Plan Review Details - Permit 14110170
Plan Review Stops For Permit 14110170
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-08 Cont ID  
Sent By jwitmer Date 2014-11-08 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2014-11-08 Time 08:30 Sent To  
Notes
2014-11-08 08:56:39SHEET A1.0: BUILDING PROVISO:
 1) THE BUILDING INDICATES THIS IS A FIRE SPRINKLERED
 BUILDING BUT NO
 PLANS FOR EXISTING AND OR NEW LAY OUT OF SPRINKLERS WAS
 SUBMITTED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE,
 CHAPTER 1, ADMINISTRATION:
 107.3.5.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS.
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 2) 2010 FBC-B 13.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDENTIFICATION
 SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORD-
 ING FOR FIRE AND SMOKE BARRIERS:
 "FIRE AND SMOKE BARRIER , PROTECT ALL OPENINGS"
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-12 Cont ID  
Sent By dhayes Date 2014-12-12 Time 15:55 Rev Time 0.00
Received By dhayes Date 2014-12-12 Time 14:45 Sent To  
Notes
2014-12-12 15:55:1512/12/2014
 PROJECT: USI
 PERMIT#: 14110170
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1)SEE PERMIT NUMBER 14100308 FOR A LOAD CALCULATION TO
 ILLUSTRATE THE THE TOTAL CONNECTED LOAD ON THE EXISTING
 SERVICE PLUS THE ADDITION OF THE PROPOSED NEW LOAD TO
 TOTAL LESS THAN THE 1600AMP SERVICE MAIN. NEC 220.12,
 220.14, 230.31
  
 2) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-10 Cont ID  
Sent By scaldero Date 2014-11-10 Time 11:53 Rev Time 0.00
Received By scaldero Date 2014-11-10 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By dhayes Date 2014-12-12 Time 15:55 Rev Time 0.00
Received By dhayes Date 2014-11-04 Time 10:58 Sent To  
Notes
2014-11-06 10:59:03C09
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-11-08 Cont ID  
Sent By jwitmer Date 2014-11-08 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2014-11-08 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By rbergsma Date 2014-12-01 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-01 Time   Sent To  
Notes
2014-12-01 09:48:58AS NOTE, O/A MVD'S

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-15 Cont ID  
Sent By tklarge Date 2014-11-15 Time 12:20 Rev Time 0.00
Received By tklarge Date 2014-11-15 Time 11:21 Sent To  
Notes
2014-11-15 12:29:31***PROVISO****
 1) THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL. FAC SEC.604.3.1.
 2) THE REQUIRED 30 INCH X 48 INCH CLEAR FLOOR SPACE
 REQUIRED FOR THE DRINKING FOUNTAIN SHALL BE CENTERED ON
 THE INDIVIDUAL UNIT AND NOT ON BOTH UNITS. FAC 602.2.
 3) KNEE & TOE CLEARANCE FOR DRINKING FOUNTAIN SHALL
 COMPLY W/ FAC SEC. 305
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved