Plan Review Details - Permit 14100545
Plan Review Stops For Permit 14100545
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-12-14 Time 18:23 Rev Time 0.00
Received By jgomez Date 2015-12-14 Time 18:23 Sent To E
Notes
2015-12-14 18:25:14BUILDING PROVISO:
  
 1- REVISE DESIGN CRITERIA. THIS IS R3 NOT R2.
 2- REVISE ENERGY CALCULATIONS: (1) WALLS & WINDOWS
 INFO. TO MATCH PLANS. (2) REVISE ORIENTATION OF
 INSULATED DOOR. (3) REVISE # OF BEDROOMS. (4) PROVIDE
 WATER HEATER INFO (5) SPECIFY BUILDER'S NAME. (6)
 COOLING/HEATING INFO. TO MATCH EQUIPMENT.
 3- A/C PLANS TO SHOW HEATING EQUIPMENT FOR BEDROOM.
 4- BEDROOM EGRESS WINDOW: VERIFY IN FIELD ALL EGRESS
 CLEAR DIMENSIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-10-29 Time 09:29 Rev Time 0.00
Received By jgomez Date 2015-10-29 Time 09:29 Sent To  
Notes
2015-10-29 09:45:1210/29/15 TALKED TO PETER (9:09AM). HE AGREED TO PASS
 BUILDING AND MECHANICAL REVIEW WITH PROVISO. REVISION
 FEES APPLY.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE DESIGN CRITERIA. THIS IS R3 NOT R2.
 2- REVISE ENERGY CALCULATIONS: (1) WALLS & WINDOWS
 INFO. TO MATCH PLANS. (2) REVISE ORIENTATION OF
 INSULATED DOOR. (3) REVISE # OF BEDROOMS. (4) PROVIDE
 WATER HEATER INFO (5) SPECIFY BUILDER'S NAME. (6)
 COOLING/HEATING INFO. TO MATCH EQUIPMENT.
 3- A/C PLANS TO SHOW HEATING EQUIPMENT FOR BEDROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2015-10-29 Cont ID  
Sent By jgomez Date 2015-10-28 Time 17:12 Rev Time 0.00
Received By jgomez Date 2015-10-28 Time 17:12 Sent To  
Notes
2015-10-28 17:28:011- DESIGN CRITERIA WAS REVISED THE OCCUPANCY SPECIFIED
 ON THE DESIGN CRITERIA IS INCORRECT. THIS IS NOT R2
 OCCUPANCY. THIS IS ONE AND TWO FAMILY RESIDENCE R3
 OCCUPANCY. SEE CHAPTER 3 OF THE 2010 FBC-BUILDING AND
 REVISE AS REQUIRED.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT).:
 A) WALLS AND WINDOWS INFORMATION DON'T MATCH PLANS.
  
 B) THERE ARE NO INSULATED DOORS ON ON THE EAST WALL.
  
 C) ENERGY CALCULATIONS SUBMITTED NOW SHOW 2 BEDROOMS.
 WHERE IS THE OTHER BEDROOM?.
  
 D) NEED OWNER/AGENT CERTIFICATION AT THE BOTTOM OF THE
 FORM.
  
 E) WHY THERE IS NOT INFORMATION FOR THE WATER HEATER.
  
 F) SPECIFY THE BUILDER'S NAME.
  
 G) COOLING AND HEATING INFORMATION DON'T MATCH A/C AHRI
 CERTIFICATED SUBMITTED.
  
 NOTE: LABELS FOR WINDOWS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION WHEN NOT USING THE PROGRAM DEFAULT.
  
 3- NEW COMMENT:
 MECHANICAL PLAN WAS REVISED AGAIN. THERE IS NO HEATING
 EQUIPMENT FOR THE BEDROOM. NEED TO COMPLY WITH THE
 HEATING REQUIREMENTS OF SEC. R303.8 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-10-07 Cont ID  
Sent By jgomez Date 2015-10-07 Time 15:55 Rev Time 0.00
Received By jgomez Date 2015-10-07 Time 15:55 Sent To  
Notes
2015-10-07 15:56:27RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- THE NEW PLANS SUBMITTED ARE REFERENCING THE 2014
 FBC. THE ORIGINAL PERMIT APPLICATION AND ALL REVIEWS
 WERE DONE BASED ON THE 2010 FBC. REVISE ALL PLANS AND
 NOTES AS REQUIRED. (REPEAT COMMENT).
  
 RESPONSE:
 PLANS WERE NO REVISED. STILL REFERENCING THE 2014 CODE
 AND NOW IS MISMATCHING CODES. DESIGN CRITERIA CALLS FOR
 THE 2010 FLORIDA MECHANICAL CODE AND THE REST OF THE
 CITED CODES ARE REFERRING TO THE 2014 CODE. ALSO, THE
 CLASSIFICATION OF WORK IS INCORRECT. THIS IS NOT
 ALTERATION LEVEL 2. THIS IS ALTERATION LEVEL 3 AND IT'S
 ALSO A CHANGE OF OCCUPANCY FROM GARAGE TO
 GARAGE/APARTMENT. REVISE AS REQUIRED. SEC. 405 AND SEC.
 406 OF 2010 FBC-EXISTING BUILDING.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) COORDINATE WITH PLANS INSULATION FOR ALL WALLS
 (INCLUDING THE ADJACENT WALL SEPARATING THE GARAGE FROM
 THE A/C AREA.) SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT).
  
 RESPONSE:
 WHERE IS THE EXTERIOR WOOD FRAMED WALL SHOWN ON ITEM
 #9(B)?. THERE ARE NOT EXTERIOR FRAMED WALLS ON PLANS.
 SEE PLANS AND REVISE AS REQUIRED. IS THIS THE ADJACENT
 WALL BETWEEN GARAGE AND NEW APARTMENT?. IF SO, THE
 CORRECT WALL DENOMINATION IS ADJACENT WALL NOT EXTERIOR
 WALL.
  
 B) WALLS AND WINDOWS SHOWN PAGE 3 OF 5 DON'T MATCH
 PLANS. REVISE WALLS AND WINDOWS INFORMATION, INCLUDING
 ORIENTATION TO MATCH PLANS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. (REPEAT COMMENT).
  
 RESPONSE:
 THERE IS NO COORDINATION WITH PLANS. INFORMATION SHOWN
 ON THE ENERGY CALCULATIONS DOESN'T MATCH PLANS. REVISE
 AS REQUIRED TO MATCH.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE R VALUE SHOWN ON THE ENERGY
 CALCULATIONS ON ITEM #11 FOR THE DUCTS. SEC. 103.2..2
 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT).
  
 RESPONSE:
 THERE IS NO COORDINATION WITH PLANS. INFORMATION SHOWN
 ON THE ENERGY CALCULATIONS DOESN'T MATCH PLANS.
 MECHANICAL PLAN WAS REVISED AND INFORMATION SHOWN ON
 ITEM #11(A) OF THE ENERGY CALCULATIONS DON'T MATCH.
 REVISE AS REQUIRED.
  
 4- NEW COMMENT:
 MECHANICAL PLAN WAS REVISED. NEW A/C EQUIPMENT DOESN'T
 PROVIDE HEATING. NEED TO COMPLY WITH THE HEATING
 REQUIREMENTS OF SEC. R303.8 OF 2010 FBC-RESIDENTIAL.
 PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE.
  
 5- PLANS DON'T SHOW THE R-VALUE FOR THE EXTERIOR WALLS.
 103.2..2 OF 2010 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 ITEM #9(A) OF THE ENERGY CALCULATIONS SUBMITTED CALLS
 FOR CONCRETE BLOCK WALL INSULATION OF R-6.2. THE R
 VALUE OF THE INSULATION ALONE NEEDS TO BE R-6.2 AS
 REQUIRED BY SEC. R304.1.2 OF 2010 FBC-ENERGY
 CONSERVATION. OTHER BUILDING MATERIALS CAN NOT BE
 INCLUDED TO OBTAIN THE REQUIRED R VALUE. REVISE THE
 "DROP CEILING SIDE VIEW SECTION" AS REQUIRED. AND,
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 R-6.2 INSULATION.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL14604-R3 SUBMITTED IS NOT APPROVED. THE APPLICATION
 STATUS SAYS "RE-APPLY". NEED COPY OF APPROVED PRODUCT
 APPROVAL.
  
 RESPONSE:
 ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE WAS
 SUBMITTED THIS TIME. NEED TO SUBMIT THE COMPLETE
 PRODUCT APPROVAL WITH THE DRAWINGS THAT WERE APPROVED.
  
 7- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 8- DROP CEILING PLAN:
 A) PROVIDE DETAIL SHOWING HOW IS THE DOUBLE 2X8
 ATTACHED TO THE MASONRY WALL AND TO THE WOOD FRAMED
 WALL? . DROP CEILING SIDE VIEW DRAWING IS NOT CLEAR?
 NOTE: FASTENERS FOR THE MASONRY WALL ARE NOT THE SAME
 AS FOR A WOOD FRAMED WALL. HOW IS THE LUS28-2 ATTACHED
 TO THE 2X4 TOP PLATE?. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 DRAWINGS SUBMITTED ARE NOT CLEAR. DROP CEILING PLAN
 DOESN'T SHOW ANY STUDS SUPPORTING THE (2)2X8 BEAM AND
 THERE IS NO WAY TO PLACE A LUS28-2 SIMPSON CONNECTOR TO
 DOUBLE 2X4 JACK STUD BELOW WOOD BEAM AS SPECIFIED ON
 THE DROP CEILING SIDE VIEW. THE WIDTH OF THE CONNECTOR
 IS WIDER THAN THE DOUBLE STUDS. THERE IS NO WAY TO NAIL
 THE CONNECTOR TO THE STUDS. REVISE AS REQUIRED.
  
 ***ENGINEER OF RECORD LETTER ADDRESSING EACH COMMENT
 WILL HELP TO EXPEDITE THE REVIEW PROCESS.
  
 NOTE: ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE
 PLAN REVIEW FEES FOR MULTIPLE REJECTIONS. SEE COPY OF
 FLORIDA STATUTE SEC. 553.80(2)(B) BELOW"
  
 "WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-09-01 Cont ID  
Sent By jgomez Date 2015-09-01 Time 10:18 Rev Time 0.00
Received By jgomez Date 2015-09-01 Time 10:17 Sent To  
Notes
2015-09-01 10:22:52RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ***NOTE: THERE IS A NEW SET OF PLANS DONE BY ANOTHER
 DESIGN PROFESSIONAL. THEREFORE A COMPLETE NEW REVIEW IS
 REQUIRED.
  
 1- THE NEW PLANS SUBMITTED ARE REFERENCING THE 2014
 FBC. THE ORIGINAL PERMIT APPLICATION AND ALL REVIEWS
 WERE DONE BASED ON THE 2010 FBC. REVISE ALL PLANS AND
 NOTES AS REQUIRED.
  
 2- SPECIFY WINDOWS AND DOORS DESIGN PRESSURES. SEC.
 R301
  
 3- IMPACT FEES: NEED NEW SET OF PLANS RE-STAMPED BY
 PALM BEACH COUNTY AND NEED COPY OF PAID RECEIPT. COPY
 OF PAID RECEIPT WAS NEVER SUBMITTED. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 NOTE: ENERGY CALCULATIONS AND PLANS NEED TO BE
 COORDINATED TO AVOID CONFLICTS AND UNNECESSARY DELAYS.
  
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 REPORT AS REQUIRED BY SEC. 405.4.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM: OWNER'S
 NAME, BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) COORDINATE WITH PLANS INSULATION FOR ALL WALLS
 (INCLUDING THE ADJACENT WALL SEPARATING THE GARAGE FROM
 THE A/C AREA.) SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 E) WALLS AND WINDOWS SHOWN PAGE 3 OF 5 DON'T MATCH
 PLANS. REVISE WALLS AND WINDOWS INFORMATION, INCLUDING
 ORIENTATION TO MATCH PLANS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE DOCUMENTATION SHOWING THE WINDOWS AND DOORS
 U-FACTOR AND SHGC FACTOR SHOWN ON ITEM #7 AS REQUIRED
 BY SEC. 405.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 6- R-30 INSULATION DOESN'T FIT ON A 2 X 6 AS SHOWN ON
 THE DROP CEILING PLAN. ENGINEER TO REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE R VALUE SHOWN ON THE ENERGY
 CALCULATIONS ON ITEM #11 FOR THE DUCTS. SEC. 103.2..2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 8- PLANS DON'T SHOW THE R-VALUE FOR THE EXTERIOR WALLS.
 103.2..2 OF 2010 FBC-ENERGY CONSERVATION.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL14604-R3 SUBMITTED IS NOT APPROVED. THE APPLICATION
 STATUS SAYS "RE-APPLY". NEED COPY OF APPROVED PRODUCT
 APPROVAL.
  
 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 11- DROP CEILING PLAN:
 A) PROVIDE DETAIL SHOWING HOW IS THE DOUBLE 2X8
 ATTACHED TO THE MASONRY WALL AND TO THE WOOD FRAMED
 WALL? . DROP CEILING SIDE VIEW DRAWING IS NOT CLEAR?
 NOTE: FASTENERS FOR THE MASONRY WALL ARE NOT THE SAME
 AS FOR A WOOD FRAMED WALL. HOW IS THE LUS28-2 ATTACHED
 TO THE 2X4 TOP PLATE?. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) 2 X 6 LEDGER: SPECIFY SPACING OF THE FASTENERS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 14:41 Rev Time 0.00
Received By jgomez Date 2015-03-19 Time 14:39 Sent To  
Notes
2015-03-19 14:43:25RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 IMPORTANT:
 THERE ARE SEVERAL ISSUES THAT NEED TO BE ADDRESSED.
 THERE WAS BUILDING, MECHANICAL, PLUMBING AND ELECTRICAL
 WORK DONE WITHOUT PERMITS. PERMIT APPLICATIONS WERE
 APPLIED FOR, BUT PERMITS WERE NOT ISSUED. ONE
 MECHANICAL PERMIT WAS ISSUED AND THE OTHER WAS NOT
 (BOTH ARE EXPIRED NOW). THE BEST WAY TO CLEAR UP ALL
 THE ISSUES IS TO PROVIDE COMPLETE PLANS AND
 SPECIFICATIONS FOR BOTH BUILDINGS, MAIN BUILDING AND
 REAR STRUCTURE. SHOW ALL WORK: DONE AND PROPOSED.
 PROVIDE PERMIT APPLICATION FOR THE MAIN HOUSE AND
 ANOTHER PERMIT APPLICATION FOR THE REAR BUILDING. WHEN
 ALL THE SCOPE OF WORK IS CLARIFIED, THE PERMITS WILL BE
 ISSUED AND ALL THE EXPIRED PERMITS AND PERMIT
 APPLICATIONS WILL BE PROPERLY REVOKED.
  
 THE FOLLOWING ARE COMMENTS TO THE RE-SUBMITTAL PACKAGE
 SUBMITTED ON 3/9/15:
  
  
 1- ARCHITECT OF RECORD TO SPECIFY ALTERATION LEVEL AS
 REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
 NOTE: KEEP IN MIND CHANGE OF USE FROM GARAGE, STORAGE,
 LAUNDRY AND PLAY ROOM (PER CITY RECORDS MAY 29, 1957)
 TO ADDITIONAL INDEPENDENT APARTMENT AND GARAGE.
  
 ***NOTE: COMMENT WAS NOT PROPERLY ADDRESSED. ARCHITECT
 SPECIFIES "ALTERATION LEVEL 1". THIS IS NOT ALTERATION
 LEVEL 1. THIS IS A CONVERSION OF PART OF THE GARAGE
 INTO AN INDEPENDENT APARTMENT. EVEN THOUGH THE
 APARTMENT IS EXISTING. THERE ARE NO CITY PERMITS FOR
 THE CONVERSION TO APARTMENT.. PLANS ARE TO SHOW CODE
 COMPLIANCE WITH THE CONVERSION TO APARTMENT. REVISE AS
 REQUIRED.
  
 2- CONVERSION TO ADDITIONAL DWELLING UNIT REQUIRES
 REVIEW BY THE THE PALM BEACH COUNTY FOR IMPACT FEES.
 PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 4- CONSTRUCTION DOCUMENTS TO PROVIDE INFORMATION
 SHOWING COMPLIANCE WITH THE ENERGY CODE AS REQUIRED BY
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 COORDINATE INFORMATION WITH THE ENERGY CALCULATIONS TO
 AVOID DELAYS OR CONFLICTS. SPECIFY INSULATION IN ALL
 WALLS AND CEILING (INCLUDING EXTERIOR WALLS). (REPEAT
 COMMENT. PARTIALLY ADDRESSED. THERE IS NOT INFORMATION
 FOR THE INSULATION ON THE EXTERIOR WALL SECTIONS. ALSO,
 CLARIFY WALL TYPE LEGEND ON SHEET A-2. WHAT'S " 5/8"
 GYP. BD (BOTH SIDES) ON 2" X 4" WOOD TRUSSES @ 16" O.C.
 (U.N.O.)". SEC. 107.2.1 CITY AMENDMENTS TO FBC. THERE
 ARE NOT WOOD TRUSSES. REVISE AS REQUIRED.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE OVERHEAD GARAGE DOOR SIZE AS
 SHOWN ON PLANS. NOA 12-1204.10 SUBMITTED IS FOR 18-2"
 NOT FOR 9'-0" WIDE DOOR.
  
