Plan Review Details - Permit 14110004
Plan Review Stops For Permit 14110004
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-11 Cont ID  
Sent By jwitmer Date 2014-12-11 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2014-12-11 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-17 Cont ID  
Sent By jwitmer Date 2014-11-17 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2014-11-17 Time 15:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-08 Cont ID  
Sent By dhayes Date 2014-12-08 Time 13:09 Rev Time 0.00
Received By dhayes Date 2014-12-08 Time 13:09 Sent To  
Notes
2014-12-08 13:38:2112/8/2014
 PROJECT: 5808 S. DIXIE
 PERMIT#: 14110004
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXEPTION
  
 1) IDENTIFY INSTA HOT MODEL # AND MODIFY LOAD
 CALCULATION AND PANEL SCHEDULE AS REQUIRED.
  
 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 4) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 5) EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. NEC 600.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By dhayes Date 2014-12-01 Time 12:23 Rev Time 0.00
Received By dhayes Date 2014-12-01 Time 12:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-05 Cont ID  
Sent By pleduc Date 2014-12-05 Time   Rev Time 0.00
Received By pleduc Date 2014-12-05 Time 12:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By pleduc Date 2014-11-05 Time   Rev Time 0.00
Received By pleduc Date 2014-11-05 Time 12:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-11 Cont ID  
Sent By jwitmer Date 2014-12-11 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 05:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-01 Cont ID  
Sent By dhayes Date 2014-12-01 Time 12:23 Rev Time 0.00
Received By dhayes Date 2014-11-03 Time 14:59 Sent To  
Notes
2014-11-03 15:04:23INCOMING SENT TO B09. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-04 Cont ID  
Sent By tklarge Date 2014-12-04 Time 05:53 Rev Time 0.00
Received By tklarge Date 2014-12-04 Time 04:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-17 Cont ID  
Sent By tklarge Date 2014-11-17 Time 05:43 Rev Time 0.00
Received By tklarge Date 2014-11-17 Time 04:10 Sent To  
Notes
2014-11-17 05:16:221) SHT.A-1 - H.C. LAVATORY DETAIL - THE PLAN VIEW OF
 THE TOILET ROOM SHOWS A 48" X 56 " CLEARANCE FOR THE
 WATER CLOSET. SEC. 603.3.1. OF THE 2010 FL.
 ACCESSIBILITY CODE REQUIRES A CLEARANCE OF 56" MINIMUM
 X 60 " MINIMUM. SHOW THE REQUIRED CLEARANCE ON THE
 FLOOR PLAN.
 2) THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR THE WATER CLOSET PER FAC SEC.603.2.3. SEE
 THE EXCEPTIONS FOR APPLICABILITY.
 3) SHT. A-1 -THE ENLARGED FLOOR PLAN OF TOILET ROOM
 SHOWS THE TOILET ROOM DOOR SWINGING INTO THE ROOM AND
 THE FLOOR PLAN ON SHT. A-1 & A-2 SHOW THE DOOR SWINGING
 OUT. CLARIFY.
 4) THE SINK IN THE COFFEE ROOM SHALL COMPLY WITH THE
 2010 FAC SEC. 212.3 AND 606.2.
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 INSTA- HOT.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SHT. A-1 NOTES THE WATER CLOEST IN THE COFFEE ROOM
 TO BE CAPPED BUT THE RISER DIAGRAM ON SHT. A-2 STATES
 "FUTURE WATER CLOSET." WHICH IS IT?
 7) SHOW THE CLEAR FLOOR SPACE FOR THE SINK IN THE
 COFFEE ROOM PER THE 2010 FAC SEC.606.2. THE CLEAR FLOOR
 SPACE SHALL BE CENTERED ON THE FIXTURE,
 8) THE SIZE OF THE VENT (2 1/2" ) FOR THE DRINKING
 FOUNTAIN AND SINK IS NOT A CONVENTIONAL PIPE SIZE.
 CLARIFY.
 9) SUBMIT A WATER RISER FOR THE CHANGES MADE TO THE
 PLUMBING SYSTEM PER THE WPB AMEND, TO 2010 FBC SEC.
 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  