Plan Review Details - Permit 14100702
Plan Review Stops For Permit 14100702
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-04 Cont ID  
Sent By jgomez Date 2014-12-04 Time 16:51 Rev Time 0.00
Received By jgomez Date 2014-12-04 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-01 Cont ID  
Sent By jgomez Date 2014-12-01 Time 15:55 Rev Time 0.00
Received By jgomez Date 2014-12-01 Time 15:52 Sent To  
Notes
2014-12-01 15:55:14RESIDENTIAL (R3) SCREEN ENCLOSURE, SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ALLOWABLE SPAN FOR GIRTS OR CHAIR RAILS
 CIRCLED WITH RED INK ON TABLE 204F SUBMITTED. THE
 SPACING IS NOT 4' 4.5" AS SPECIFIED ON THE E-MAIL. SEE
 PLANS AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: THIS DIMENSION IS MORE CRITICAL ON THE ALLOWABLE
 SPAN FOR THE SIDE WALLS. LOOK ON THE DIMENSIONS FOR THE
 TOP CHAIR RAIL (3'-5" AND 6'-0"). ALSO, THE REVISED
 TABLE WAS NOT SUBMITTED IN THIS E-MAIL. RE-SUBMIT NEW
 RE-REVISED TABLE.
  
 *****NOTE: THE CITY AMENDMENTS CAN BE VIEWED AND
 PRINTED FROM THE CITY OF WEST PALM BEACH WEBSITE.
 PLEASE LOOK UNDER DEVELOPMENT SERVICES DEPARTMENT AND
 NAVIGATE IN THE PERMITS SECTION. LOOK FOR "BUILDING
 CODE AMENDMENTS".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By jgomez Date 2014-11-26 Time 11:02 Rev Time 0.00
Received By jgomez Date 2014-11-26 Time 11:02 Sent To  
Notes
2014-11-26 11:39:29RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE THE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- PROVIDE DETAILS FOR THE 5" SUPPER GUTTER
 CONNECTIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 3- THE ALLOWABLE SPAN FOR PURLINS TABLE 102F SUBMITTED
 IS 4'-10". THIS DOESN'T REFLECT SPAN SHOWN ON PLANS.
 REVISE AS REQUIRED TO COMPLY. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 4- REVISE ALLOWABLE POST/COLUMN SPAN CIRCLED WITH RED
 INK ON TABLE 103F SUBMITTED. THE SPACING FOR SIDE WALL
 POSTS IS NOT 6'-6". SEE PLANS AND REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 5- REVISE ALLOWABLE SPAN FOR GIRTS OR CHAIR RAILS
 CIRCLED WITH RED INK ON TABLE 204F SUBMITTED. THE
 SPACING IS NOT 4'-0". SEE PLANS AND REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- ALLOWABLE POST HEIGHT FOR 3/8" CONCRETE FASTENERS ON
 TABLE 105 SUBMITTED IS 8.3'. THIS DOESN'T REFLECT POST
 HEIGHT IN PLANS. REVISE AS REQUIRED TO COMPLY. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 7- SPECIFY SIZE OF EXISTING FOOTING. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 8- PROVIDE ONLY THE DETAILS AND TABLES THAT APPLY TO
 THIS PROJECT TO AVOID CONFLICTS OF CONFUSION. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-04 Cont ID  
Sent By jgomez Date 2014-12-04 Time 16:50 Rev Time 0.00
Received By jgomez Date 2014-12-04 Time 16:49 Sent To  
Notes
2014-12-04 16:50:01E-MAIL RESPONSE FROM RENE CANTIN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-01 Cont ID  
Sent By jgomez Date 2014-12-01 Time 15:55 Rev Time 0.00
Received By jgomez Date 2014-12-01 Time 15:52 Sent To  
Notes
2014-12-01 15:52:35E-MAIL FROM RENE CANTIN ADDRESSING COMMENTS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-26 Cont ID  
Sent By jgomez Date 2014-11-26 Time 11:02 Rev Time 0.00
Received By jgomez Date 2014-10-22 Time 13:09 Sent To  
Notes
2014-10-22 13:10:08ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-10-23 Cont ID  
Sent By sgraham Date 2014-10-23 Time 10:44 Rev Time 0.00
Received By sgraham Date 2014-10-23 Time 10:44 Sent To B
Notes
***NONE***