Plan Review Details - Permit 14100705
Plan Review Stops For Permit 14100705
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-04 Cont ID  
Sent By jgomez Date 2014-12-04 Time 16:02 Rev Time 0.00
Received By jgomez Date 2014-12-04 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-03 Cont ID  
Sent By jgomez Date 2014-12-03 Time 15:17 Rev Time 0.00
Received By jgomez Date 2014-12-03 Time 14:44 Sent To  
Notes
2014-12-01 19:07:33RESIDENTIAL (R3) SCREEN ENCLOSURE SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE DETAILS FOR THE 5" SUPER GUTTER CONNECTION.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
 ***NOTE: E-MAIL RESPONSE DIDN'T INCLUDE THIS DETAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By jgomez Date 2014-11-25 Time 16:49 Rev Time 0.00
Received By jgomez Date 2014-11-25 Time 16:49 Sent To  
Notes
2014-11-25 16:57:42RESIDENTIAL (R3) SCREEN ENCLOSURE BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SCREEN ENCLOSURE SITE SPECIFIC LAYOUT. PROVIDE THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN AS REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
 ***NOTE: SEE ZONING COMMENTS. SCREEN ENCLOSURE
 DIMENIOSN MAY NEED TO BE REVISED.
  
 2- SCREEN ENCLOSURE FLOOR PLAN AND ELEVATIONS SHOWN ON
 THE SITE SPECIFIC LAYOUT DON'T MATCH. CLARIFY WHY THERE
 IS A 2X9 BEAM SHOWN ON THE ELEVATIONS. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CLEARLY IDENTIFY SIZE OF ALL FRAMING MEMBERS. SCREEN
 ENCLOSURE LAYOUT SHOW DIFFERENT PURLIN SIZES, DIFFERENT
 K-BRACING SIZES, DIFFERENT EAVE RAIL SIZES, ETC. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 4- PROVIDE DETAILS FOR THE 5" SUPER GUTTER CONNECTION.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 5- ACCORDING TO TABLE 101(F)11 SUBMITTED THE ALLOWABLE
 SPAN FOR THE 2X9 BEAM IS 19'-11". THE ACTUAL BEAM SPAN
 SHOWN ON THE SCREEN ENCLOSURE LAYOUT IS 20'-7". REVISE
 AS REQUIRED TO COMPLY. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 6- ACCORDING TO TABLE 102F SUBMITTED THE ALLOWABLE SPAN
 FOR PURLINS FOR THE 2X7 PURLIN IS 6'-10". THE ACTUAL
 PURLIN SPAN SHOWN ON THE SCREEN ENCLOSURE LAYOUT IS
 7'-3 5/8". REVISE AS REQUIRED TO COMPLY. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 7- ACCORDING TO TABLE 105 SUBMITTED THE ALLOWABLE POST
 HEIGHT FOR 3/8" CONCRETE FASTENERS IS 7.2'. THIS
 DOESN'T MATCH THE POST SPAN SHOWN ON PLANS . REVISE AS
 REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 8- PROVIDE SIZE OF EXISTING FOOTING. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 9-PROVIDE ONLY THE DETAILS AND TABLES THAT APPLY TO
 THIS PROJECT. SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-04 Cont ID  
Sent By jgomez Date 2014-12-04 Time 15:48 Rev Time 0.00
Received By jgomez Date 2014-12-04 Time 15:09 Sent To  
Notes
2014-12-04 15:10:04E-MAIL RESPONSE FROM RENE CANTIN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-01 Cont ID  
Sent By jgomez Date 2014-12-01 Time 19:03 Rev Time 0.00
Received By jgomez Date 2014-12-01 Time 19:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-25 Cont ID  
Sent By jgomez Date 2014-11-25 Time 16:57 Rev Time 0.00
Received By jgomez Date 2014-10-22 Time 16:53 Sent To  
Notes
2014-10-22 16:54:25ZONING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-03 Cont ID  
Sent By sgraham Date 2014-12-03 Time 08:37 Rev Time 0.00
Received By sgraham Date 2014-12-03 Time 09:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-23 Cont ID  
Sent By sgraham Date 2014-10-23 Time 15:32 Rev Time 0.00
Received By sgraham Date 2014-10-23 Time 15:32 Sent To  
Notes
2014-10-23 15:37:1810/23/14 ZONING FAILED
  
 1. THE SIDE SETBACK FOR IBIS IS 3' ON BOTH SIDES FOR
 SCREEN ENCLOSURES.