Plan Review Details - Permit 14100405
Plan Review Stops For Permit 14100405
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-20 Cont ID  
Sent By shill Date 2015-01-20 Time 11:44 Rev Time 0.00
Received By shill Date 2015-01-20 Time 11:44 Sent To  
Notes
2015-01-20 11:44:39****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 INSTALLATION SCHEDULE DID NOT INCLUDE THE FOLLOWING
 INFORMATION:
  
 SHUTTER CONNECTION MOUNTING TYPE (SHOULD CORRELATE WITH
 THE ANCHOR CHARTS ON PAGE 4 OF THE NOA; EITHER C1, C2,
 C3, C4, OR C5)
 ANCHOR SPACING
  
 THEREFORE, INSTALLATION SCHEDULE HAS BEEN REDLINED FOR
 WORST CASE (C5, 5" ANCHOR SPACING)
  
 IF THIS IS NOT ACCEPTABLE, SUBMIT A REVISION WHICH
 INCLUDES A REVISED INSTALLATION SCHEDULE WITH SHUTTER
 CONNECTION MOUNTING TYPE AND ANCHOR SPACING PROPOSED;
 OR, DO NOT PICK UP THIS PERMIT AND RESUBMIT WITH A
 REVISED INSTALLATION SCHEDULE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-20 Cont ID  
Sent By jwitmer Date 2014-11-20 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 15:58 Sent To  
Notes
2014-11-20 16:46:52BUILDING PLAN REVIEW
 PERMIT: 14100405
 ADD: 519 PILGRIM RD
 CONT: T. H. MOTTLEY
 TEL: (561)502-1986
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. NOV. 20/ 2014
 ACTION: DENIED
  
 1) THE WINDOW SUBMITTED IS FOR A JELD-WEN PREMIUM
 ATLANTIC ALUMINUM 6100 SINGLE HUNG WINDOW NON-IMPACT .
 THE 5 EGRESS WINDOWS THAT ARE BEING INSTALLED ARE A
 36X63 NON-IMPACT WINDOW. PLEASE PROVIDE MANUFACTURERS
 SPECIFICATIONS FOR THIS WINDOW. THE 2ND STORY WINDOWS
 REQUIRE A 5.7 SQ. FT. CLEAR OPENING. DPENDING ON THE
 MANUFACTURERS SOME WINDOWS MEET THE 2ND STORY EGRESS
 REQUIREMENTAND SOME HAVE MODIFIED SASH STOPS TO
 MEETTHIS WINDOW WITH THE DIMENSIONS OF 36X63 INCH
 WINDOW, THE 2ND ISSUE WITH THIS PARTICULAR WINDOW IS
 THE TOP SASH IS SMALLER THAN THE BOTTOM SASH SO THE
 BOTTOM SASH WILL HANG BENEATH THE UPPER VENT.
 2010 FBC-R R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530
 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
  
 2) DEPENDING ON THE RESULTS OF COMMENT # 1 THE HEIGHT
 REQUIREMENTS OF THE SHUTTERS MAY NEED TO BE MODIFIED.
 THE SECOND ISSUE WITH THE SHUTTER INSTALATION SCHEDULE
 IS THE SPACING HAS NOT BEEN IDENTIFIED ON THE CHART OR
 ON THE SCHEDULE. 107.2.1.3 ADDITIONAL DATAREQUIRED.
  
 .THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-21 Cont ID  
Sent By shill Date 2014-10-21 Time 09:48 Rev Time 0.00
Received By shill Date 2014-10-21 Time 09:48 Sent To  
Notes
2014-10-21 09:51:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE THE FLOOR PLAN TO SHOW WINDOW SIZES.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-20 Cont ID  
Sent By shill Date 2015-01-20 Time 11:44 Rev Time 0.00
Received By shill Date 2015-01-13 Time 17:48 Sent To  
Notes
2015-01-13 17:48:26TO SHILL DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-20 Cont ID  
Sent By jwitmer Date 2014-11-20 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-21 Cont ID  
Sent By shill Date 2014-10-21 Time 09:51 Rev Time 0.00
Received By shill Date 2014-10-15 Time 12:57 Sent To  
Notes
2014-10-14 10:54:04ROUTED TO BLDG $5000 & UNDER