Plan Review Details - Permit 14100630
Plan Review Stops For Permit 14100630
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-04 Cont ID  
Sent By shill Date 2015-05-04 Time 14:02 Rev Time 0.00
Received By shill Date 2015-05-04 Time 09:59 Sent To  
Notes
2015-05-04 14:06:52****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE PROVISO ITEM FROM PERMIT ISSUANCE:
  
 (33). EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO
 ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS
 AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE
 INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF
 EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED;
 PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS.
  
 PLEASE INCORPORATE THIS LANGUAGE INTO ARCHITECT'S PLAN
 AT THIS TIME.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-28 Cont ID  
Sent By shill Date 2015-02-28 Time 13:11 Rev Time 0.00
Received By shill Date 2015-02-28 Time 10:02 Sent To  
Notes
2015-02-28 13:14:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE PROVISO ITEM FROM PERMIT ISSUANCE:
  
 (33). EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO
 ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS
 AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE
 INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF
 EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED;
 PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS. THIS
 SHEET IS NOT REQUIRED TO BE SUBMITTED AT THIS TIME.
  
 2ND REVIEW, I APOLOGIZE FOR THE AMBIGUOUS LANGUAGE IN
 PREVIOUS REVIEW. PROVISO 33 WAS FROM THE TIME OF PERMIT
 ISSUANCE (AND COPIED AND PASTED INTO REVISION REVIEW).
 PLAN WAS REDLINED AT THAT TIME WITH THE REQUEST THAT
 THE LANGUAGE BE INCORPORATED INTO THE ARCHITECT?S PLAN
 BUT NOT REQUIRED TO BE SUBMITTED AT THAT TIME (MEANING
 THE TIME OF ISSUANCE OF THE PERMIT).
  
 THE LANGUAGE WAS NOT INCORPORATED INTO THE PLAN, AS
 EVIDENCED BY THE REVISION SUBMITTED WITHOUT THE REVISED
 LANGUAGE REGARDING GATES. SO THAT REQUREMENTS ARE CLEAR
 TO ALL PARTIES (CONTRACTOR, SUBS, INSPECTORS), PLEASE
 INCORPORATE THIS LANGUAGE INTO ARCHITECT'S PLAN AT THIS
 TIME.
  
 3. A0.1.2 AND OTHER SHEETS (LEVELS), EXIT ACCESS IS
 INTERRUPTED BY THE PARKING GARAGE AREA, SEE FBC 1020.1;
 LEVEL OF PROTECTION IS TO BE MAINTAINED UNTIL EXIT
 DISCHARGE. OCCUPANT ENTERS THE RATED CORRIDOR FROM THE
 UNIT, THEN ENTERS THE PARKING GARAGE OR OTHER NON RATED
 STORAGE AREA (SEE MARK ON PLAN), THEN ENTERS THE RATED
 EXIT STAIR. PLEASE REVISE TO PROVIDE CONTINUOUS
 PROTECTION.
 2ND REVIEW, THIS PORTION OF THE PLAN WAS NOT REVISED.
 SHEET A0.1.2 HAS BEEN MARKED TO NOTE LOCATION OF NON
 CONTINUITY.
  
 8. A0.1.5, 8TH LEVEL LIFE SAFETY PLAN, SOME ITEMS FROM
 THE ROOF DECK BELOW ARE NOT GREYED OUT. FOR INSTANCE, A
 DOOR IS SHOWN OPENING INTO WHAT APPEARS TO BE A
 CONCRETE EYEBROW TO WHAT APPEARS TO BE OPEN SPACE, ROOF
 DECK BELOW (AT STAIR 3). THIS DOOR IS NOT SHOWN ON
 A2.1.8. PLEASE CORRELATE, GREY OUT ITEMS NOT ACTUALLY A
 PART OF THE 8TH LEVEL, OR PROVIDE AREA/ROOM DESIGNATION
 FOR CLARITY, FBC 107.
 2ND REVIEW, PURPOSE OF THE DOOR IS NOT CLEAR. IT
 APPEARS TO OPEN ONTO A DROP TO THE LEVEL BELOW. ALSO
 THERE IS ANOTHER AREA WHICH IS NOT CLEAR AS TO WHAT THE
 RECTANGLES DEPICT. THESE TWO AREAS HAVE BEEN MARKED
 (CLOUDED) ON THE PLAN.
  
 NEW COMMENTS:
  
 REV2 1: THIS IS A REMINDER THAT TEST REPORTS FOR
 FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO
 INSTALLATION. PLEASE BE ADVISED THAT, AT THIS TIME, NO
 MANUFACTURER HAS PROVIDED ALL THREE TESTS (FLAME SPREAD
 PER FBC 603.1/803.1.1, IIC PER FBC 1207.3, STC PER FBC
 1207.2) FOR TILE ON A 6" SLAB WITHOUT A DROPPED
 CEILING. IF YOU DO NOT INTEND TO FIELD TEST FOR SOUND
 (SO A STC/IIC OF 45 IS REQUIRED RATHER THAN 50) YOU ARE
 ENCOURAGED TO ADDRESS THIS ISSUE TIMELY. PLEASE FEEL
 FREE TO CONTACT ME TO DISCUSS WHEN YOU ARE READY TO
 MAKE THE FLOORING UNDERLAYMENT SELECTION.
  
 REV2 2: LOUVERS ARE SHOWN ON SHEET A2.1.2 AND POSSIBLY
 OTHER LOCATIONS, GLASS BLOCK SHOWN ON LEGEND ON A SHEET
 ELEVATIONS (FOR EXAMPLE, A3.1.2). PRODUCT APPROVALS FOR
 ALL COMPONENTS, CLADDING, LOUVERS ARE TO BE SUBMITTED
 (AS A SUBMITTAL, NO FEE) FOR REVIEW PRIOR TO
 INSTALLATION. REVIEW BY DESIGNER OF RECORD REQUIRED
 PRIOR TO SUBMITTAL. IF SUBMITTED IN PAPER FORM, THREE
 SETS REQUIRED. PLEASE NOTE THAT DIGITAL ONLY WILL BE
 REQUIRED AT SOME POINT IN THE NEAR FUTURE.
  
 REV2 3: A2.1.6, A PORTION OF TWO APARTMENTS AND WHAT
 APPEARS TO POSSIBLY BE STAIR #2 ARE SHOWN OUTSIDE OF
 THE BUILDING ENVELOPE (NW CORNER OF BUILDING). THIS HAS
 BEEN MARKED (CLOUDED) ON THE SHEET. PLEASE REMOVE OR
 CLARIFY.
  
 REV2 4: SHEET S0.3 GENERAL NOTE M11 REFERS TO NOA
 14-0903.02 (CAST CRETE LINTELS). WHEN RESUBMITTING,
 PLEASE UPLOAD THIS NOA FOR THE PERMIT RECORD.
  
 REV2 5: SHEET M2.1.3, CORRIDOR TO STORAGE (SE PORTION
 OF BUILDING), PENETRATIONS THROUGH RATED WALLS REQUIRE
 A FIRE DAMPER, FBC 709.9, 716. 4TH FLOOR ALSO MISSING
 FD IN SAME LOCATION. CHECK ALL AND REVISE ACCORDINGLY.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-08 Cont ID  
Sent By shill Date 2014-12-08 Time 18:33 Rev Time 0.00
Received By shill Date 2014-11-09 Time 12:51 Sent To  
Notes
2014-12-08 18:33:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE PROVISO ITEMS 17 AND 33 FROM BUILDING PLAN
 REVIEW 3 FOR PERMIT 14030096 AND ADDRESS AT THIS TIME
 OR ADVISE AS TO WHEN THEY WILL BE ADDRESSED. FOR YOUR
 CONVENIENCE, THEY ARE AS FOLLOWS:
  
 (17). S1.8, ROOF DESIGN PRESSURES TREAT ZONE 3 AS ZONE
 2. PLEASE SEE ASCE7010, FIGURE 30.6-1, FOOTNOTE ,
 PARAPET TO BE EQUAL TO OR HIGHER THAN 3FT. DETAIL A
 A7.1 APPEARS TO SHOW A 2FT PARAPET AT STAIR 1, PLEASE
 CLARIFY OR INCLUDE ZONE 3 PRESSURES FOR ROOF CORNER
 ZONES LACKING A 3 FT PARAPET. REVISE ROOF PLAN TO
 CLARIFY WHERE HIGHER ZONE 3 DESIGN PRESSURES ARE
 REQUIRED. PRIOR TO ROOF PERMIT APPLICATION, THIS SHEET
 SHOULD EITHER BE REVISED OR REVISE DETAILS WHICH SHOW A
 2 FT HIGH PARAPET. THIS IS TO BE SUBMITTED AS A
 REVISION PRIOR TO ROOF PERMIT APPLICATION.
 (33). EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO
 ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS
 AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE
 INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF
 EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED;
 PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS. THIS
 SHEET IS NOT REQUIRED TO BE SUBMITTED AT THIS TIME.
  
 2. STAIR 6 EXIT DISCHARGE, SHOW PATH TO PUBLIC WAY FBC
 1027.6. AREA BETWEEN END OF LANDING SHOWN AND SIDEWALK
 IS NOT CLEAR. THE WALKWAY FROM STAIR 6 EXIT DISCHARGE
 TO PUBLIC SIDEWALK IS STILL SHOWN ON SP1 (AND OTHER
 SHEETS SUCH AS CIVILS) BUT THERE IS NO LONGER A DOOR IN
 THIS LOCATION. THE NEW EXIT DOOR LOCATION DOES NOT
 APPEAR TO INCLUDE AN EXIT DISCHARGE WHICH IS CONTINUOUS
 TO THE PUBLIC WAY.
  
 3. A0.1.2 AND OTHER SHEETS (LEVELS), EXIT ACCESS IS
 INTERRUPTED BY THE PARKING GARAGE AREA, SEE FBC 1020.1;
 LEVEL OF PROTECTION IS TO BE MAINTAINED UNTIL EXIT
 DISCHARGE AFTER THE OCCUPANT ENTERS THE EXIT. IT
 APPEARS THAT THE OCCUPANT ENTERS THE RATED CORRIDOR,
 THEN ENTERS THE PARKING GARAGE OR OTHER NON RATED
 STORAGE AREA, THEN ENTERS THE ENCLOSED STAIR. PLEASE
 REVISE TO PROVIDE CONTINUOUS PROTECTION.
  
 4. A0.1.2, A2.1.2, THE ACCESS AISLE FOR NORTH END
 ACCESSIBLE PARKING SPACE HAS BEEN REMOVED, FBC 2010
 ACCESSIBILITY 502.3. CHECK ALL SHEETS.
  
 5. A0.1.2, THE UNIT TYPES, OTHER ROOM DESIGNATIONS HAVE
 BEEN REMOVED, PLEASE RESTORE (TO EXPEDITE PLAN REVIEW)
 OR EXPLAIN RATIONALE FOR REMOVAL, FBC 107.
  
 6. A0.1.2, THE FIRE RATED WALL BETWEEN UNITS AT THE
 OPEN PORCH HAVE BEEN REMOVED. SPECIFY WALL TYPE. FOR
 INSTANCE, SHEET A0.1.2, TWO CENTER UNITS AT NORTH
 (PREVIOUSLY MARKED AS TWO A1 UNITS), OTHER LOCATIONS
 ALSO AFFECTED.
  
 7. A0.1.4, SOUTH WEST DOOR FROM DECK TO CORRIDOR SHOULD
 SWING IN THE DIRECTION OF EGRESS TRAVEL FBC 1008.1.2.
  
 8.A0.1.5, 8TH LEVEL LIFE SAFETY PLAN, SOME ITEMS FROM
 THE ROOF DECK BELOW ARE NOT GREYED OUT. FOR INSTANCE, A
 DOOR IS SHOWN OPENING INTO WHAT APPEARS TO BE A
 CONCRETE EYEBROW TO WHAT APPEARS TO BE OPEN SPACE, ROOF
 DECK BELOW (AT STAIR 3). THIS DOOR IS NOT SHOWN ON
 A2.1.8. PLEASE CORRELATE, GREY OUT ITEMS NOT ACTUALLY A
 PART OF THE 8TH LEVEL, OR PROVIDE AREA/ROOM DESIGNATION
 FOR CLARITY, FBC 107.
  
 9. A0.1.5, THE GRAPHICS FOR THE 2 HR RATED MECH SHAFTS
 LOCATED IN THE SOUTH CORRIDOR, STAIR 2, ELEVATOR 1, ALL
 OTHER 2 HOUR RATINGS HAVE BEEN REMOVED; PLEASE RESTORE
 SO DESIGN INTENT IS CLEAR, FBC 708.4, 1022.
  
 10. A2.1.1, IT APPEARS THAT PARKING SPACES WERE RE
 NUMBERED SO THE DEDICATED LEASING PARKING SPACES NO
 LONGER INCLUDE WHAT IS NOW ACCESSIBLE SPACE NUMBER 13
 (PREVIOUSLY SPACE NUMBER 11) AND THEREFORE DOES NOT
 COMPLY WITH FBC 2010 ACCESSIBILITY 208.2. PLEASE
 REVISE. COMPLIANCE WITH FAIR HOUSING AND ACCESSIBILITY
 SHOULD BE CLEAR ON THE PLANS.
  
 INDEX PAGE INDICATES THAT SHEET SD 1 INCLUDES PARKING
 DATA. I WAS UNABLE TO LOCATE SUMMARIZED PARKING ON THAT
 SHEET OR ON ANY OTHER SHEET, PLEASE REVISE.
  
 11. SHEET SP1 HAS A NOTE WHICH PREVIOUSLY STATED *481
 SPACES* AND NOW STATES *409 SPACES* BUT THIS NUMBER
 DOES NOT APPEAR TO BE CONSISTENT WITH THE TOTAL OF THE
 NUMBER OF PARKING SPACES FOR EACH FLOOR. CLARIFY TOTAL
 UNIT SPACES, TOTAL SPACES DEDICATED TO LEASING AREA,
 TOTAL ACCESSIBLE SPACES (SERVING THE LEASING AREA),
 TOTAL ACCESSIBLE SPACES SERVING UNIT RESIDENTS AND
 THEIR GUESTS. FBC 2010 ACCESSIBILITY/FAIR HOUSING.
  
 12. SEE FIRE COMMENTS REGARDING DAMPERS AND EXIT
 LIGHTING. THIS IS ALSO REQUIRED BY FBC 713 AND FBC
 1011.1.
  
 13. S0.4, STRUCTURAL STEEL NOTE APPEARS INCOMPLETE, SEE
 SS12.
  
 14. SHEET S 1.4 HAS NOT BEEN CORRECTLY NAMED; THIS
 SHOULD BE S1.4.4. SHEET S 1.4 HAS BEEN REMOVED FROM
 THIS PROJECT (SEE INDEX SHEET) AND THE NEW SHEET S1.4.4
 SHOULD BE NAMED PROPERLY IN ORDER TO REPLACE THE
 PREVIOUS VERSION.
  
 15. DUE TO FILE NAMING, SOME SHEETS ARE NOT IN ORDER.
 FOR INSTANCE, S1.3B APPEARS BEFORE S1.3A; SHEETS S1.4.4
 A THROUGH C DO NOT FOLLOW S1.4.4 (SO, THE STRUCTURAL
 DRAWINGS FOR THE 4TH FLOOR FOLLOW THE 6TH FLOOR).
 PLEASE COORDINATE WITH OUR PROJECTDOX COORDINATOR TO
 DETERMINE THE IMPACT ON RECORDS RETENTION AND ISSUANCE
 OF THE REVISION (IF ANY) OTHER THAN THE FACT THAT, IN
 THE FIELD (FOR COORDINATION, CONSTRUCTION, AND
 INSPECTIONS), PAGES WILL NOT BE IN THE ORDER ON THE
 INDEX SHEET, AND STRUCTURAL INFORMATION BY FLOOR MAY
 ALSO BE OUT OF ORDER. IT IS STRONGLY SUGGESTED THAT,
 SINCE THE PLANS INCLUDE OVER 200 SHEETS, FILES BE
 RENAMED SO THAT ALL SHEETS PRINT IN THE ORDER OF THE
 INDEX PAGE, FBC 107.
  
 16. SHEET S1.4.4B NOTE IN THE BOX NEAR THE BOTTOM RIGHT
 CORNER REFERS TO SHEET S1.4A WHICH, ACCORDING TO THE
 INDEX, NO LONGER EXISTS. PLEASE REVISE THIS AND ANY
 OTHER NOTES WHICH REFER TO THE SHEETS (S1.4, 1.4A,
 1.4B, 1.4C) WHICH HAVE BEEN ELIMINATED. OR, RESTORE
 SHEETS AND REVISE INDEX TO REFLECT, FBC 107.
  
 17. GARAGE FRAMING NOTES APPEAR INCOMPLETE. SEE SHEET
 S1.5A, *GARAGE FRAMING NOTES*, NOTES 4, 6 AND REVISE TO
 REFER TO CORRECT SHEETS. PLEASE CHECK ALL SIMILAR NOTES
 ON ALL SHEETS AS THIS APPEARS TO OCCUR ON OTHER SHEETS.
  
 18. SEE ITEM 1 REGARDING PROVISO ITEM CONCERNING
 PREVIOUS COMMENT LIST NUMBER 17. DETAIL 1 S1.7B DOES
 NOT APPEAR TO SHOW A PARAPET AT THE ELEVATOR ROOF, AND
 SHEET S1.7A (AND OTHER SHEETS, DETAILS) PARAPET LEGEND
 SHOWS A 2FT PARAPET AT STAIRS. THIS COMMENT WAS IN
 BUILDING PLAN REVIEWS 1 AND 2 AND PERMIT WAS ISSUED
 WITH PROVISO THAT THIS BE REVISED. IF ENGINEER
 DISAGREES WITH THIS COMMENT, PLEASE CONTACT ME. IF
 ENGINEER DOES NOT DISAGREE WITH THIS COMMENT, PLEASE
 EITHER REVISE ROOF PRESSURES ON SHEET S1.8 OR ADVISE AS
 TO WHEN THIS SHEET WILL BE REVISED.
  
 PERMIT WAS ISSUED WITH PROVISO THAT THIS SHEET BE
 REVISED (OR THIS ISSUE OTHERWISE RESOLVED) PRIOR TO
 ISSUANCE OF THE ROOFING PERMIT. A ROOF SUB PERMIT WAS
 APPLIED FOR ON NOV 25. A PRINT HOLD HAS BEEN PLACED ON
 THIS PERMIT SUBJECT TO RESOLUTION OF THIS COMMENT.
  
 19. S5.1, TYPICAL CONCRETE COLUMN, INCLUDES REFERENCE
 TO PILE CAP. PLEASE REMOVE, FBC 107, OR INDICATE WHERE
 PILES WILL BE INSTALLED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-10 Cont ID  
Sent By dhayes Date 2015-06-10 Time 16:40 Rev Time 0.00
Received By dhayes Date 2015-06-10 Time 14:18 Sent To  
Notes
2015-06-10 16:42:186/10/2015
 PROJECT: LOFTIN PLACE
 PERMIT#: 14030096
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW OF REVISION# 14100630
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SHEET E-1.1.1
 RELOCATE NOTE THAT WAS ADDED REGARDING THE SITE AND
 LANDSCAPE LIGHTING IN THE VICINITY OF THE POOL. THE
 NOTE WAS INADVERTENTLY PLACED ON TOP OF THE PLAN AND IS
 DIFFICULT TO SPOT AND READ. RELOCATE THE NOTE FOR
 CLARIFICATION TO AN OPEN SPACE ON THE SHEET WHERE IT
 WILL BE EASIER TO SPOT AND READ. WPB AMENDMENTS TO FBC
 107.
  
 2) E-4.1
 A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS
 LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE
 LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND
 ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS.
 B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST
 COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES
 CLOSET.
 C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW
 VOLTAGE PANELS. NEC 110.26(D)
 D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING
 OUTLET. NEC 210.70
 THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN
 BUT NO SWITCH CONTROLLED LIGHT OUTLET.
  
 3) E-4.2
 A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS
 LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE
 LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND
 ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS.
 B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST
 COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES
 CLOSET.
 C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW
 VOLTAGE PANELS. NEC 110.26(D)
 D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING
 OUTLET. NEC 210.70
 THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN
 BUT NO SWITCH CONTROLLED LIGHT OUTLET.
  
 4) E-6.1.1
 SWITCHBOARD ?4?, CIRCUIT 3 FEEDS PANEL L FROM A 350AMP
 OCPD AND INDICATES TO REFERENCE THE PANEL SCHEDULE FOR
 PANEL ?L? FOR THE FEEDER SIZE. PANEL L DOES NOT
 INDICATE THE FEEDER SIZE, NEITHER DOES THE RISER
 DIAGRAM. THE RISER DIAGRAM INDICATES TO REFERENCE NOTE
 17 FOR THE FEEDER SIZE. BUT NOTE 17 SAYS TO REFERENCE
 THE PANEL SCHEDULE. PROVIDE THE FEEDER SIZE FOR THE
 FEEDER FROM SWITCHBOARD ?4? TO PANEL L
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING,
 GENERATORS, FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-05 Cont ID  
Sent By dhayes Date 2015-03-05 Time 13:07 Rev Time 0.00
Received By dhayes Date 2015-03-02 Time 08:51 Sent To  
Notes
2015-03-05 13:07:213/3/2015
 PROJECT: LOFTIN PLACE REVISION
 PERMIT#: REVISION TRACKING# 14030096
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW OF REVISION 14100630
 ACTION: DENIED
  
 SHEET E-1.1.0
 ADD NOTES TO ADDRESS THE AUTOMATIC CONTROL OF INTERIOR
 AND EXTERIOR LIGHTING AS REQUIRED THROUGHOUT. FBC
 505.2.2
 THIS NOTE SHOULD ALSO BE ADDED TO THE PANEL SCHEDULES
 CONTROLLING LIGHTING IN THESE COMMON AREAS
  
 SHEET E-1.1.1
 1) MOVE THE NEW NOTE THAT WAS INCLUDED TO ADDRESS THE
 PREVIOUS REVIEW COMMENT REGARDING LIGHTING IN THE
 VICINITY OF A SWIMMING POOL. NEC ARTICLE 680.8-10. THIS
 NOTE WAS PLACED ON TOP OF THE PLAN RATHER THAN BEING
 PLACED IN AN OPEN SPACE FOR CLARITY.
  
 SHEET E-2.1.1
 2) MOVE THE NOTE ?ALL CORRIDOR RECEPTACLES SHALL BE
 GFCI AND TAMPER RESISTANT? THIS NOTE WAS PLACED ON TOP
 OF THE PLAN RATHER THAN BEING PLACED IN AN OPEN SPACE
 FOR CLARITY. THE SYMBOL SHOULD BE CHANGED IN ALL
 CORRIDORS TO INDICATE THIS PARTICULAR OUTLET TYPE ON
 THE FLOOR PLAN.
  
 SHEET E-4.1 AND E-4.2
 3) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING
 OUTLET. NEC 210.70
 THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN
 BUT NO SWITCH CONTROLLED LIGHT OUTLET. THE GREAT ROOM
 INDICATES A SWITCH CONTROLLED RECEPTACLE BUT THE SYMBOL
 FOR THE OUTLET IS NOT DESIGNATED AS A SWITCH CONTROLLED
 RECEPTACLE.
  
 4) THE OUTLETS REQUIRED BY 210.52 (SPACING) DO NOT
 INCLUDE THE OUTLETS INDICATED FOR WALL MOUNTED TV?S
 WHERE THE RECEPTACLE OUTLET WILL BE INSTALLED ABOVE OR
 WHERE THEY ARE CONTROLLED BY A SWITCH SUCH AS IN THE
 GREAT ROOM. 210.52 ADDITIONAL RECEPTACLE OUTLET ARE
 REQUIRED TO MEET THIS CRITERIA.
  
 5) ADDITIONAL OUTLETS ARE REQUIRED AT THE KITCHEN
 COUNTERTOP BETWEEN THE STOVE AND THE SINK. 210.52
  
 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 PLANS AND ENGINEERING ARE REQUIRED FOR SITE LIGHTING,
 GENERATORS. HOOD EXHAUST, FIRE ALARM, ACCESS CONTROL
 SYSTEM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA,
 AND, COMMUNICATION.
  
 SHEET E-4.3
 7) ADDITIONAL EMERGENCY LIGHTING IS REQUIRED FOR THE
 COMMON AREA CORRIDORS, STAIRS, AND LOBBY AREAS. NEC
 700.16, 700.12
  
 SHEET E-6.11
 8) PARKING LOT LIGHTS ARE ALSO REQUIRED TO BE
 CONTROLLED SO AS NOT TO BE IN OPERATION WHEN NOT
 REQUIRED OR DURING DAYTIME HOURS. THE REQUIREMENTS OF
 FBC-ENERGY SECTION 505.2 WILL ALSO APPLY TO THESE
 CIRCUITS.
  
 SHEET E-6.1.2
 9) A SIMPLE TIME CLOCK IS NOT SUFFICIENT FOR CONTROL OF
 THE EXTERIOR LIGHTING TO COMPLY WITH THE FBC-ENERGY
 SECTION 505.2. STATES: ?LIGHTING FOR ALL EXTERIOR
 APPLICATIONS NOT EXEMPTED IN SECTION 505.1 SHALL HAVE
 AUTOMATIC CONTROLS CAPABLE OF TURNING OFF EXTERIOR
 LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN
 THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME HOURS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH.?
  
 SHEET E-9.1.1
 10) REVISE THE LIGHTING FIXTURE SCHEDULE TO INCLUDE THE
 FIXTURES STAIRWAY LIGHTING THAT ARE REQUIRED TO HAVE
 BATTERY BACKUP. NONE OF THE SYMBOLS IN THE LEGEND
 INCLUDE THE FIXTURE SYMBOL THAT HAS BEEN ADDED IN THE
 STAIRWAYS THAT REQUIRE BATTERY BACKUP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-12 Cont ID  
Sent By dhayes Date 2014-12-12 Time 09:20 Rev Time 0.00
Received By dhayes Date 2014-12-12 Time 09:20 Sent To  
Notes
2014-12-12 09:33:0512/11/2014
 PROJECT: LOFTIN PLACE REVISION
 PERMIT#: 14030096
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW OF REVISION 14100630
 ACTION: DENIED
  
 SHEET E-1.1.1
 1) VERIFY THE LOCATION, AND ELEVATION OF POWER AND
 LIGHTING INCLUDING THEIR ASSOCIATED CONDUITS AND WIRING
 IN THE VICINITY OF THE SWIMMING POOL. NEC680.8.680.10,
 680.22, 680.24
  
 SHEET E-2.1.2
 1) EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT
 OF SAME LOCAL AREA. NEC 700.12 (F) (4)
  
 E.2.1.7
 2) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED
 IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE
 OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT
 DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT
 REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. FBC
 505.2.4 EXTERIOR LIGHTING CONTROLS.
  
 3) PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES
 INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609
  
 SHEET E-4.1
 4) STUDIO ONE UNIT REQUIRES AN OUTLET AT THE KITCHEN
 ISLAND. NEC 210.52
  
 SHEET 4.1A
 5) PANEL A1 INDICATES CIRCUIT #1,3 FOR THE A/C IS A
 2POLE 35 WITH #12. REVISE THE PANEL SCHEDULE TO
 INDICATE A CIRCUIT CONDUCTOR ADAQUATE FOR THE 35AMP
 OCPD. NEC 310.16
  
 E-4.3
 6) THE CORRIDORS AND COMMON AREAS REQUIRE EMERGENCY
 LIGHTING. LIGHTING SYSTEMS SHALL BE DESIGNED AND
 INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL
 LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP,
 CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES
 EMERGENCY ILLUMINATION. NEC 700.16
  
 7) IDENTIFY ALL LIGHTING CIRCUITS ON THE FLOOR PLAN.
 FBC 107.3.2
  
 8) EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT
 OF SAME LOCAL AREA. NEC 700.12 (F) (4)
  
 E-4.4
 9) PROVIDE EMERGENCY LIGHTING FOR STAIRWELLS. EMERGENCY
 LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO
 THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT,
 SUCH AS THE BURNING OUT OF A LAMP, CANNOT LEAVE IN
 TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY
 ILLUMINATION. NEC 700.16
  
 E-5.1.1
 10) CLARIFY THE CIRCUIT FEEDING THE FIRE PUMP. THE
 RISER ON 7.1.1 INDICATES THE FIRE PUMP SERVICE FROM THE
 UTILITY TO THE FIRE PUMP CONTROLLER AND THE FLOOR PLAN
 ON SHEET 5.1.1 INDICATES THE FIRE PUMP BEING FED FROM
 SWITCHBOARD 4 CIRCUIT #10 AND THE PANEL SCHEDULE FOR
 SWITCH BOARD 4 CIRCUIT #10 INDICATES A SPACE. REVISE
 THE FLOOR PLAN ON SHEET 5.1.1 TO INDICATE THE ACTUAL
 FEEDER.
  
 E-6.1.1
 11) REVISE PANEL SCHEDULES AND LOAD CALCULATIONS IN
 SWITCH BOARD 2 AND 3. THE TOTAL CALCULATED LOADS
 REPRESENTED IN THE CHART LABELED TOTAL UNIT CONNECTED
 LOAD STATES THE TOTAL CONNECTED LOAD IN VA PER METER
 CENTER. THE PANEL SCHEDULE FOR SWITCH BOARD ?3?
 INDICATES THE LOADS TO BE SLIGHTLY DIFFERENT THAN WHAT
 IS REPRESENTED IN THE CHART ON E7.1.1 PARTICULARLY THE
 LOAD FOR METER CENTER 8. THE PANEL SCHEDULE ON E6.1.1
 INDICATES MC 8 WITH A TCL OF 847.7KVA BUT THE LOAD
 INDICATED IN THE CHART ON E7.1.1 IS INDICATED TO BE
 1,078,144VA OR 1,078KVA. REVISE LOADS IN PANEL
 SCHEDULES AND LOAD CALCULATIONS TO BE ACCURATE AND TO
 MATCH FROM PAGE TO PAGE
  
 E-7.1.1. AND E-7.1.2
 12) NEC240.4(C) WHERE THE OVERCURRENT DEVICE IS RATED
 OVER 800 AMPERES, THE AMPACITY OF THE CONDUCTORS IT
 PROTECTS SHALL BE EQUAL TO OR GREATER THAN THE RATING
 OF THE OVERCURRENT DEVICE DEFINED IN NEC 240.6. 3 SETS
 OF 500MCM CU IS NOT ADEQUATE FOR A 1200AMP OCPD
 13) VERIFY SAME FOR ALL SERVICE ENTRANCE AND FEEDERS
  
 14) NEC240.4(C) DEVICES RATED OVER 800 AMPERES. WHERE
 THE OVERCURRENT DEVICE IS RATED OVER 800 AMPERES, THE
 AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE EQUAL
 TO OR GREATER THAN THE RATING OF THE OVERCURRENT DEVICE
 DEFINED IN NEC 240.6
 3 SETS OF 500MCM CU IS NOT ADEQUATE FOR A 1200AMP OCPD
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-12-16 Cont ID  
Sent By Mgonzale Date 2014-12-16 Time   Rev Time 1.00
Received By mgonzale Date 2014-12-16 Time   Sent To I
Notes
2014-12-16 11:58:05SHEET C7 REVISIONS ARE ACCEPTABLE.
  
 FDC LOCATION IS ADEQUATE AS REQUESTED PER FIRE REVIEW.
  
 EOR WILL PROVIDE AS-BUILT LOCATION OF SUCH ELEMENT TO
 CITY OF WPB PUBLIC WORKS DEPARTMENT UPON REQUESTING
 TCO/CO.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-04-29 Cont ID  
Sent By wjolin Date 2015-04-29 Time 12:48 Rev Time 0.00
Received By wjolin Date 2015-04-29 Time 09:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-02-26 Cont ID  
Sent By wjolin Date 2015-02-26 Time 13:05 Rev Time 0.00
Received By wjolin Date 2015-02-24 Time 16:23 Sent To  
Notes
2015-02-24 16:23:59705 NORTH OLIVE AVEUE
 TRACKING #14100630
 PERMIT #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SHEET A-0.1.2: THE FIRE RATED NORTH
 CORRIDOR NO LONGER PROVIDES DIRECT ACCESS INTO THE EXIT
 STAIR ENCLOSURE (STAIR #5) PER FFPC SECTION 7.5.1.1.1.
 THE FIRE RATING SEPARATING THE PARKING GARAGE (STORAGE)
 FROM RESIDENTIAL HAS BEEN RELOCATED REQUIRING APARTMENT
 OCCUPANTS TO ENTER THE STORAGE OCCUPANCY TO REACH THE
 PROTECTED EXIT. PER FFPC SECTION 7.5.1.6 EXIT ACCESS
 SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO PASS
 THROUGH ANY AREA IDENTIFIED UNDER PROTECTION OF HAZARDS
 (STORAGE: SEETABLE 30.3.2.1.1). TYPICAL ALL LEVELS.
  
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-19 Cont ID  
Sent By wjolin Date 2014-11-19 Time 17:36 Rev Time 0.00
Received By wjolin Date 2014-11-18 Time 11:12 Sent To  
Notes
2014-11-18 17:13:28705 NORTH OLIVE AVEUE
 TRACKING #14100630
 PERMIT #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-0.1.2: THE FIRE RATED NORTH CORRIDOR NO LONGER
 PROVIDES DIRECT ACCESS INTO THE EXIT STAIR ENCLOSURE
 (STAIR #5) PER FFPC SECTION 7.5.1.1.1. THE FIRE RATING
 SEPARATING THE PARKING GARAGE (STORAGE) FROM
 RESIDENTIAL HAS BEEN RELOCATED REQUIRING APARTMENT
 OCCUPANTS TO ENTER THE STORAGE OCCUPANCY TO REACH THE
 PROTECTED EXIT. PER FFPC SECTION 7.5.1.6 EXIT ACCESS
 SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO PASS
 THROUGH ANY AREA IDENTIFIED UNDER PROTECTION OF HAZARDS
 (STORAGE: SEETABLE 30.3.2.1.1). TYPICAL ALL LEVELS.
  
 SHEET A-0.1.4: THE WEST EXIT ACCESS DOOR LEADING FROM
 THE ASSEMBLY ROOF AREA INTO THE EXIT ACCESS CORRIDOR
 HAS A DOOR SWING THAT IS AGAINST THE FLOW OF TRAFFIC.
  
 SHEET M-4.4: SEVERAL SECTIONS OF DUCTWORK ARE
 PENETRATING FIRE RATED WALLS WITH NO DAMPERS SHOWN.
 REFER TO SHEET A--0.1.2 FOR FIRE RATED WALL LOCATIONS.
  
 SHEET E-4.3: SEVERLY DEFICIENT EXIT SIGNAGE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-11 Cont ID  
Sent By cpuell Date 2015-06-11 Time 08:08 Rev Time 0.00
Received By cpuell Date 2015-03-27 Time 14:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-05 Cont ID  
Sent By cpuell Date 2015-03-05 Time 13:22 Rev Time 0.00
Received By cpuell Date 2015-01-29 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-27 Cont ID  
Sent By skennedy Date 2014-12-27 Time 10:13 Rev Time 0.00
Received By cpuell Date 2015-01-29 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-03-02 Cont ID  
Sent By hmoser Date 2015-03-02 Time 11:23 Rev Time 0.00
Received By hmoser Date 2015-03-02 Time 09:22 Sent To  
Notes
2015-03-02 11:23:49PASS
 1) REFER TO SECTION 607.5.5 SHAFT ENCLOSURE MOTORIZED
 DAMPERS REQUIRED
 2010 FBC (M)
 2) RTU TIE DOWN DETAIL IS NOT RECOMMENDED BECAUSE OF
 MAINTENANCE ISSUES
 3) REFER TO SECTION 602.2.1 INCLUDING A/C CLOSET DOORS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-27 Cont ID  
Sent By hmoser Date 2014-12-27 Time 07:42 Rev Time 0.00
Received By hmoser Date 2014-11-05 Time 14:26 Sent To  
Notes
2014-12-27 07:47:53PASS PROVISO
 REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 INCLUDING DOORS 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 06:38 Rev Time 0.00
Received By tklarge Date 2015-02-07 Time 04:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By tklarge Date 2014-11-07 Time 07:36 Rev Time 0.00
Received By tklarge Date 2014-11-07 Time 04:59 Sent To  
Notes
2014-11-07 07:36:08 
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) DWG. P-5.1 - THE WATER RISER FOR UNIT # B1 APPEARS
 TO HAVE THE PIPE SIZES REVERSED AND THE HOT AND COLD
 WATER LINES ARE REVERSED AT SOME OF THE FIXTURES. MOST
 OF THE FIXTURES ARE BEING FED FROM A 1/2 " COLD WATER
 LINE.
 2) DWG. P-5.4C - RISER #117 - THE VENT STACK IS SHOWN
 AS 3" AND ON SHT. P-5.3 IT IS SHOWN AS 4". CLARIFY.
 3) SHT.P-5.4C - RISER #113 IS LABELED AS RISER #13 -
 CORRECT
 4) DWG.P-5.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 FIXTURE UNIT LOAD FOR THE WATER PIPING.
 5) WG. P-5.5 - STORM COLLECTION RISER #1 - A 3" ROOF
 DRAIN WITH A COLLECTION AREA OF 1520 SQ. FT.IS
 DISCHARGING INTO A HORIZONTAL LINE THAT IS 4 " IN
 DIAMETER. THE MAXIMUM SQUARE FOOTAGE PERMITTED ON A 4"
 LINE AT MIN. 1/8" SLOPE IS 1504 SQ. FT. THIS LINE HAS
 TO BE INCREASED TO 5 " OR THE SLOPE OF THE PIPE SHALL
 BE INCREASED TO 1/4 " SLOPE PER FT.
 6) PROVIDE A LEGEND FOR THE HOT AND COLD WATER LINES (
 THE WATER RISERS SHOW THE LINES IDENTIFIED WITH ONE AND
 TWO DASHES. JUST IDENTIFY WHICH ONE IS FOR HOT AND
 WHICH ONE IS FOR COLD).
 7) SHT. P-5.3 - THE BOTTOM HALF OF THE PAGE - THE
 GROUPS OF RISER NUMBERS ARE SPACED SO CLOSE TO EACH
 OTHER THAT IT IS DIFFICULT TO FIGURE OUT WHICH RISER
 NUMBERS APPLY TO THE SPECIFIC RISERS.
 8) DWG. P-5.3 - SHOWS RISER # 117 FOR TWO DIFFERENT
 RISERS - CLARIFY.
 9) DWG.P-6.2 - A WATER HAMMER ARRESTOR SHALL BE
 INSTALLED ON THE TRASH CHUTE WASHDOWN PER 2010 FPC
 SEC.604.9.
 10) DWG. P-6.2 - THE EJECTOR SHALL BE PROVIDED WITH A
 FULL FLOW VALVE ( SHUTOFF VALVE) AND CHECK VALVE
 LOCATED IN THE DISCHARGE PIPING BETWEEN THE PUMP OR
 EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. 2010 FPC
 SEC.712.2.
 11) IF THE ELEVATOR IS A HYDRAULIC ELEVATOR THE
 EFFLUENT FROM THE SUMP PIT SHALL DISCHARGE INTO AN OIL
 SEPARATOR. INDICATE ON THE DRAWING IF THE ELEVATOR IS
 CBLE DRIVEN OR HYDRAULIC.
 12) DWG. P-6.2 - INDICATE ON THE PLAN WHETHER THE FLOOR
 DRAIN RECEIVING THE WASTE FROM THE ELEVATOR PIT IS
 DISCHARGING TO THE STORM OR SANITARY.
 13) DWG. P-5.4B - INDICATE THE SLOPE OF THE 8" SANITARY
 LINE ON THE DRAWING. COMPLY W/2010 FPC TABLE 710.1 (1)
 FOR THE SLOPE OF PIPE AND THE MAXIMUM NUMBER OF FIXTURE
 UNITS THAT THE PIPE CAN CARRY.
 14) ANY WASHING MACHINE BOXES LOCATED IN FIRE RATED
 WALLS SHALL EITHER BE FIRE RATED OR INSTALLED TO
 MAINTAIN THE FIRE RATING OF THE WALL. 2010 FBC SEC.713.
 15) DWG. P-6.2 - THE P & T LINES AND PAN DRAINS SHALL
 NOT USE THE SAME RISER PER THE 2010 FPC SEC.504.6 (4).
 16) DWG.P-6.2 - THE PAN DRAIN SHALL BE DRAINED BY AN
 INDIRECT WASTE PIPE PER THE 2010 FPC SEC. 504.7.1.
 17) DWG. P-5.6A - SHOWS THE RELIEF LINES AS A DIRECT
 CONNECTION TO THE RISER AND THE WATER HEATER DETAIL ON
 DWG. P-6.2 SHOWS RELIEF LINES DISCHARGING TO AN AIR GAP
 FITTING . CLARIFY.
 18) COMBUSTIBLE MATERIALS ARE NOT PERMITTED IN RETURN
 AIR PLENUMS PER THE 2010 FPC SEC.307.6 FL. MECH CODE.
 SEC.602.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-06-26 Cont ID  
Sent By skennedy Date 2015-06-26 Time 11:02 Rev Time 0.00
Received By skennedy Date 2015-06-23 Time 12:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-18 Cont ID  
Sent By aaponte Date 2014-12-18 Time 14:27 Rev Time 0.00
Received By aaponte Date 2014-12-18 Time 14:26 Sent To  
Notes
2014-12-18 14:30:49PROVISO: THE FOLLOWING ITEMS SHALL BE CORRECTED:
 1. BALCONIES AND EYEBROWS REMOVED OR REDUCED IN SIZE
 SHALL BE RESTORED TO THE ORIGINAL DIMENSION APPROVED AS
 PART OF THE DAC SPECIAL REVIEW. THE REMOVAL OF THE
 BALCONIES ALTERS THE FACADE APPROVED BY THE BOARD IN A
 SUBSTANTIAL MANNER.
 2. AWNINGS ORIGINALLY INDICATED AND APPROVED AS PART OF
 THE DAC SPECIAL REVIEW SHALL BE MAINTAINED. A SEPARATE
 PERMIT FOR AWNINGS SHALL BE SUBMITTED.
 3. CONFIRM PARKING AREAS ARE NOT EXPOSED TO THE SKY.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.