Plan Review Details - Permit 14101066
Plan Review Stops For Permit 14101066 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2015-02-02 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-02 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-02 |
Time |
10:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2014-12-31 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-12-31 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-12-31 |
Time |
13:59 |
Sent To |
|
|
Notes |
2014-12-31 15:29:30 | 12/31/2014 | | PROJECT: COASTAL WAREHOUSE | | PERMIT#: 14101066 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE PLANS SUBMITTED WAS NOT SIGNED OR SEALED BY THE | | ENGINEER ON THE TITLE BLOCK. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, | | 668.001-668.006 FBC, WPB AMENDMENTS 107.2.1 | | | | 2) FL SS 471.025 - SEALS 668.001-668.006. | | (1) ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, | | OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND | | BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS | | PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE | | SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH | | SAID SEAL. | | (3) NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED HIS | | OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY PLAN, | | SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR OTHER | | DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT | | LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER | | PROFESSION OR SPECIALTY THEREIN. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-11-15 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-15 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-11-15 |
Time |
12:45 |
Sent To |
|
|
Notes |
2014-11-15 13:06:49 | 11/15/2014 | | PROJECT: COASTAL WAREHOUSE | | PERMIT#: 14101066 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) PROVIDE INFORMATION ON THE PLAN FOR THE METHODS AND | | MATERIALS PROPOSED FOR THE INSTALLATION OF THE SYSTEM. | | THE FLOOR PLAN INDICATE A CONNECTION FROM A FEW DEVICES | | TO OTHER DEVICES BUT DIAGRAM IS INCOMPLETE. PROVIDE A | | COMPLETE AND DETAILED PLAN OF THE INSTALLATION | | INCLUDING THE COMPLETE INTERCONNECTION BETWEEN DEVICES | | AND THE TERMINATION TO THE FACP ALL IN ACCORDANCE WITH | | THE REQUIREMENTS IN NEC 760. | | | | 2) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL ON THE | | FLOOR PLAN ALONG WITH AN ELECTRICAL PANEL SCHEDULE | | INCLUDING THE FACP CIRCUIT INDICATING THAT IT WILL BE | | INSTALLED WITH A LOCK ON DEVICE AND BE IDENTIFIED WITH | | PERMANENT RED MARKING. | | | | 3) ALL INFORMATION ON THE PLANS INCLUDING THE | | SPECIFICATIONS AND MANUFACTURER PRODUCT INFORMATION | | DATA SHALL BE LEGIGBLE. THE BATTERY CALCULATIONS AND | | CIRCUIT DETAIL CHARTS ARE NOT LEGIBLE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2015-01-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-01-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-01-22 |
Time |
13:07 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-12-19 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-12-31 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-12-19 |
Time |
10:59 |
Sent To |
E |
|
Notes |
2014-12-19 11:07:20 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO. | | | | ADD 1 STROBE IN THE DISPLAY AREA. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-11-07 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-11-07 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2014-11-07 |
Time |
10:59 |
Sent To |
E |
|
Notes |
2014-11-07 11:05:18 | THIS PLAN WAS REVIEWED AND FAILED WITH THE FOLLOWING | | COMMENTS; | | | | PERMIT# 14101066 | | | | PROVIDE LEGIBLE BATTERY CALCULATIONS. | | | | ALL DUCT DETECTORS TO INITIATE GENERAL ALARM. | | | | REMOTE PULL IS NOT PROVIDED AT REQUIRED EXIT SOUTH WALL | | OF NON AC STORAGE. | | | | CEILING HEIGHT IS NOT PROVIDED, ALSO CANDELA IS NOT | | PROVIDED. | | | | ROY LINDOW | | WEST PALM BEACH FIRE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-02-02 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-02 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-01-16 |
Time |
17:40 |
Sent To |
|
|
Notes |
2015-01-16 17:40:39 | RE-SUBMITTAL SENT TO FIRE SHELF FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-12-31 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-12-31 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-12-17 |
Time |
07:08 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-11-15 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-15 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-10-31 |
Time |
14:03 |
Sent To |
|
|
Notes |
2014-10-31 14:03:25 | ROUTED TO FIRE |
|
|
|