Plan Review Details - Permit 14101066
Plan Review Stops For Permit 14101066
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-02-02 Cont ID  
Sent By dhayes Date 2015-02-02 Time 10:35 Rev Time 0.00
Received By dhayes Date 2015-02-02 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 13:59 Rev Time 0.00
Received By dhayes Date 2014-12-31 Time 13:59 Sent To  
Notes
2014-12-31 15:29:3012/31/2014
 PROJECT: COASTAL WAREHOUSE
 PERMIT#: 14101066
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED WAS NOT SIGNED OR SEALED BY THE
 ENGINEER ON THE TITLE BLOCK.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471,
 668.001-668.006 FBC, WPB AMENDMENTS 107.2.1
  
 2) FL SS 471.025 - SEALS 668.001-668.006.
 (1) ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS,
 OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND
 BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
 (3) NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED HIS
 OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR OTHER
 DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-15 Cont ID  
Sent By dhayes Date 2014-11-15 Time 13:06 Rev Time 0.00
Received By dhayes Date 2014-11-15 Time 12:45 Sent To  
Notes
2014-11-15 13:06:4911/15/2014
 PROJECT: COASTAL WAREHOUSE
 PERMIT#: 14101066
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE INFORMATION ON THE PLAN FOR THE METHODS AND
 MATERIALS PROPOSED FOR THE INSTALLATION OF THE SYSTEM.
 THE FLOOR PLAN INDICATE A CONNECTION FROM A FEW DEVICES
 TO OTHER DEVICES BUT DIAGRAM IS INCOMPLETE. PROVIDE A
 COMPLETE AND DETAILED PLAN OF THE INSTALLATION
 INCLUDING THE COMPLETE INTERCONNECTION BETWEEN DEVICES
 AND THE TERMINATION TO THE FACP ALL IN ACCORDANCE WITH
 THE REQUIREMENTS IN NEC 760.
  
 2) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL ON THE
 FLOOR PLAN ALONG WITH AN ELECTRICAL PANEL SCHEDULE
 INCLUDING THE FACP CIRCUIT INDICATING THAT IT WILL BE
 INSTALLED WITH A LOCK ON DEVICE AND BE IDENTIFIED WITH
 PERMANENT RED MARKING.
  
 3) ALL INFORMATION ON THE PLANS INCLUDING THE
 SPECIFICATIONS AND MANUFACTURER PRODUCT INFORMATION
 DATA SHALL BE LEGIGBLE. THE BATTERY CALCULATIONS AND
 CIRCUIT DETAIL CHARTS ARE NOT LEGIBLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-01-22 Cont ID  
Sent By pleduc Date 2015-01-22 Time   Rev Time 0.00
Received By pleduc Date 2015-01-22 Time 13:07 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-31 Time 15:29 Rev Time 0.00
Received By pleduc Date 2014-12-19 Time 10:59 Sent To E
Notes
2014-12-19 11:07:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO.
  
 ADD 1 STROBE IN THE DISPLAY AREA.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By wjolin Date 2014-11-07 Time 11:07 Rev Time 0.00
Received By wjolin Date 2014-11-07 Time 10:59 Sent To E
Notes
2014-11-07 11:05:18THIS PLAN WAS REVIEWED AND FAILED WITH THE FOLLOWING
 COMMENTS;
  
 PERMIT# 14101066
  
 PROVIDE LEGIBLE BATTERY CALCULATIONS.
  
 ALL DUCT DETECTORS TO INITIATE GENERAL ALARM.
  
 REMOTE PULL IS NOT PROVIDED AT REQUIRED EXIT SOUTH WALL
 OF NON AC STORAGE.
  
 CEILING HEIGHT IS NOT PROVIDED, ALSO CANDELA IS NOT
 PROVIDED.
  
 ROY LINDOW
 WEST PALM BEACH FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-02 Cont ID  
Sent By dhayes Date 2015-02-02 Time 10:35 Rev Time 0.00
Received By dhayes Date 2015-01-16 Time 17:40 Sent To  
Notes
2015-01-16 17:40:39RE-SUBMITTAL SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-31 Cont ID  
Sent By wjolin Date 2014-12-31 Time 15:29 Rev Time 0.00
Received By dhayes Date 2014-12-17 Time 07:08 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-15 Cont ID  
Sent By dhayes Date 2014-11-15 Time 13:07 Rev Time 0.00
Received By dhayes Date 2014-10-31 Time 14:03 Sent To  
Notes
2014-10-31 14:03:25ROUTED TO FIRE