 6- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
 NOTE: PROVIDE REVIEW STAMP ON THE FRONT OF THE PRODUCT
 APPROVAL NOT ON THE BACK. STAMP ON THE BACK OF THE PAGE
 IS NOT ACCEPTABLE BECAUSE IS WILL NOT BE SCANNED FOR
 FILING PURPOSES. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 7- PARTITION WALL TYPE 1B DETAIL ON SHEET A-2: PROVIDE
 SPECS SHOWING HOW IS THE GYPSUM BOARD ATTACHED TO THE
 BOTTOM OF THE TRUSSES. THE WAY IT'S DRAWN IT LOOKS LIKE
 IT'S SUSPENDED ON THE AIR NOT ATTACHED TO THE TRUSS.
 REVISE/CLARIFY DETAIL AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC. (REPEAT COMMENT. DETAIL IS NOT
 CLEAR).
  
 NOTE: PLANS SUBMITTED ONLY SHOW WORK IN THE REAR
 APARTMENT BUILDING. THERE ARE NO PLANS FOR THE MAIN
 HOUSE, EXCEPT FOR THE A/C WORK. THERE ARE EXPIRED
 PERMIT APPLICATIONS DATED FEBRUARY 27, 2014 FOR WORK ON
 THE MAIN HOUSE (14021046 AND 14021045). THIS PERMITS
 WERE NEVER ISSUED. THIS ISSUE NEEDS TO BE ADDRESSED
 ALSO.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By J Gomez Date 2015-02-27 Time 18:17 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2015-02-27 18:18:152/27/15 TALKED TO ROBERT BROWN. STOPPED REVIEWS BECAUSE
 PLAN REVIEW FEES STILL ARE NOT PAID. TALKED TO NEYITA
 TO INFORM HER ABOUT THE FEES. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-31 Cont ID  
Sent By jgomez Date 2014-10-30 Time 17:24 Rev Time 0.00
Received By jgomez Date 2014-10-30 Time 17:24 Sent To  
Notes
2014-10-30 17:27:00RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ARCHITECT OF RECORD TO SPECIFY ALTERATION LEVEL AS
 REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
 NOTE: KEEP IN MIND CHANGE OF USE FROM GARAGE, STORAGE,
 LAUNDRY AND PLAY ROOM (PER CITY RECORDS MAY 29, 1957)
 TO ADDITIONAL INDEPENDENT APARTMENT AND GARAGE.
  
 2- CONVERSION TO ADDITIONAL DWELLING UNIT REQUIRES
 REVIEW BY THE THE PALM BEACH COUNTY FOR IMPACT FEES.
 PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 3- WINDOWS IN THE PROPOSED BEDROOM DON'T COMPLY WITH
 SEC. R310 OF 2010 FBC-RESIDENTIAL. AT LEAST ONE WINDOW
 NEEDS TO COMPLY WITH THE MINIMUM WIDTH, HEIGHT AND
 TOTAL CLEAR OPENING. REVISE PLANS AS REQUIRED TO
 COMPLY.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 5- CONSTRUCTION DOCUMENTS TO PROVIDE INFORMATION
 SHOWING COMPLIANCE WITH THE ENERGY CODE AS REQUIRED BY
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 COORDINATE INFORMATION WITH THE ENERGY CALCULATIONS TO
 AVOID DELAYS OR CONFLICTS. SPECIFY INSULATION IN ALL
 WALLS AND CEILING (INCLUDING EXTERIOR WALLS). NOTE: R19
 INSULATION DOESN'T FIT ON A 2X4 STUD WALL. REVISE AS
 REQUIRED. ALSO, CLARIFY WALL TYPE AND STUD SPACING:
 WALL LEGEND SAYS METAL STUDS, WHILE WALL SECTION 1B
 SAYS WOOD STUDS. REVISE AS REQUIRED TO MATCH.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE OVERHEAD GARAGE DOOR AS SHOWN ON
 PLANS.
  
 7- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 8- PARTITION WALL TYPE 1B DETAIL ON SHEET A-2: PROVIDE
 SPECS SHOWING HOW IS THE GYPSUM BOARD ATTACHED TO THE
 BOTTOM OF THE TRUSSES. THE WAY IT'S DRAWN IT LOOKS LIKE
 IT'S SUSPENDED ON THE AIR NOT ATTACHED TO THE TRUSS.
 REVISE/CLARIFY DETAIL AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 9- CLARIFY WHY THERE WAS A SEPARATE SIGNED AND SEALED
 WINDOW AND DOOR SCHEDULED SUBMITTED?. THIS SCHEDULES
 ARE ALREADY SHOWN ON SHEET A-4. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- REVISE STRUCTURAL DOORS AND WINDOWS STRUCTURAL BUCK
 SHOWN ON SHEET A-4. THE BUCK SIZE NEEDS TO PROVIDE FULL
 SUPPORT TO THE DOOR AND WINDOW FRAME AS REQUIRED BY
 SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 NOTE: PLANS SUBMITTED ONLY SHOW WORK IN THE REAR
 APARTMENT BUILDING. THERE ARE NO PLANS FOR THE MAIN
 HOUSE, EXCEPT FOR THE A/C WORK. THERE IS AN EXPIRED
 PERMIT APPLICATION DATED FEBRUARY 27, 2014 FOR WORK ON
 THE MAIN HOUSE. THIS PERMIT WAS NEVER ISSUED.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2015-12-23 Cont ID  
Sent By albarran Date 2015-12-23 Time 10:34 Rev Time 0.00
Received By albarran Date 2015-12-23 Time 09:17 Sent To I
Notes
2015-12-23 10:35:10ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2015-11-02 Cont ID  
Sent By albarran Date 2015-11-02 Time 19:30 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 18:46 Sent To  
Notes
2015-11-02 19:44:30PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALRTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE.
  
 UPON COMPLETION OF MY PREVIOUS REVIEW, I RECEIVED A
 TELEPHONE CALL FROM SOMEONE WITH REGARDS TO THIS
 REVIEW. THE PERSON WAS COMPLAINING BECAUSE HE WAS UNDER
 THE IMPRESSION THAT THIS HAD ALREADY PASSED THE
 ELECTRICAL REVIEW. I WENT ON TO TELL HIM WHAT NEEDED TO
 BE DONE FOR A SATISFACTORY ELECTRICAL REVIEW.
 APPARENTLY THE PERSON IGNORED MY COMMENTS, BECAUSE WITH
 THE SUBSEQUENT SUBMITTAL FAILED TO ADDRESS ANY OF THE
 ELECTRICAL DEFICIENCIES. THIS HAS ALREADY BEEN THROUGH
 THE SIXTH REVIEW. PER FLORIDA STATUTE ONCE THE THERE IS
 A THIRD FAILURE THERE SHALL BE A 4 TIMES REVIEW FEE
 SURCHARGE PLACED THE APPLICATION. THEREFORE, NEXT
 REVIEW WILL HAVE THE SURCHARGE ATTACHED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2015-10-22 Cont ID  
Sent By albarran Date 2015-10-22 Time 13:09 Rev Time 0.00
Received By albarran Date 2015-10-22 Time 11:41 Sent To  
Notes
2015-10-22 13:25:11THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
 1. KITCHEN COUNTER RECEPTACLES SHALL BE SPACED AS
 INSTRUCTED IN NEC 210.52(C).
 A) SPACE THE ONE CLOSEST TO THE ENTRY DOOR PROPERLY SO
 AS NOT TO HAVE > THAN 2? OF COUNTER SPACE ON EITHER
 SIDE.
 B) SPACE THE OTHER TWO 2? FROM THE SINK & REFRIGERATOR
 TO ACCOMPLISH THE SAME. THE GAP WILL HAVE TO BE FILLED
 WITH AN ADDITIONAL OUTLET.
 2. LIVING ROOM OUTLETS SHALL BE SPACED AS PER NEC
 210.52(A). PLACE THE OUTLETS NO MORE THAN 6? FROM THE
 OPENING; THE GAP CAN BE SPLIT WITH THE THIRD OUTLET TO
 COMPLY.
 3. THE SAME RULE HOLDS TRUE FOR THE DINING ROOM. IT IS
 MISSING AN OUTLET NO MORE THAN 6? FROM THE OPENING.
 4. THE BEDROOM IS MISSING AN OUTLET ON THE WALL OUTSIDE
 OF THE BATHROOM.
 5. PER NEC REQUIRED BRANCH CIRCUITS YOU SHALL PROVIDE A
 LAUNDRY CIRCUIT, WHICH SHALL BE INCLUDED IN THE LOAD
 CALCULATIONS AND PANEL SCHEDULE.
 6. YOU SHALL INDICATE THE LOCATION OF THE AIR HANDLER,
 WATER HEATER AND DISPOSAL ON THE PLANS.
 7. YOU SHALL PROVIDE A FULL AND SITE SPECIFIC
 ELECTRICAL SERVICE RISER DIAGRAM AND SHOW THE LOCATION
 OF ALL ELECTRICAL METERS, MAIN DISCONNECTS AND THE
 PANEL FOR THE APARTMENT IN QUESTION.
 8. YOU ARE REQUIRED TO PROVIDE A SWITCH FOR THE GARAGE
 LIGHT AT THE ENTRANCE FROM THE APARTMENT.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
  
2015-10-07 16:09:22NEW PLANS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-09-02 Cont ID  
Sent By ppetty Date 2015-09-02 Time 10:59 Rev Time 0.00
Received By ppetty Date 2015-09-02 Time 10:58 Sent To  
Notes
2015-09-02 10:59:43GARAGE/CONVERSION REAR BLDG ONLY
 DENIED SMALL BIN #C
 PP

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-03-31 Cont ID  
Sent By sciard Date 2015-03-31 Time 13:25 Rev Time 0.00
Received By sciard Date 2015-03-31 Time 13:25 Sent To  
Notes
2015-03-31 13:28:291. ADDRESS BUILDING COMMENTS FOR WORK DONE WITHOUT
 PERMITS.
 2. ALL PREVIOUS COMMENTS NOT ADDRESSED.
 3. INCLUDE PANEL SCHEDULE FOR PANEL "M".

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By S Ciard Date 2015-02-27 Time 18:19 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2015-02-27 18:19:112/27/15 TALKED TO ROBERT BROWN. STOPPED REVIEWS BECAUSE
 PLAN REVIEW FEES STILL ARE NOT PAID. TALKED TO NEYITA
 TO INFORM HER ABOUT THE FEES. JG.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-20 Cont ID  
Sent By sciard Date 2014-10-20 Time 13:47 Rev Time 0.00
Received By sciard Date 2014-10-20 Time 13:47 Sent To  
Notes
2014-10-20 13:55:171. SHOW COMPLETE SERVICE RISER DIAGRAM. SUBMITTED PLAN
 SHOWS DOUBLE LUGGED METER CAN.
 2. N.E.C. 225.31,225.32,225.36. DISCONNECTING MEANS TO
 MEET CRITERIA OF CODE SECTION NOTED FOR SEPARATE
 BUILDING.
 3. N.E.C. 250.32 (D). GROUNDING OF SEPARATE BUILDING OR
 STRUCTURE ON SAME PREMISES.
 4. N.E.C. 210.52 (B) (1). DINING ROOM RECEPTACLE TO BE
 ON SMALL APPLIANCE CIRCUIT. NOT GENERAL LIGHTING.
 5. N.E.C. 422.11 (E). OCPD FOR 5000 WATT WATER HEATER.
 ON PANEL SCHEDULE.
 6. MECHANICAL PLAN SHOWS 5 KW AHU. CHECK OCPD ON PANEL
 SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2015-12-23 Cont ID  
Sent By albarran Date 2015-12-23 Time 10:35 Rev Time 0.00
Received By albarran Date 2015-12-07 Time 10:26 Sent To  
Notes
2015-12-23 10:36:1012/23/15 PASSED ELECTRICAL, THE LAST OF ALL REVIEWS.
 RUNNER NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "M".
 MA
2015-12-09 10:26:10R16

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2015-11-03 Cont ID  
Sent By albarran Date 2015-11-03 Time 09:33 Rev Time 0.00
Received By albarran Date 2015-10-23 Time 12:59 Sent To  
Notes
2015-11-03 09:39:5211/3/15 FAILED ELECTRICAL REVIEW FOR THE SIXTH TIME.
 CONTRACTOR NOTIFIED OF ESCALATED FEES & REVIEW STATUS.
 SENT TO SMALL DENIED BIN "M". MA
2015-10-26 12:59:39RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-10-22 Cont ID  
Sent By albarran Date 2015-10-22 Time 13:26 Rev Time 0.00
Received By albarran Date 2015-09-25 Time 14:20 Sent To  
Notes
2015-10-22 13:27:0210/22/15 FAILED ELECTRICAL REVIEW AS NOTED. PERMIT
 RUNNER NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN
 "M". MA
2015-09-25 14:21:21ON JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-09-25 Cont ID  
Sent By cpuell Date 2015-09-25 Time 14:18 Rev Time 0.00
Received By cpuell Date 2015-08-13 Time 13:56 Sent To  
Notes
2015-08-28 10:51:208/28/15 PLANS GIVEN TO JGOMEZ TO DO REVIEW, THEN TO
 GIVE TO ZONING OR ELECTRICAL.
2015-08-25 09:51:238/25/15 NEW PLANS SUBMITTED. SENT TO "LIBRARY" FOR
 REVIEW. JG.
2015-08-13 13:57:06RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-05-13 Cont ID  
Sent By jgomez Date 2015-05-13 Time 17:40 Rev Time 0.00
Received By jgomez Date 2015-05-13 Time 17:38 Sent To  
Notes
2015-05-13 17:39:19SUBMITTAL OF PLANS WITH COUNTY IMPACT FEES STAMP. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-31 Cont ID  
Sent By sciard Date 2015-03-31 Time 13:30 Rev Time 0.00
Received By sciard Date 2015-03-09 Time   Sent To  
Notes
2015-03-20 14:09:443/20/15 SENT TO R29 SHELF FOR ZONING AND ELECTRICAL
 REVIEW. JG.
2015-03-09 17:00:29SENT TO J. GOMEZ'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-27 Cont ID  
Sent By jgomez Date 2015-02-27 Time 17:58 Rev Time 0.00
Received By jgomez Date 2015-01-30 Time 14:16 Sent To  
Notes
2015-02-27 18:02:222/27/15 TALKED TO ROBERT BROWN. STOPPED REVIEWS BECAUSE
 PLAN REVIEW FEES STILL ARE NOT PAID. TALKED TO NEYITA
 TO INFORM HER ABOUT THE FEES. JG.
2015-01-30 14:39:06R-10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-30 Cont ID  
Sent By jgomez Date 2014-10-30 Time 18:24 Rev Time 0.00
Received By jgomez Date 2014-10-17 Time 13:15 Sent To  
Notes
2014-10-17 13:16:15R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-10-29 Cont ID  
Sent By jgomez Date 2015-10-29 Time 11:13 Rev Time 0.00
Received By jgomez Date 2015-10-29 Time 11:13 Sent To  
Notes
2015-10-29 11:13:5610/29/15 @ 1:03PM. CALLED WILLIE SWOOPE (COUNTY) IMPACT
 FEES PAID $4116.25. MU-2015-9033. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-10-07 Cont ID  
Sent By jgomez Date 2015-10-07 Time 16:26 Rev Time 0.00
Received By jgomez Date 2015-10-07 Time 16:26 Sent To  
Notes
2015-10-07 16:28:261- IMPACT FEES: NEED COPY OF PAID RECEIPT. COUNTY
 IMPACT FEES STAMP ON PLANS STATES THAT $4116.25 IS DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-09-01 Cont ID  
Sent By jgomez Date 2015-09-01 Time 13:12 Rev Time 0.00
Received By jgomez Date 2015-09-01 Time 13:12 Sent To  
Notes
2015-09-01 13:13:201- IMPACT FEES: NEED NEW SET OF PLANS STAMPED BY PALM
 BEACH COUNTY AND NEED COPY OF PAID RECEIPT. REQUIRED BY
 THE COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-05-13 Cont ID  
Sent By jgomez Date 2015-05-13 Time 17:40 Rev Time 0.00
Received By jgomez Date 2015-05-13 Time 17:40 Sent To  
Notes
2015-05-13 17:41:011- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. JG.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-12-14 Time 19:07 Rev Time 0.00
Received By jgomez Date 2015-12-14 Time 19:07 Sent To  
Notes
2015-12-14 19:07:53MECHANICAL PROVISO:
  
 1- PROVIDE COMPLETE HEATING /COOLING CALCULATIONS USING
 AN APPROVED PROGRAM.
 2- PROVIDE A/C PLANS SHOWING HEATING FOR ALL HABITABLE
 ROOMS AND EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-10-29 Time 08:57 Rev Time 0.00
Received By jgomez Date 2015-10-29 Time 07:29 Sent To  
Notes
2015-10-29 08:58:2910/29/15 TALKED TO PETER. HE AGREED TO PROVIDE COMPLETE
 AND CORRECT INFORMATION UNDER A REVISION. FEES APPLY.
  
 PROVIDE MECHANICAL REVISION WITH THE FOLLOWING:
 1- HEATING /COOLING CALCULATIONS USING AN APPROVED
 PROGRAM.
 2- PROVIDE A/C PLANS SHOWING HEATING FOR ALL HABITABLE
 ROOMS AND EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2015-10-08 Cont ID  
Sent By jgomez Date 2015-10-08 Time 09:23 Rev Time 0.00
Received By jgomez Date 2015-10-08 Time 07:55 Sent To  
Notes
2015-10-08 09:26:58RESIDENTIAL (R3) ALTERATION, FOURTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS USING AN APPROVED PROGRAM.
 INFORMATION SUBMITTED DOESN'T IDENTIFY WHICH PROGRAM
 WAS USED. ALSO. SPECIFY EQUIPMENT MANUFACTURER AND
 MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- ENGINEER SHOWN ON THE TITLE BLOCK OF THE EQUIPMENT
 SIZING SIZING CALCULATIONS TO SIGN AND SEAL
 CALCULATIONS AS REQUIRED BY CHAPTER 471 F.S. (REPEAT
 COMMENT).
  
 RESPONSE:
 CALCULATIONS SUBMITTED LAST TIME WAS MISSING THE SEAL
 OF THE ENGINEER. CALCULATIONS SUBMITTED NOW ARE MISSING
 THE SEAL AND SIGNATURE.
  
 3- NEW COMMENT: MECHANICAL PLANS WAS REVISED.
 CALCULATIONS SUBMITTED DON'T MATCH REVISED MECHANICAL
 PLAN. REVISED AS REQUIRED. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 ***ENGINEER OF RECORD LETTER ADDRESSING EACH COMMENT
 WILL HELP TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-09-01 Cont ID  
Sent By jgomez Date 2015-09-01 Time 15:24 Rev Time 0.00
Received By jgomez Date 2015-09-01 Time 12:49 Sent To  
Notes
2015-09-01 15:35:08RESIDENTIAL (R3) ALTERATION, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS USING AN APPROVED PROGRAM.
 INFORMATION SUBMITTED DOESN'T IDENTIFY WHICH PROGRAM
 WAS USED. ALSO. SPECIFY EQUIPMENT MANUFACTURER AND
 MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- ENGINEER WHO SIGNED THE EQUIPMENT SIZING
 CALCULATIONS TO PROVIDE HIS ENGINEER SEAL AS REQUIRED
 BY CHAPTER 471 F.S.
  
 3- MECHANICAL PLAN SUBMITTED: LOCATION OF RETURN AIR BY
 THE KITCHEN DOESN'T COMPLY WITH SEC. M1602.2 OF 2010
 FBC-RESIDENTIAL.
  
 4- EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15 TIMES
 GREATER THAN THE TOTAL CALCULATED LOAD. SEC. 403.6.1.1
 OF 2010 FBC-ENERGY CONSERVATION.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 18:47 Rev Time 0.00
Received By jgomez Date 2015-03-19 Time 18:47 Sent To  
Notes
2015-03-19 18:48:16RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 IMPORTANT:
 THERE ARE SEVERAL ISSUES THAT NEED TO BE ADDRESSED.
 THERE WAS BUILDING, MECHANICAL, PLUMBING AND ELECTRICAL
 WORK DONE WITHOUT PERMITS. PERMIT APPLICATIONS WERE
 APPLIED FOR, BUT PERMITS WERE NOT ISSUED. ONE
 MECHANICAL PERMIT WAS ISSUED AND THE OTHER WAS NOT
 (BOTH ARE EXPIRED NOW). THE BEST WAY TO CLEAR UP ALL
 THE ISSUES IS TO PROVIDE COMPLETE PLANS AND
 SPECIFICATIONS FOR BOTH BUILDINGS, MAIN HOUSE AND REAR
 BUILDING . SHOW ALL WORK: DONE AND PROPOSED. PROVIDE
 PERMIT APPLICATION FOR THE MAIN HOUSE AND ANOTHER
 PERMIT APPLICATION FOR THE REAR BUILDING. WHEN ALL THE
 SCOPE OF WORK IS CLARIFIED, THE PERMITS WILL BE ISSUED
 AND ALL THE EXPIRED PERMITS AND PERMIT APPLICATIONS
 WILL BE PROPERLY REVOKED.
  
 THE FOLLOWING ARE COMMENTS TO THE RE-SUBMITTAL PACKAGE
 SUBMITTED ON 3/9/15:
  
 1- PROPOSED APARTMENT:
 A) PROVIDE COMPLETE (NOT JUST THE SUMMARY) HEATING AND
 COOLING EQUIPMENT SIZING CALCULATIONS USING AND
 APPROVED METHOD AND BASED ON THE BUILDING ACTUAL L
 ORIENTATION. ALSO, SPECIFY EQUIPMENT MANUFACTURER AND
 MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) EQUIPMENT SIZING CALCULATIONS TO BE DONE BASED ON
 THE REQUIREMENTS OF SEC. 403.6.1 AND SEC. 302.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15 TIMES
 GREATER THAN THE TOTAL CALCULATED LOAD. SEC. 403.6.1.1
 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) ARCHITECT SIGNED AND SEALED THE EQUIPMENT SIZING
 CALCULATIONS. NEED TO PROVIDE COMPLETE ARCHITECT'S
 INFORMATION AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- MAIN HOUSE:
  
 A) PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AND
 MANUFACTURER NAME AND MODEL NUMBERS. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION. NONE SUBMITTED AT THIS TIME.
 NOTE: SEE COMMENTS ABOVE REGARDING THE EQUIPMENT SIZING
 CALCULATIONS.
  
 B) BALANCED RETURN AIR INFORMATION SHOWN ON SHEET M-2
 IS NOT CLEAR. CLEARLY IDENTIFY WHICH RETURN AIR GRILL
 AND DUCTS ARE CONNECTED BACK TO THE AIR HANDLER UNIT .
 THERE IS A RETURN AIR GRILL SHOWN ON THE DINING ROOM
 AREA, BUT IT DOESN'T SHOW IF IT'S CONNECTED TO THE
 UNIT. SEC. M1602.4.
  
 C) REVISE THE BALANCED RETURN AIR TRANSFER GRILL SIZE
 SPECIFIED FOR THE MASTER BEDROOM. NEED TO CONSIDER ALL
 THE SUPPLY AIR INTO THE MASTER BEDROOM TO PROPERLY SIZE
 THE TRANSFER GRILL. SEE EXCEPTION #3 OF SEC. M1602.4 OF
 2010 FBC-RESIDENTIAL.
  
  
 ****NOTE: SEPARATE A/C PERMIT IS REQUIRED FOR EACH
 BUILDING.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By J Gomez Date 2015-02-27 Time 18:18 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2015-02-27 18:18:302/27/15 TALKED TO ROBERT BROWN. STOPPED REVIEWS BECAUSE
 PLAN REVIEW FEES STILL ARE NOT PAID. TALKED TO NEYITA
 TO INFORM HER ABOUT THE FEES. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-31 Cont ID  
Sent By jgomez Date 2014-10-30 Time 18:22 Rev Time 0.00
Received By jgomez Date 2014-10-30 Time 18:22 Sent To  
Notes
2014-10-30 18:24:16RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROPOSED APARTMENT AND GARAGE BUILDING:
 A) PROVIDE EQUIPMENT SIZING CALCULATIONS WITH THE
 EQUIPMENT MANUFACTURER'S AND MODEL NUMBER AS REQUIRED
 BY SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. NOTE:
 EQUIPMENT TO MATCH EQUIPMETN LISTED IN THE A/C PLAN.
  
 B) PROVIDE COMPLIANCE WITH THE BALANCED RETURN AIR FOR
 THE BEDROOM AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. NOTE: THIS IS ONE BEDROOM APARTMENT.
 SO, IT COUNTS AS A MASTER BEDROOM. SEE EXCEPTION #3 OF
 SEC. M1602.4 OF 2010 FBC-RESIDENTIAL FOR PROPER DUCT
 SIZING.
  
 2- MAIN HOUSE:
 A) PROVIDE EQUIPMENT SIZING CALCULATIONS WITH THE
 EQUIPMENT MANUFACTURER'S AND MODEL NUMBER AS REQUIRED
 BY SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. NOTE:
 EQUIPMENT TO MATCH EQUIPMETN LISTED IN THE A/C PLAN.
  
 B) PROVIDE COMPLIANCE WITH THE BALANCED RETURN AIR FOR
 ALL THE BEDROOMS AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. NOTE: SEE EXCEPTION #3 OF SEC. M1602.4
 OF 2010 FBC-RESIDENTIAL FOR MASTER BEDROOM PROPER DUCT
 SIZING.
  
 ****NOTE: SEPARATE A/C PERMIT MAY BE REQRUIED FOR EACH
 BUILDING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 09:29 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-10-29 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 15:37 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 15:37 Sent To  
Notes
2015-10-29 11:20:31NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-08 Cont ID  
Sent By gjohnson Date 2015-10-08 Time 16:28 Rev Time 0.00
Received By gjohnson Date 2015-10-08 Time 16:28 Sent To  
Notes
2015-10-07 16:08:22NEW PLANS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-08-27 Cont ID  
Sent By gjohnson Date 2015-08-27 Time 14:08 Rev Time 0.00
Received By gjohnson Date 2015-08-27 Time 14:08 Sent To  
Notes
2015-08-25 09:52:308/25/15 NEW PLANS SUBMITTED. SENT TO R21 SHELF FOR
 REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-10-28 Cont ID  
Sent By tklarge Date 2014-10-28 Time 04:25 Rev Time 0.00
Received By tklarge Date 2014-10-28 Time 04:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2015-09-04 Cont ID  
Sent By sgraham Date 2015-09-04 Time 09:58 Rev Time 0.00
Received By sgraham Date 2015-09-04 Time 09:58 Sent To  
Notes
2015-08-25 09:52:548/25/15 NEW PLANS SUBMITTED. SENT TO R21 SHELF FOR
 REVIEW. JG.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-03-27 Cont ID  
Sent By sgraham Date 2015-03-27 Time 16:03 Rev Time 0.00
Received By sgraham Date 2015-03-27 Time 16:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-02-24 Cont ID  
Sent By S Graham Date 2015-02-24 Time 09:43 Rev Time 0.00
Received By sgraham Date 2015-02-24 Time 09:43 Sent To  
Notes
2015-02-24 09:44:272/24/15 2ND CHECKLIST
  
 1. PROVIDE TWO UP TO DATE SURVEYS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-27 Cont ID  
Sent By sgraham Date 2014-10-27 Time 15:13 Rev Time 0.00
Received By sgraham Date 2014-10-27 Time 15:13 Sent To  
Notes
2014-10-27 15:13:1810/27/14 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS