Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-17 Cont ID  
Sent By pleduc Date 2014-11-17 Time   Rev Time 0.00
Received By pleduc Date 2014-11-17 Time 13:10 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-22 Cont ID  
Sent By pleduc Date 2014-10-22 Time   Rev Time 0.00
Received By pleduc Date 2014-10-22 Time 14:12 Sent To M
Notes
2014-10-22 16:25:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FIRE SPRINKLER RISER AND FDC IS COMMON EQUIPMENT TO
 THE ENTIRE BUILDING AND SHALL NOT BE BLOCKED FROM
 ACCESS.
  
 THE FACP LOCATED ON THE EXTERIOR WALL SHALL ALSO NOT BE
 BLOCKED FROM ACCESS.
  
 THE PROPOSED FENCING SHALL BE MOVED AWAY FROM THE WALL,
 AS HAND DRAWN ON ONE OF THE SUBMITTED PLAN SHEETS, OR
 THE ENTIRE RISER AND FDC BE MOVED TO A COMMON AREA WITH
 UNLIMITED ACCESS.
  
 THE LOCATION OF THE FACP, NOT SHOWN ON THE PALN, SHALL
 NOT BE ENCLOSED BY FENCING AND SHALL ALSO HAVE
 UNLIMITED ACCESS.
  
 CLOSE COORDINATION WITH THE FIRE PREVENTION BUREAU IS
 STRONGLY ENCOURAGED TO ENSURE THAT ACCESS IS
 MAINTAINED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-20 Cont ID  
Sent By hmoser Date 2014-11-20 Time 13:37 Rev Time 0.00
Received By hmoser Date 2014-11-14 Time 08:07 Sent To  
Notes
2014-11-15 08:08:11ROUTED TO FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-28 Cont ID  
Sent By hmoser Date 2014-10-28 Time 13:35 Rev Time 0.00
Received By hmoser Date 2014-10-20 Time 09:36 Sent To  
Notes
2014-10-20 09:49:54ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-11-20 Cont ID  
Sent By hmoser Date 2014-11-20 Time 13:36 Rev Time 0.00
Received By hmoser Date 2014-11-20 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-28 Cont ID  
Sent By hmoser Date 2014-10-28 Time 13:35 Rev Time 0.00
Received By hmoser Date 2014-10-28 Time 13:30 Sent To  
Notes
2014-10-28 13:35:16PLAN DENIED
 REFER TO FIRE NOTES ON ACCESS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676