Plan Review Details - Permit 14110155
Plan Review Stops For Permit 14110155
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-06 Cont ID  
Sent By jwitmer Date 2015-01-06 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2015-01-06 Time 14:38 Sent To  
Notes
2015-01-06 14:41:01SEE PROVISO UNDER 1ST REVIEW/ NOTED THIS REVIEW WINDOW
 & DOOR SHOP DRAWINGS SUBMITTED, RETURNING TO CONTRACTOR
 TO BE SUBMITTED AS A DEFERRED SUBMITTAL WITH PRODUCT
 APPROVALS, NO PRODUCT APPROVALS WERE SUBMITTED. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2014-11-24 Time 14:51 Sent To  
Notes
2014-11-26 09:17:05BUILDING PLAN REVIEW
 PERMIT: 14110155
 ADD: 700 S ROSEMARY AVE. SUITE 140
 CONT: CHANDLER CONSTRUCTION
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 26/ 2014
  
 NOTICE GREASE DUCTS WILL REQUIRE A SEPARATE PERMIT &
 REVIEW.
  
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) SHEET A2.2 SHOWS A GREASE DUCT WITH A 2 HR. DUCT
 WRAP THAT WILL BE INCOMPLIANCE WITH FBC-M ASTM E 2336.
 NO LITERATURE HAS BEEN PROVIDED. THE 2010 FBC-B 708.2
 EXCEPTION #4 STATES GREASE DUCTS SHALL BE PROTECTED IN
 ACCORDANCE WITH THE FBC-MECHANICAL. PLEASE PROVIDE THE
 LITERATURE SHOWING COMPLIANCE.
  
 2) THERE IS A DISCREPANCY IN THE PLANS AND HOW THE
 ACTUAL FIELD CONDITION OF THE 2 HR. DUCT WRAP, PLEASE
 REVIEW 2010 FBC-M 506.3.10.2. THE SURFACE OF THE DUCT
 SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM THE
 POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET
 TERMINAL. THE PLANS, TYPICAL CURB DETAIL ON A2.1 &
 SECTION THROUGH THE GREASE DUCT CHASE, A2.2 SHOW THE
 DUCT WRAP CONTINUING TO THE ROOF TOP HOOD EXHAUST FAN.
 IN REALITY THE DUCT WRAP STOPS AT THE TOP OF THE HOOD
 EXHAUST DUCT ROOF TOP CURB, PLEASE SHOW THE OUTLET
 TERMINAL HOW IT WILL BE MADE WATER TIGHT, AND HOW IT
 WILL BE ATTACHED TO THE ROOF TOP CURB. PLEASE ALLOW IN
 SIZING FOR THE CURB 2 LAYERS OF DUCT WRAP TO CONTINUE
 TO THE TOP OF THE ROOF CURB.
  
 3A) SHEET A-8.2 DETAIL B SHOWS NEW GLAZING IN THE
 STOREFRONT, THESE PRODUCT APPROVALS ARE TO BE REVIEWED
 AS A DEFERRED SUBMITTAL UNDER 107.3.4.2 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION,.
  
 3B) ALSO NOTE THAT THE DESIGNER OF RECORD IS TO HAVE
 REVIEWED AND APPROVED THE SUBMITTED PRODUCT APPROVALS
 WITH THEIR SHOP DRAWING STAMP OF APPROVAL.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-05 Cont ID  
Sent By skennedy Date 2015-01-05 Time 13:48 Rev Time 0.00
Received By skennedy Date 2015-01-05 Time 13:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-03 Cont ID  
Sent By dhayes Date 2014-12-03 Time 09:04 Rev Time 0.00
Received By dhayes Date 2014-12-03 Time 09:04 Sent To  
Notes
2014-12-03 09:23:11APPROVED WITH EXCEPTION: CORRECT THE CONFLICT ON PLANS.
 SHEET E-3 INDICATES A #6 WIRE FEEDING PANE LVA FROM
 PANEL LV, HOWEVER SHEET E-4 INDICATES A # 8WIRE BEING
 FED FROM A 60AMP BREAKER IN PANEL LV FEEDING PANEL LVA.
  
 SHEET E-4
 REPLACE EITHER THE PROPOSED 3PH60AMP OCPD FEEDING PANEL
 LVA, #37,39,41, WITH A 3PH 50AMP OCPD *OR* REPLACE THE
 #8THWN CU WIRE SHOWN ON THE PANEL SCHEDULE WITH #6THWN
 CU AS INDICATED ON THE RISER DIAGRAM SHT E-3 IF THE
 60AMP OCPD FEEDING PANEL LVA IS PROPOSED TO REMAIN.
  
 SHEET E-3
 MAKE THE RISER MATCH THE PANEL SCHEDULE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By pleduc Date 2014-11-05 Time   Rev Time 0.00
Received By pleduc Date 2014-11-05 Time 13:49 Sent To  
Notes
2014-11-05 13:53:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING PROVISO:
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 THE REAR EXIT DOOR SHALL BE EQUIPPED WITH PANIC
 HARDWARE. FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD OF 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA
 BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date   Cont ID  
Sent By tklarge Date 2015-01-04 Time 09:09 Rev Time 0.00
Received By tklarge Date 2015-01-04 Time 09:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By tklarge Date 2014-11-20 Time   Rev Time 0.00
Received By tklarge Date 2014-11-19 Time   Sent To  
Notes
2015-01-26 09:10:38SEE PLUMBING COMMENTS FOR GAS REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-06 Cont ID  
Sent By jwitmer Date 2015-01-06 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2014-12-30 Time 13:39 Sent To  
Notes
2014-12-31 13:39:33C26
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-17 Cont ID  
Sent By skennedy Date 2014-12-17 Time 07:01 Rev Time 0.00
Received By skennedy Date 2014-11-04 Time 16:13 Sent To  
Notes
2014-11-04 16:14:00C01
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-01-06 Cont ID  
Sent By hmoser Date 2015-01-06 Time 12:24 Rev Time 0.00
Received By hmoser Date 2015-01-06 Time 10:14 Sent To  
Notes
2015-01-06 12:24:25PASS PROVISO
 1) PROVIDE A DETAIL FROM THE ENGINEER SHOWING THE
 SIZE BOLTS USED TO TIE THE CONDENSER STAND DOWN
 TO THE ROOF AT FIRST INSPECTION. PER SECTION
 301.12 WIND RESISTANCE FBC (M) 2010
 2) HOOD AND COOLERS REQUIRE SEPARATE
 APPLICATION, PLANS AND PERMIT. HOOD
 AND COOLERS ARE NOT PART OF THIS REVIEW.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By hmoser Date 2014-12-16 Time 15:19 Rev Time 0.00
Received By hmoser Date 2014-12-16 Time 14:21 Sent To  
Notes
2014-12-16 15:19:48PLAN DENIED
 1) DON'T TIE FRESH AIR DAMPER INTO TIME CLOCK
 PER SECTION 503.2.5.4 FLORIDA ENERGY CODE 2010
 2) REFER TO SECTION 501.2.1 EXHAUST LOCATION
 EXHAUST OUTLETS. 2010 FBC (M)
 3) PROVIDE THE BOLT SIZE USED FOR ANCHORING
 CONDENSER STAND TO ROOF.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 651-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-04 Cont ID  
Sent By tklarge Date 2015-01-04 Time 07:38 Rev Time 0.00
Received By tklarge Date 2015-01-04 Time 06:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-20 Cont ID  
Sent By tklarge Date 2014-11-20 Time 05:07 Rev Time 0.00
Received By tklarge Date 2014-11-19 Time 15:07 Sent To  
Notes
2014-11-19 15:11:001) SHT. A-0.3 - THE HANDICAP DETAILS ARE ILLEGIBLE.
 SUBMIT A SHEET THAT IS CLEAR IN DETAIL AND LEGIBLE. WPB
 AMEND. TO 2010 FBC SEC. 107.2.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC. 301.3.
 3) SHOW THE LOCATION AND SIZE OF THE EXISTING GREASE
 TRAP. WPB AMEND. TO FBC 107.2.1.
 4) SHT.P-1 SHOWS INDIRECT WASTE FROM ICE MAKER
 DISCHARGING INTO THE GREASE TRAP. WASTES THAT DO NOT
 REQUIRE TREATMENT OR SEPARATION SHALL NOTBE DISCHARGED
 INTO ANY INTERCEPTOR OR SEPARATOR. 2010 FPC SEC.1003.2.
 5) SHT.P-2 - SIZE THE LOOP VENT FOR THE RESTROOMS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.
 6) SHT. P-2 - PLANS SHOW AN "EXISTING SANITARY LINE"
 WITH A TRENCH DRAIN CONNECTING TO THE "EXISTING GREASE
 LINE". CLARIFY. SANITARY LINE CANNOT DISCHARGE INTO THE
 GREASE LINE PER THE 2010 FPC SEC.1003.2.
 7) SHT. P-2 - THE SIZING OF THE GREASE INTERCEPTOR
 SHALL BE DONE IN ACCORDANCE W/ 2010 FPC SEC.1003.5.1,
 NOT TABLE 709.1 AS NOTED ON SHT.P-2.. SUBMIT
 CALCULATIONS FOR THE ADDED FIXTURES TO THE GREASY
 WASTE.
 8) SHT. P-2 - SIZE THE SECTION OF GAS LINE BETWEEN THE
 MANUAL SHUT-OFF VALVE 6' A.F.F. TO THE CONVECTION OVEN.
 9) SHT.P-3 - "GENERAL PLUMBING NOTES" - SECOND COLUMN -
 3RD SENTENCE DOWN - REFERENCE IS MADE TO CODE SEC.
 13-412.1.ABC.2.5.2. OF 2010 FBC. THERE IS NO SUCH CODE
 SECTION. THIS IS FROM A PREVIOUS EDITION OF THE
 FL.ENERGY CODE.THE CORRECT CODE SEC. IS 504.8.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-01-02 Cont ID  
Sent By eschneid Date 2015-01-02 Time 16:40 Rev Time 0.25
Received By eschneid Date 2015-01-02 Time 16:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-21 Cont ID  
Sent By eschneid Date 2014-11-21 Time 10:32 Rev Time 0.50
Received By eschneid Date 2014-11-21 Time 10:32 Sent To  
Notes
2014-11-21 10:34:48FAILED
  
 1) PROVIDE VERIFICATION THAT THE NEW ROOFTOP EQUIPMENT
 IS SCREENED IN ACCORDANCE WITH THE CITYPLACE DRI
 REQUIREMENTS.
  
 2) ALL OTHER ELEMENTS OF PLAN COMPLY WITH ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-11-14 12:11:3911/14/14