Plan Review Details - Permit 14100830
Plan Review Stops For Permit 14100830 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-12-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-12-01 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-12-01 |
Time |
14:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-11-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-11-05 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-11-05 |
Time |
11:25 |
Sent To |
FIRE |
|
Notes |
2014-11-05 11:31:50 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC 2010 | | 107.2.1: | | | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | CODE AND RELEVANT LAWS, ORDINANCES, RULES | | AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). | | | | SEE ALSO FBC 107.2.1.4: QUALITY OF BUILDING PLANS: | | | | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | MEDIUM. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN | | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION | | PROGRAM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF | | FLORIDA STATUTES. | | | | 2. SEE ALSO 107.3.5, MINIMUM PLAN REVIEW CRITERIA FOR | | BUILDINGS. PLAN SUBMITTED IS NOT TO SCALE, DOES NOT | | HAVE ROOMS LABELED AS TO USE, DETAIL FOR PROPOSED WALL | | AND DOOR FRAMING NOT PROVIDED, OVERALL DIMENSIONS NOT | | SHOWN. PROVIDE AN ARCHITECTURAL QUALITY PLAN, TO SCALE, | | WHICH SHOWS PROPOSED IMPROVEMENT. | | | | 3. AS IT APPEARS THAT YOU ARE ADDING BEDROOMS, IMPACT | | FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED (PER | | WILLIE SWOPE). PLEASE CALL 561-233-5025 FOR MORE | | INFORMATION. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2014-11-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-11-21 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-11-21 |
Time |
10:28 |
Sent To |
FIRE |
|
Notes |
2014-11-21 10:49:30 | 11/21/2014 | | PROJECT: BEDROOM WALL | | PERMIT#: 14100830 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314 AND 315. PROVIDE OR VERIFY THE REQUIRED SMOKE | | DETECTORS IN THE LOCATIONS REQUIRED BY THE FBC-R314, | | 315 | | | | 2) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL | | SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE | | OUTLET.). NEC 210.52(A)(1) IT APPEARS AS THOUGH AN | | ADDITIONAL OUTLET IS REQUIRED IN THE NEW PARTITION. | | EITHER INDICATE A NEW OUTLET WILL BE INSTALLED OR | | INDICATE HOW THE EXISTING OUTLETS COMPLY WITH THE NEC | | 210.52(A)(1) | | | | 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | | | 4) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET | | SHALL BE INSTALLED IN EVERY HABITABLE ROOM AND | | BATHROOM. CLARIFY HOW THE INTENT OF NEC 210.70(A)(1) | | WILL BE MET. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-11-14 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-14 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-11-14 |
Time |
16:23 |
Sent To |
|
|
Notes |
2014-11-14 16:32:28 | 11/14/2014 | | PROJECT: BEDROOM WALL | | PERMIT#: 14100830 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) MINIMUM ELECTRICAL PLAN REVIEW CRITERIA SHALL | | INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: WIRING, | | SERVICES, FEEDERS AND BRANCH CIRCUITS, OVERCURRENT | | PROTECTION, GFCIS, GROUNDING, WIRING METHODS AND | | MATERIALS, WPB AMENDMENTS TO FBC 107.3.5.1.2 | | | | 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | BY THE BUILDING OFFICIAL. | | WPB AMENDMENTS TO FBC 107.2.1 | | | | 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314 AND 315 | | | | 4) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL | | SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE | | OUTLET. 210.52(A)(1) | | | | 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-11-24 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-11-24 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-11-21 |
Time |
15:48 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-11-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-11-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-11-06 |
Time |
11:20 |
Sent To |
E |
|
Notes |
2014-11-06 11:36:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | THE SUBMITTED PLAN LACKS THE REQUIRED DETAIL REGARDING | | LIFE SAFETY SYSTEMS DEVICE LOCATIONS, INCLUDING BUT NOT | | LIMITED TO, SMOKE DETECTORS, SPRINKLER HEADS, AND FIRE | | ALARM DEVICES; BOTH EXISTING AND PROPOSED. | | | | WHAT IS THE PROPOSED OCCUPANCY TYPE, RESIDENTIAL, | | BUSINESS OR OTHER? | | | | THE ROOMS ARE NOT LABELED AND IS THE DRAWING THE ENTIRE | | SPACE OR JUST A PORTION OF A LARGER SPACE? | | | | A LIFE SAFETY PLAN IS NOT PROVIDED, INDICATING ALL | | OCCUPANCY LOADS, EXIT PATHS, EXITS SIGNS(IF REQUIRED | | FOR BUSINESS), EMERGENCY LIGHTS(IF REQUIRED FOR | | BUSINESS) AND EXIT DOORS. | | | | PLEASE ALSO REVIEW OTHER DEPARTMENT COMMENTS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-12-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-12-01 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-11-20 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-11-14 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-14 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-10-28 |
Time |
13:26 |
Sent To |
|
|
Notes |
2014-11-05 11:32:12 | 11/5 TO FIRE | | | 2014-10-28 13:26:54 | SENT TO BLDG. BOX <$5K. JW |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2014-12-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-14 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2014-10-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-10-28 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-10-28 |
Time |
13:27 |
Sent To |
|
|
Notes |
|
|
|