Plan Review Details - Permit 14101018
Plan Review Stops For Permit 14101018
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-22 Cont ID  
Sent By jwitmer Date 2014-11-22 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2014-11-22 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-08 Cont ID  
Sent By dhayes Date 2014-12-08 Time 12:13 Rev Time 0.00
Received By dhayes Date 2014-12-08 Time 10:38 Sent To  
Notes
2014-12-08 12:13:2512/8/2014
 PROJECT: TENANT IMPROVEMENTS, PP STE1000
 PERMIT#: 14101018
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) NEC 240.4 CLARIFICATION REQUIRED. SHEET E1.1
 INDICATES A TWO POLE 30AMP CIRCUIT #27/29 WITH TWO #8CU
 FEEDING CU-10E-9 LOCATED ON THE ROOF. HOWEVER,
 ELECTRICAL KEYNOTE 1 ON THE SAME SHEET STATES CONNECT
 CU-10E-9 TO AHU-10E-9 USING TWO #12 1#12G IN 1/2"
 CONDUIT. PLEASE INDICATE WHERE, HOW AND WITH WHAT TYPE,
 SIZE AND STYLE OF OCPD PROTECT THE #12 CIRCUIT FROM THE
 CU-10E-9 TO AHU-10E-9.
  
 2) NEC 314.27(C ) BOXES LISTED SPECIFICALLY FOR THIS
 APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED IN
 THE FLOOR. PROVIDE MANUFACTURER'S SPECIFICATION DATA
 SHEETS FOR THE OUTLETS LOCATED IN THE FLOOR.
 A. NEC 300.21 PROVIDE A FIRE STOP DETAIL FOR ALL WALL
 AND FLOOR PENETRATIONS OF FIRE RATED ASSEMBLIES.
 B. FBC 713.4 PENETRATIONS OF A FLOOR, FLOOR/CEILING
 ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY NOT REQUIRED TO BE ENCLOSED IN A SHAFT BY
 SECTION 708.2 SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTIONS 713.4.1 THROUGH 713.4.2.2.
  
 3) FBC 505.2.2 EX 4.SPACES WHERE AN AUTOMATIC SHUTOFF
 WOULD ENDANGER OCCUPANT SAFETY OR SECURITY. ELECTRICAL
 ROOM LIGHTS SHOULD NOT BE CONNECTED TO A MOTION SENSOR
 SWITCH.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, NETWORK, DATA, COMMUNICATION, SITE
 LIGHTING, AND GENERATORS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-03 Cont ID  
Sent By scaldero Date 2014-11-03 Time 12:49 Rev Time 0.00
Received By scaldero Date 2014-11-03 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-11 Cont ID  
Sent By dhayes Date 2014-12-11 Time 08:05 Rev Time 0.00
Received By skennedy Date 2014-10-30 Time 16:17 Sent To  
Notes
2014-12-08 12:37:23FIRE SPRINKLER PLAN NOT STAMPED. EMAILED TO FIRE AND
 MECHANICAL. RETURNED TO C06 TO COMPLETE REVIEWS. DAH
2014-10-31 16:18:09C06

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-02 Cont ID  
Sent By rbergsma Date 2014-12-02 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-01 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-13 Cont ID  
Sent By tklarge Date 2014-11-13 Time 14:41 Rev Time 0.00
Received By tklarge Date 2014-11-12 Time 10:48 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved