|
 |
 |
 |
 |
 |
Plan Review Details - Permit 14110170
Plan Review Stops For Permit 14110170 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2014-11-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-11-08 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-11-08 |
Time |
08:30 |
Sent To |
|
|
Notes |
2014-11-08 08:56:39 | SHEET A1.0: BUILDING PROVISO: | | 1) THE BUILDING INDICATES THIS IS A FIRE SPRINKLERED | | BUILDING BUT NO | | PLANS FOR EXISTING AND OR NEW LAY OUT OF SPRINKLERS WAS | | SUBMITTED. | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | CODE, | | CHAPTER 1, ADMINISTRATION: | | 107.3.5.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | BUILDINGS. | | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | SCHEMATIC FIRE SPRINKLERS | | | | 2) 2010 FBC-B 13.6 FIRE WALLS, FIRE BARRIERS, FIRE | | PARTITIONS, SMOKE | | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL | | REQUIRED TO HAVE | | PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY | | IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER | | ACCEPTABLE TO THE | | AUTHORITY HAVING JURISDICTION. SUCH IDENTIFICATION | | SHALL BE ABOVE | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | SUGGESTED WORD- | | ING FOR FIRE AND SMOKE BARRIERS: | | "FIRE AND SMOKE BARRIER , PROTECT ALL OPENINGS" | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-12-12 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-12-12 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-12-12 |
Time |
14:45 |
Sent To |
|
|
Notes |
2014-12-12 15:55:15 | 12/12/2014 | | PROJECT: USI | | PERMIT#: 14110170 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION | | | | 1)SEE PERMIT NUMBER 14100308 FOR A LOAD CALCULATION TO | | ILLUSTRATE THE THE TOTAL CONNECTED LOAD ON THE EXISTING | | SERVICE PLUS THE ADDITION OF THE PROPOSED NEW LOAD TO | | TOTAL LESS THAN THE 1600AMP SERVICE MAIN. NEC 220.12, | | 220.14, 230.31 | | | | 2) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | 110.16, 110.22 | | | | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. NEC 110.9 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-11-10 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2014-11-10 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2014-11-10 |
Time |
11:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-12-12 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-12-12 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-11-04 |
Time |
10:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2014-11-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-11-08 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-11-08 |
Time |
08:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2014-12-01 |
|
|
Cont ID |
|
Sent By |
rbergsma |
Date |
2014-12-01 |
Time |
|
Rev Time |
0.50 |
Received By |
rbergsma |
Date |
2014-12-01 |
Time |
|
Sent To |
|
|
Notes |
2014-12-01 09:48:58 | AS NOTE, O/A MVD'S |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-11-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-11-15 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-11-15 |
Time |
11:21 |
Sent To |
|
|
Notes |
2014-11-15 12:29:31 | ***PROVISO**** | | 1) THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL | | BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE | | SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR | | FROM THE REAR WALL. FAC SEC.604.3.1. | | 2) THE REQUIRED 30 INCH X 48 INCH CLEAR FLOOR SPACE | | REQUIRED FOR THE DRINKING FOUNTAIN SHALL BE CENTERED ON | | THE INDIVIDUAL UNIT AND NOT ON BOTH UNITS. FAC 602.2. | | 3) KNEE & TOE CLEARANCE FOR DRINKING FOUNTAIN SHALL | | COMPLY W/ FAC SEC. 305 | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |