Plan Review Details - Permit 14100783
Plan Review Stops For Permit 14100783
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-16 Cont ID  
Sent By dhayes Date 2014-12-16 Time 16:59 Rev Time 0.00
Received By dhayes Date 2014-12-16 Time 16:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-27 Cont ID  
Sent By dhayes Date 2014-10-27 Time 16:30 Rev Time 0.00
Received By dhayes Date 2014-10-27 Time 16:30 Sent To FIRE
Notes
2014-12-17 07:57:231.) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12(F)
  
 2.) OUTLETS INSTALLED OUTDOORS OR WITHIN 6' OF A SINK
 SHALL BE GFCI PROTECTED. NEC 210.8(B)(4)
 A.) GFI OUTLETS INSTALLED IN DAMP OR WET LOCATIONS
 SHALL ALSO BE THE WEATHER RESISTANT TYPE. NEC
 406.8(B)(1)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-12 Cont ID  
Sent By wjolin Date 2014-12-12 Time 16:28 Rev Time 0.00
Received By wjolin Date 2014-12-12 Time 16:24 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-31 Cont ID  
Sent By wjolin Date 2014-10-31 Time 16:08 Rev Time 0.00
Received By wjolin Date 2014-10-31 Time 15:52 Sent To  
Notes
2014-10-31 16:08:54300 COURTNEY LAKES CIRCLE
 TRACKING #14100783
 MASTER #13051012
 FA #14020403
 FIRE DEPT COMMENTS
  
 SHEET E1.71 SHOWS A COMPLETE MANUAL FIRE ALARM SYSTEM
 PROTECTING THE CLUBHOUSE; HOWEVER, THE CONTRACTOR'S
 SHOP DRAWINGS SHOW NO SUCH PROTECTION AND INDICATE THAT
 ONLY A CONTROL PANEL FOR MONITORING THE APARTMENT
 BUILDING'S SPRINKLER SYSTEMS IS TO BE INSTALLED IN THE
 CLUBHOUSE. BOTH THE ENGINEER'S AND CONTRACTOR'S
 DRAWINGS ARE ACCEPTABLE BUT THEY ARE IN CONFLICT WITH
 EACHOTHER. PLEASE COORDINATE WHAT LEVEL OF FIRE
 PROTECTION IS TO BE PROVIDED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WPB FIRE RESCUE
 561.804.4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-16 Cont ID  
Sent By dhayes Date 2014-12-16 Time 16:59 Rev Time 0.00
Received By dhayes Date 2014-12-08 Time 12:00 Sent To  
Notes
2014-12-09 12:00:39SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-31 Cont ID  
Sent By wjolin Date 2014-10-31 Time 16:09 Rev Time 0.00
Received By wjolin Date 2014-10-25 Time 07:04 Sent To  
Notes
2014-10-25 07:05:07SENT TO D HAYES