014-12-10 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-12-10 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-12-10 |
Time |
07:57 |
Sent To |
|
|
Notes |
2014-12-10 07:59:36 | 1ST REVIEW: FBC 2010 | | | | PLEASE BE ADVISED THAT A SEPARATE PERMIT IS REQUIRED | | FOR ROOFING. PLEASE PROVIDE TWO COPIES OF THE ROOFING | | PRODUCT APPROVAL SPECIFIED ON SHEET S-3. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2015-04-20 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-04-20 |
Time |
16:33 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2015-04-20 |
Time |
16:33 |
Sent To |
B |
|
Notes |
2015-04-20 16:33:44 | PASSED | | | | LANDSCAPE PERMIT 14030648 SHALL BE REVISED TO SHOW THE | | NEW AND RELOCATED LANDSCAPE INCLUDED WITH THE GAZEBO | | PROJECT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-12-04 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-12-04 |
Time |
08:17 |
Rev Time |
0.75 |
Received By |
eschneid |
Date |
2014-12-04 |
Time |
08:17 |
Sent To |
B |
|
Notes |
2014-12-03 15:51:39 | FAILED | | | | 1) THE ADDITION OF A NEW STRUCTURE ON THE PROPERTY | | REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT | | AMENDMENT TO THE SITE PLAN BY THE PLANNING DIVISION. | | PLEASE CONTACT THE PLANNING DIVISION AT (561) 822-1446 | | FOR THE APPLICATION. | | | | 2) THE LOCATION OF THE PROPOSED GAZEBO CONFLICTS WITH | | THE LOCATION OF A REQUIRED TREE. IF THE TREE IS | | CURRENTLY INSTALLED, THEN A TREE ALTERATION PERMIT FROM | | THE PLANNING DIVISION IS REQUIRED PRIOR TO THE | | RELOCATION OF THE TREE ON-SITE. THE CHANGE TO THE | | APPROVED LANDSCAPE PLAN SHALL BE INCLUDED WITH THE | | MINOR PLANNED DEVELOPMENT AMENDMENT. | | | | 3) THE NEW GAZEBO STRUCTURE REQUIRES FOUNDATION | | PLANTING. | | | | 4) LANDSCAPE PERMIT 14030648 SHALL BE REVISED TO SHOW | | THE NEW AND RELOCATED LANDSCAPE. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|