Plan Review Details - Permit 14100647
Plan Review Stops For Permit 14100647
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-07 Cont ID  
Sent By JWITMER Date 2014-11-07 Time 13:08 Rev Time 0.00
Received By jwitmer Date 2014-11-07 Time 11:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-28 Cont ID  
Sent By SKENNEDY Date 2014-10-28 Time 11:05 Rev Time 0.00
Received By rlecky Date 2014-10-28 Time 10:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-23 Cont ID  
Sent By pleduc Date 2014-10-23 Time   Rev Time 0.00
Received By pleduc Date 2014-10-23 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-24 Cont ID  
Sent By tklarge Date 2014-12-24 Time 08:13 Rev Time 0.00
Received By tklarge Date 2014-12-23 Time 12:42 Sent To  
Notes
2014-12-23 12:43:55TO TKLARGE DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By skennedy Date 2014-12-02 Time 09:49 Rev Time 0.00
Received By skennedy Date 2014-10-21 Time 11:05 Sent To  
Notes
2014-10-22 11:06:11REVISION SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By HMOSER Date 2014-12-01 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-01 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-24 Cont ID  
Sent By tklarge Date 2014-12-24 Time 08:13 Rev Time 0.00
Received By tklarge Date 2014-12-24 Time 08:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-01 Cont ID  
Sent By JWITMER Date 2014-11-01 Time 10:04 Rev Time 0.00
Received By tklarge Date 2014-11-01 Time 10:04 Sent To  
Notes
2014-11-01 10:04:441) A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 OF
 THE 2010 FL. PLUMBING CODE. THE FL. ACCESSIBILITY CODE
 SEC. 211.2 REQUIRES A MINIMUM OF TWO FOUNTAINS. THE
 DRINKING FOUNTAINS SHALL COMPLY WITH SECS. 211 & 602 OF
 THE 2010 FACBC.
 2) THE 2" PIPE FOR THE WATER HEATER PAN DRAIN WILL NOT
 HAVE ANYWAY OF RESEALING THE P-TRAP. COMPLY W/ 2010 FBC
 SEC.1002.4.
 3) THE TWO LAVS IN THE MEN'S RESTROOM REQUIRE VENTS.
 FPC SEC.901.2, 901.2.1.
 4) CLEANOUTS ARE REQD. IN ALL STACKS PER 2010 FPC
 SEC.708.3.4.
 5) THE VIEW OF TWO RESTROOM'S DRAINAGE SYSTEM IS
 DIFFICULT TO READ DUE TO THE NAMES OF THE RESTROOMS
 PRINTED OVER THE RISER.SUBMIT A CLEAR, LEGIBLE CODE
 COMPLIANT RISER DOCUMENT.
 6) AS PRESENTLY DESIGNED THERE ARE TWO MANY OF THE SAME
 TYPE OF FIXTURES ON A WET VENT. COMPLY W/ 2010 FPC
 SEC.909.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  