2014-12-08 13:38:21 | 12/8/2014 |
| PROJECT: 5808 S. DIXIE |
| PERMIT#: 14110004 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXEPTION |
| |
| 1) IDENTIFY INSTA HOT MODEL # AND MODIFY LOAD |
| CALCULATION AND PANEL SCHEDULE AS REQUIRED. |
| |
| 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16, 110.22 |
| |
| 4) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT |
| FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING |
| OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS |
| SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE |
| AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14 |
| |
| 5) EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. NEC 600.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |