Plan Review Details - Permit 14110156
Plan Review Stops For Permit 14110156
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-17 Cont ID  
Sent By rmcdouga Date 2015-01-17 Time 12:01 Rev Time 0.00
Received By rmcdouga Date 2015-01-17 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-17 Cont ID  
Sent By rmcdouga Date 2014-12-17 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2014-12-17 Time 16:23 Sent To  
Notes
2014-12-17 16:24:01PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE DOOR SCHEDULE ON SHEET A-1 HAS SEVERAL MISTAKES.
 EXTERIOR DOOR #1 DOES NOT HAVE A SIDELITE, DOOR #5 IS
 AN IMPACT RATED EXTERIOR SLIDING GLASS DOOR, THE WIDTHS
 OF DOORS #7 AND #8 ARE WIDER THAN THE CLOSETS THEY
 SERVE, DOOR #6 IS A PAIR OF SWINGING DOORS AND THE ID
 TAGS FOR THE CLOSET DOORS IN BEDROOMS #2 AND #3 ARE
 MISSING FROM THE FLOOR PLAN. FBC 107.2.1
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THE AWNING WINDOW ("D" ON SHEET A-1) THOSE PRODUCTS
 WHICH ARE REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 3) THE PRODUCT APPROVALS FOR THE BORAL TILESEAL ( NOA
 NO.12-0417.06 ) AND THE CAST-CRETE 8" LINTELS ( NOA NO.
 12-0209.13 ) HAVE BEEN SUPERSEDED. SUBMIT TWO SETS OF
 CURRENT PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC
 107.3.4
  
 4) SPECIFY WHICH ONE OF THE TILES LISTED IN THE PRODUCT
 APPROVAL WILL BE USED AND SPECIFY THE ATTACHMENT METHOD
 THAT WILL BE USED. THE TILE PROFILE AND THE NUMBER AND
 TYPE OF MECHANICAL FASTENERS OR ADHESIVE IS NEEDED TO
 DETERMINE THAT THE REQUIRED WIND RESISTANCE IS MET. FBC
 107.2.1 & FBC-R905.3 NOTE: IF A TILE ADHESIVE IS USED,
 SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 5) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS PLACEMENT
 PLANS AND TRUSS DRAWINGS THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE STRUCTURAL ENGINEER FOR THE
 PROJECT. FBC-R 802.1.6.1
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-16 Cont ID  
Sent By rmcdouga Date 2014-12-16 Time 18:37 Rev Time 0.00
Received By rmcdouga Date 2014-12-16 Time 18:37 Sent To  
Notes
2014-12-18 09:32:50APPROVED WITH EXCEPTION.
 SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS WITH
 THE CORRECT SQUARE FOOTAGE. THE SQUARE FOOTAGE IN THE
 LOAD CALCULATIONS ON THE PLANS ARE LARGER THAN THE
 ACTUAL TOWNHOUSE UNITS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-17 Cont ID  
Sent By rmcdouga Date 2015-01-17 Time 12:02 Rev Time 0.00
Received By rmcdouga Date 2015-01-09 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-17 Cont ID  
Sent By rmcdouga Date 2014-12-17 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2014-11-04 Time 09:31 Sent To  
Notes
2014-11-10 09:31:49R28
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-01-17 Cont ID  
Sent By rmcdouga Date 2015-01-17 Time 12:02 Rev Time 0.00
Received By rmcdouga Date 2015-01-17 Time 12:01 Sent To  
Notes
2015-01-17 12:02:41MU2015-502

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By rmcdouga Date 2014-12-15 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2014-12-15 Time 15:49 Sent To  
Notes
2014-12-15 15:49:53BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-15 Cont ID  
Sent By rmcdouga Date 2014-12-15 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2014-12-15 Time 15:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-18 Cont ID  
Sent By tklarge Date 2014-11-18 Time 09:35 Rev Time 0.00
Received By tklarge Date 2014-11-18 Time 09:35 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-01-17 Cont ID  
Sent By rmcdouga Date 2015-01-17 Time 12:01 Rev Time 0.00
Received By rmcdouga Date 2015-01-17 Time 12:01 Sent To  
Notes
2015-01-17 12:01:51ROOFING MATERIALS
 BORAL TILE SEAL - NOA NO. 13-1113.05
 MALIBU CONCRETE TILE - NOA NO. 1-0321.01

Review Stop Z ZONING
Rev No 2 Status P Date 2015-01-16 Cont ID  
Sent By eschneid Date 2015-01-16 Time 16:41 Rev Time 0.25
Received By eschneid Date 2015-01-16 Time 16:41 Sent To B
Notes
2015-01-16 16:41:35PASSED W/PROVISOS
  
 1) THE PERMIT VALUE OF BUILDINGS 16 AND 17 TRIGGER THE
 CITY'S ART ASSESSMENT IN ACCORDANCE WITH SECTION 78-122
 OF THE CITY CODE.
  
 2) THE INTERIOR FINISH AND FIXTURES SHALL BE OF THE
 SAME STANDARDS AS THE NON-WORKFORCE UNITS.
  
 3) SEPARATE PERMITS, WITH PLANS, REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. PARKING LOT
 D. LIGHT POLES
 E. AWNINGS
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By eschneid Date 2014-12-02 Time 10:06 Rev Time 0.50
Received By eschneid Date 2014-12-02 Time 09:59 Sent To  
Notes
2014-12-02 10:06:33FAILED
  
 PLEASE BE AWARE THAT THE PERMIT VALUE OF BUILDINGS 16
 AND 17 TRIGGER THE CITY'S ART ASSESSMENT IN ACCORDANCE
 WITH SECTION 78-122 OF THE CITY CODE.
  
 1) PROVIDE VERIFICATION THAT THE DEVELOPER HAS ENTERED
 INTO THE AGREEMENT FOR THE PROVISION OF WORKFORCE
 HOUSING UNITS WITH THE CITY.
  
 2) THE WORKFORCE TOWNHOMES ARE A DIFFERENT PRODUCT TYPE
 FROM THE PREVIOUSLY REVIEWED PLANS. REMOVE THE
 LANDSCAPE VALUE FROM THE VALUE OF THE BUILDING. THE
 LANDSCAPE VALUE SHALL BE INCLUDED ONLY ON THE LANDSCAPE
 PERMIT.
  
 3) THE INTERIOR FINISH AND FIXTURES SHALL BE OF THE
 SAME STANDARDS AS THE NON-WORKFORCE UNITS.
  
 4) THE LIGHT POST SHOWN BETWEEN LOTS 103 AND 104 SHALL
 BE RELOCATED. ITS LOCATION, AS SHOWN ON THE SURVEY,
 CONFLICTS WITH THE REQUIRED TREE FOR THAT LANDSCAPE
 ISLAND. STAFF SUGGESTS MOVING IT BETWEEN LOTS 104 AND
 105.
  
 5) SEPARATE PERMITS, WITH PLANS, REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. PARKING LOT
 D. LIGHT POLES
 E. AWNINGS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
 NOTE: BUILDING AND LOCATION COMPLY WITH ZONING.
  
2014-11-14 12:20:3711/14/14