Plan Review Details - Permit 14110041
Plan Review Stops For Permit 14110041
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-06 Cont ID  
Sent By hmoser Date 2014-11-06 Time 11:22 Rev Time 0.00
Received By hmoser Date 2014-11-05 Time 11:10 Sent To  
Notes
2014-11-03 11:18:52ROUTED TO MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-01-23 Cont ID  
Sent By hmoser Date 2015-01-23 Time 14:49 Rev Time 0.00
Received By hmoser Date 2015-01-23 Time 14:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-05 Cont ID  
Sent By hmoser Date 2014-11-05 Time 11:28 Rev Time 0.00
Received By hmoser Date 2014-11-05 Time 11:11 Sent To Z
Notes
2014-11-05 11:28:17PLAN DENIED
 1) PROVIDE CFM ON ALL SUPPLY DROPS.
 PER SECTION 107 FBC 2010
 2) PROVIDE EQUIPMENT SCHEDULE ON PLANS
 PER SECTION 107 FBC (M)
 3) REFER TO SECTION M1401.3 SIZING
 2010 RESIDENTIAL CODE AND 403.6.1
 EQUIPMENT SIZING 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676