2014-11-13 16:48:06 | BUILDING PLAN REVIEW |
| PERMIT: 14100487 |
| ADD: 5818 S. DIXIE HWY. |
| CONT: MACO CONSTRUCTION |
| TEL: (561)379-3171 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. NOV. 13/ 2014 |
| ACTION: DENIED |
| |
| 1) SITE PLAN: |
| 1A) PLEASE SEE THE 2010 FL ACCESS. CODE FOR AN |
| ACCESSIBLE AISLE WIDTH. 2010 FL. ACCESS. CODE 502.3.1. |
| ACCESS AISLES SERVING CAR AND VAN PARKING SPACES SHALL |
| BE 60 INCHES (1525 MM) WIDE MINIMUM. |
| |
| 1B) THE ACCESS AISLE IS ALSO TO BE DOUBLE STRIPED PER |
| CITY MUNI. CODE 94-485. PLEASE SEE 2010 ACCESS. |
| ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE |
| TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT |
| THE AISLE BE CLEARLY MARKED. |
| |
| 2) THE PLANS INDICATE THIS REMODEL IS TO BECOME A |
| URGENT CARE FACILITY. NOTE IF IT IS CONSIDERED A |
| REHABILITATION FACILITIES AND OUTPATIENT PHYSICAL |
| THERAPY FACILITIES SEE ADVISORY: |
| ADVISORY 208.2.2 REHABILITATION FACILITIES AND |
| OUTPATIENT PHYSICAL THERAPY FACILITIES. CONDITIONS THAT |
| AFFECT MOBILITY INCLUDE CONDITIONS REQUIRING THE USE OR |
| ASSISTANCE OF A BRACE, CANE, CRUTCH, PROSTHETIC DEVICE, |
| WHEELCHAIR, OR POWERED MOBILITY AID; ARTHRITIC, |
| NEUROLOGICAL, OR ORTHOPEDIC CONDITIONS THAT SEVERELY |
| LIMIT ONE?S ABILITY TO WALK; RESPIRATORY DISEASES AND |
| OTHER CONDITIONS WHICH MAY REQUIRE THE USE OF PORTABLE |
| OXYGEN; AND CARDIAC CONDITIONS THAT IMPOSE SIGNIFICANT |
| FUNCTIONAL LIMITATIONS. |
| |
| IF THIS UNIT IS CONSIDERED A REHABILITATION FACILITIES |
| AND OUTPATIENT PHYSICAL THERAPY FACILITIES, THEN |
| PARKING COMPLIANCE WITH: |
| FL ACCESS. CODE IS REQUIRED. 208.2.2 REHABILITATION |
| FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES. |
| TWENTY PERCENT OF PATIENT AND VISITOR PARKING SPACES |
| PROVIDED TO SERVE REHABILITATION FACILITIES |
| SPECIALIZING IN TREATING CONDITIONS THAT AFFECT |
| MOBILITY AND OUTPATIENT PHYSICAL THERAPY FACILITIES |
| SHALL COMPLY WITH 502. |
| |
| 3) MISSING SOILS REPORT. SHEET S-2 NOTE # 2 INDICATES |
| THE SAFE MINIMUM BEARING VALUE OF THE SOIL IS 2500 PSF. |
| NOTE # 1 INDICATES A SOILS ENGINEER IS TO PROVIDE A |
| SOILS AND FOUNDATION INVESTIGATION REPORT BY AN |
| APPROVED TESTING LABORATORY. 2010 FBC-B. 1803.5.2 |
| QUESTIONABLE SOIL. |
| |
| 4) FLORIDA ENERGY GAUGE REPORT FORM 506-2010 |
| PERFORMANCE BASED COMPLIANCE. |
| |
| 4A) THE ENERGY GAUGE REPORT INDICATES THE EXTERIOR WALL |
| INSULATION IS TO BE A R-4.8 VALUE. SHEET A-3 DETAIL # |
| 10 SHOWS THE R4.8 INSULATION BUT THE DETAIL DOES NOT |
| PROVIDE HOW HIGH THE EXTERIOR WALL INSULATION IS TO BE |
| INSTALLED. ENERGY 506.3.2. |
| |
| 4B) THE ENERGY GAUGE REPORT INDICATES THE EXTERIOR PAIR |
| OF DOORS ARE ALUMINUM DOORS W/ (2) SIDE LITES, 1.25 IN. |
| W/ POLYSTYRENE INSULATION. THES DOORS ARE OVER 50% |
| GLAZED DOORS AND SHOULD BE TAKEN AS WINDOWS. THE WINDOW |
| SIZES PROVIDED DO NOT CORRELATE WITH THE SIZES PROVIDED |
| ON THE PLANS. |
| THE REPORT LIST THE SHGC AS 0.50 THE SHADING |
| COEFFICIENT HAS NOT BEEN DEMINTRATED, AND THE REPORT |
| ALSO INDICATES THE WINDOWS ARE NOT SHADED, WHERE AS THE |
| PLANS INDICATE THE USE OF BAHAMA SHUTTERS OVER THE |
| WINDOWS AND A PORCH OVER THE FRONT ENTRY. |
| |
| 4C) DISCREPANCY IN REPORT UNDER THE HEADING ROOFING |
| PAGE 3, ZONE PR)ZO1 THE REPORT INDICATES THE ROOFING |
| INSULATION TO BE 4 IN. ISO/ METAL ROOF DECK W/ BUILT UP |
| ROOF 2 IN. OF GRAVEL. ROOF VALUE OF R 6.7. PAGE 7 NAME |
| BUILT UP ROOF INDICATES BUILT UP ROOF GRAVEL/ 2IN. ISO/ |
| METAL DECK THE R VALUE OF 6.7 WITHOUT THE 4 INCHES OF |
| INSULATION? 107.2.1.3 DISCREPANCY. |
| |
| 4D) THE PLANS DO NOT PROVIDE HOW THE ROOF INSULATION |
| UNDER THE NEW TOWER WILL BE APPLIED. WILL IT BE ON THE |
| EXISTING ROOF DECK OR WILL IT CONTINUE UP AND INTO THE |
| TOWER WALLS AND UNDER THE ROOF DECK? 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. ENERGY 506.3.2 |
| |
| 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) TO DATE PRODUCT APPROVALS HAVE NOT BEEN REVIEWED BY |
| THE DESIGNER OF RECORD. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. NO APPROVALS WERE SUBMITTED FOR |
| THE GLAZED FRENCH DOORS.L |
| (B) WINDOWS NOT REVIEWED BY THE DESIGNER OF RECORD. |
| (C) WALL LOUVERS A/C FRESH AIR MAKE UP? |
| (D) ROOFING PRODUCTS AND ASSEMBLIES NOT REVIEWED BY THE |
| DESIGNER OF RECORD, NOTE WHAT ATTACHMENT METHODS WILL |
| BE REQUIRED FOR EACH ROOF ZONE. |
| (E) SHUTTERS BAHAMA SHUTTERS IN OPEN FIXED POSITION. |
| 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. FBC-B |
| 3105.5.1 LOADS. |
| RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO |
| RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE |
| EXCEPT THAT STRUCTURES OR PARTS THEREOF WHICH ARE |
| INTENDED TO BE REMOVED OR REPOSITIONED DURING PERIODS |
| OF HIGH WIND VELOCITY SHALL BE DESIGNED IN THEIR OPEN |
| OR EXTENDED POSITION TO DESIGN PRESSURES BASED ON A |
| BASIC WIND SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST |
| WITH APPLICABLE SHAPE FACTORS. |
| |
| (G) PRE-ENGINEERED A/C STANDS IF APPLICABLE. |
| |
| 7) SHEET A3 DETAIL # 10 INDICATES THE USE OF BEVELED |
| WOOD BUCKS WITH THE BACK WINDOW FRAME SUPPORT NOT |
| RESTING ON THE BEVELED BUCK. 2010 FBC-B |
| 1715.5.4.2 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND |
| BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME |
| SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED. |
| |
| 8) SHEET A4.2 DETAIL # 12 THE RECEPTION DESK SHOWS THE |
| COUNTER HEITH OF 42 INCHES HIGH. PLEASE PROVIDE |
| COMPLIANCE WITH : |
| 2010 FL ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. |
| WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| WITH 902.3. |
| 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND |
| OR |
| 904.4 SALES AND SERVICE COUNTERS. |
| SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| SERVICE COUNTER TOP. |
| EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A |
| COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A |
| REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK |
| STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL |
| BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION |
| WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH |
| 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR |
| GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF |
| THE COUNTER. |
| 904.4.1 PARALLEL APPROACH. |
| A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915 |
| MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR |
| OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915 |
| MM) MINIMUM LENGTH OF COUNTER. |
| EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS |
| THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER |
| SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE |
| THE FINISH FLOOR. |
| 904.4.2 FORWARD APPROACH. |
| A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760 |
| MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH |
| 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR |
| OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| FOR A FORWARD APPROACH TO THE COUNTER. |
| |
| TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| TUS.ASPX FOR PERMIT STATUS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |