Plan Review Details - Permit 14100871
Plan Review Stops For Permit 14100871
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-19 Cont ID  
Sent By rmcdouga Date 2014-11-19 Time 12:42 Rev Time 0.00
Received By rmcdouga Date 2014-11-19 Time 12:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By dhayes Date 2014-11-05 Time 09:11 Rev Time 0.00
Received By dhayes Date 2014-11-05 Time 09:11 Sent To B
Notes
2014-11-05 09:23:5411/5/2014
 PROJECT: ATT SIGN
 PERMIT#: 14100871
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING
 ? FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3
 LISTING.
  
 2) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 4) PROVIDE PROOF OF OVERALL VALUE OF THE PROJECT IS
 REQUIRED AND SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ARCHITECTURAL DESIGN FEES, FABRICATION,
 STRUCTURAL, AND ELECTRICAL, PLUS OVERHEAD AND PROFIT.
 FINAL PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL. FBC WPB AMENDMENTS. SECTION 109.3
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2014-11-05 09:11:36TO MISC. 2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-19 Cont ID  
Sent By rmcdouga Date 2014-11-19 Time 12:43 Rev Time 0.00
Received By rmcdouga Date 2014-10-28 Time 12:42 Sent To  
Notes
2014-10-28 10:06:52ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-04 Cont ID  
Sent By ajones Date 2014-11-04 Time 16:28 Rev Time 0.00
Received By ajones Date 2014-11-04 Time 16:28 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved