Plan Review Details - Permit 14100755
Plan Review Stops For Permit 14100755
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-12-10 Cont ID  
Sent By shill Date 2014-12-10 Time 17:26 Rev Time 0.00
Received By shill Date 2014-12-10 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-09 Cont ID  
Sent By shill Date 2014-12-09 Time 08:04 Rev Time 0.00
Received By shill Date 2014-12-09 Time 08:04 Sent To  
Notes
2014-12-09 08:58:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ENGINEER HAS RESPONDED TO COMMENTS WITH AN
 EXPLANATION REFERRING TO A HIP ROOF AND A MONOSLOPE
 ROOF.
  
 ENGINEERING IS NOT REQUIRED FOR THE HIP ROOF. REVISION
 DESCRIPTION IS: "CHANGE / ADD SMALL REAR FLAT ROOF" .
 ENGINEERING IS REQUIRED FOR THE FLAT ROOF. ENGINEERING
 HAS BEEN REVISED, SLOPE IS SHOWN AS 0, BUT THE RESPONSE
 LETTER REFERS TO A HIP ROOF AND MONOSLOPE ROOF.
  
 ENGINEERING APPEARS TO NOW BE CORRECT BUT IS NOT
 NECESSARY IF THIS IS A HIP ROOF. CONTRACTOR TO CONFIRM
 THAT THIS IS A FLAT DECK, FBC 107.
  
 2. VALUE STATED IS $0 TO ADD THE FLAT DECK TO THE SCOPE
 OF WORK. PLEASE PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB, FBC 109.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-14 Cont ID  
Sent By shill Date 2014-11-14 Time 16:33 Rev Time 0.00
Received By shill Date 2014-11-14 Time 16:29 Sent To  
Notes
2014-11-14 16:33:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGN PRESSURE FOR ZONE 3 IS THE SAME AS ZONE 2.
 USE OF ZONE 2 PRESSURES FOR CORNERS REQUIRES A PARAPET
 ON ALL FOUR SIDES. AERIAL PHOTOGRAPHS APPEAR TO SHOW A
 FLAT ROOF OVER THE PORCH AT THE REAR OF THE HOUSE, NO
 PARAPET. PLEASE PROVIDE INFORMATION REGARDING PARAPET
 AND HEIGHT, FBC 2010 RESIDENTIAL 301.
  
 2. ENGINEER TO CLARIFY MEANING OF "ZONE 2 & 2' " AND
 "ZONE 3 & 3' ". FBC 107
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-23 Cont ID  
Sent By shill Date 2014-10-23 Time 16:34 Rev Time 0.00
Received By shill Date 2014-10-23 Time 16:34 Sent To  
Notes
2014-10-23 16:37:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ORIGINAL PERMIT APPLICATION INDICATED THAT THIS
 STRUCTURE HAS A WOOD DECK. SEE PAGE 17 OF THE NOA; -45
 PSF IS THE LIMITATION FOR THE ASSEMBLY SELECTED. AS
 GENERAL LIMITATION #9 IS NOTED FOR THIS ASSEMBLY, YOU
 CANNOT USE ENGINEERING FOR ENHANCED FASTENING (SEE
 GENERAL LIMITATION #9 ON THE LAST PAGE OF THE NOA). A
 DIFFERENT ASSEMBLY MUST BE SELECTED AND, IF THE
 ASSEMBLY DOES NOT MEET THE DESIGN PRESSURES FOR ZONES 2
 & 3, ASSEMBLY MUST REFER TO GENERAL LIMITATION #7 AND
 ENGINEERING INCLUDED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-09 Cont ID  
Sent By shill Date 2014-12-09 Time 09:14 Rev Time 0.00
Received By shill Date 2014-12-08 Time 11:35 Sent To  
Notes
2014-12-08 11:36:10TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-14 Cont ID  
Sent By shill Date 2014-11-14 Time 16:33 Rev Time 0.00
Received By shill Date 2014-11-14 Time 08:43 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-23 Cont ID  
Sent By shill Date 2014-10-23 Time 16:34 Rev Time 0.00
Received By shill Date 2014-10-23 Time 16:34 Sent To  
Notes
***NONE***