Plan Review Details - Permit 14100359
Plan Review Stops For Permit 14100359
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-04 Cont ID  
Sent By jwitmer Date 2014-12-04 Time 06:16 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 05:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-15 Cont ID  
Sent By jwitmer Date 2014-10-15 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2014-10-11 Time 14:02 Sent To  
Notes
2014-10-11 14:28:17BUILDING PLAN REVIEW
 PERMIT: 14100359
 ADD: 333 CLEMATIS ST
 CONT: RAYMOND NORDINE
 TEL: (561)252-1662
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 11/ 2014
 ACTION: DENIED
  
 1) PROVIDE THE EXISTING LAYOUT AS WELL AS THE PROPOSED
 WORK TO BE ACCOMPLISHED UNDER THIS PERMIT. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 THE DECLARED VALUE SEEMS LOW FOR THE AMOUNT OF WORK
 DESCRIBED UNDER THIS PERMIT. 108.3* BUILDING PERMIT
 VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS
  
 2) THE REAR RESTROOM BLOCKS THE EGRESS PATH, PLEASE
 COMPLY WITH 2010 FBC-B 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-15 Cont ID  
Sent By tlarge Date 2014-12-15 Time 16:18 Rev Time 0.00
Received By dhayes Date 2014-12-15 Time 16:18 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-30 Cont ID  
Sent By dhayes Date 2014-10-30 Time 17:03 Rev Time 0.00
Received By dhayes Date 2014-10-30 Time 16:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-03 Cont ID  
Sent By pleduc Date 2014-12-03 Time   Rev Time 0.00
Received By pleduc Date 2014-12-03 Time 12:43 Sent To  
Notes
2014-12-03 12:55:58RESUBMITTED COMMENTS:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO
  
 THE PROPOSED DOOR SWING INTO THE EXIT HALLWAY IS NOT
 ACCEPTABLE. THE BATHROOM DOOR SHALL SWING INTO THE
 BATHROOM, KEEPING CLEAR THE EXIT PATH LEADING TO THE
 REAR EXIT DOOR.
  
 ADD AN ADDITIONAL EXIT SIGN AT THE BEGINNING OF THE
 HALLWAY LEADING TO THE REAR EXIT DOOR.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-20 Cont ID  
Sent By pleduc Date 2014-10-20 Time   Rev Time 0.00
Received By pleduc Date 2014-10-20 Time 13:23 Sent To  
Notes
2014-10-20 13:28:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO
  
 THE PROPOSED DOOR SWING INTO THE EXIT HALLWAY IS NOT
 ACCEPTABLE. THE BATHROOM DOOR SHALL SWING INTO THE
 BATHROOM, KEEPING CLEAR THE EXIT PATH LEADING TO THE
 REAR EXIT DOOR.
  
 ADD AN ADDITIONAL EXIT SIGN AT THE BEGINNING OF THE
 HALLWAY LEADING TO THE REAR EXIT DOOR.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-16 Cont ID  
Sent By tklarge Date 2014-12-16 Time 12:34 Rev Time 0.00
Received By tklarge Date 2014-12-02 Time   Sent To  
Notes
2014-12-03 06:54:46INCOMING SENT TO B05 .

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-30 Cont ID  
Sent By dhayes Date 2014-10-30 Time 17:05 Rev Time 0.00
Received By dhayes Date 2014-10-10 Time 13:56 Sent To  
Notes
2014-10-10 13:57:17INCOMING SENT TO B-06 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-10-10 Cont ID  
Sent By jwitmer Date 2014-10-10 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2014-10-10 Time 13:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-10-27 Cont ID  
Sent By hmoser Date 2014-10-27 Time 14:31 Rev Time 0.00
Received By hmoser Date 2014-10-27 Time 14:05 Sent To  
Notes
2014-10-27 14:31:07CALLED RAYMOND NORDINE THERE IS NO MECHANICAL WORK AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-12-16 Cont ID  
Sent By tklarge Date 2014-12-16 Time 12:34 Rev Time 0.00
Received By tklarge Date 2014-12-16 Time 06:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-12-04 Cont ID  
Sent By tklarge Date 2014-12-04 Time 10:34 Rev Time 0.00
Received By tklarge Date 2014-12-04 Time 06:46 Sent To  
Notes
2014-12-04 10:34:161) THE SINK NEXT TO THE 3 COMPARTMENT SINK IS MISSING
 FROM THE WATER RISER DIAGRAM.
 2) AS DRAWN, THE SANITARY RISER SHOWS THE GREASE TRAP,
 MOP SINK, FLOOR SINKS, AND HAND SINKS ON A HORIZONTAL
 WET VENT WHICH IS PROHIBITED BY THE 2010 FL. PLUMBING
 CODE (FPC) SEC.909. A VENT DRAWN ON THE WATER CLSET IS
 AN OPTION TO CORRECT THIS VIOLATION. 2ND REQUEST.
 3) SUBMIT MANUF.SPECS/INSTALLATION INSTRUCTIONS FOR THE
 GELATO MACHINE.WPB AMEND TO 2010 FBC SEC.107.2.1. 2ND
 REQUEST.
 4) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. IF THE
 INTERCEPTOR IS CONCRETE, THE DESIGN SHALL COMPLY WITH
 THE 2010 FPC SECS. 1003.5.2, 1003.5.3, AND THE FLORIDA
 ADMINISTRATIVE CODE RULE 64E-6. SUBMIT A DETAIL FOR THE
 INTERCEPTOR. 2ND REQUEST.WPB AMEND. TO 2010 FPC SEC.
 107.2.1. 2ND REQUEST.
 5) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS
 INDICATE 17 SEATS BUT THE PLAN ONLY SHOWS 8. CLARIFY.
 2ND REQUEST.
 6) YOU HAVE PROVIDED CALCULATIONS FOR THE GPM
 DISCHARGING INTO THE INTERCEPTOR. IN ORDER TO FIGURE
 THE TOTAL GPM DISCHARGING INTO THE INTERCEPTOR, ALL THE
 FIXTURES DISCHARGING INTO THE INTERCEPTOR MUST BE
 INCLUDED IN THE CALCULATIONS.YOU HAVE NOT INCLUDED THE
 THREE HAND SINKS. CLARIFY.
 7) A FULL FLOW VALVE IS REQD.ON THE C.W.FEED TO THE
 WATER HEATER. 2010 FPC SEC.606.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-29 Cont ID  
Sent By tklarge Date 2014-10-23 Time 04:47 Rev Time 0.00
Received By tklarge Date 2014-10-23 Time 04:47 Sent To  
Notes
2014-10-23 11:00:191) THE PLANS SHOW THE RESTROOMS LOCATED IN AN AREA THAT
 REQUIRES ACCESS THROUGH THE FOOD PREPARATION AREA.THE
 ROUTE TO PUBLIC TOILET FACILITIES REQUIRED BY SEC.403.3
 OF THE FLORIDA PLUMBING CODE SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS OR CLOSETS PER SEC.403.3.1.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE GELATO MACHINE.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT A LAYOUT OF THE EXISTING FLOOR PLAN. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SHT. A-3 - THE PLANS REFERENCE THE 2007 FLORIDA
 BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC.
 THERE IS NO CHAPTER 11 IN THE 2010 FBC AND THE FIGURE
 NUMBERS LISTED IN THE DETAILS DO NOT EXIST IN THE 2010
 ACCESIBILITY CODE.
 5) SHT. A-5 - DETAIL #3 - PLUMBING FIXTURE MOUNTING
 HEIGHTS - THE WATER CLOSET SHALL BE 16"-18" TO THE
 CENTERLINE FROM ANY SIDE WALL OR PARTITION. FAC
 SEC.604.2.
 6) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC.107.3.5.1.3.
 7) AS DRAWN, THE SANITARY RISER HAS THE GREASE TRAP AND
 ALL THE OTHER GREASE WASTE FIXTURES ON A WET VENT WHICH
 DOES NOT COMPLY W/ 2010 FPC SEC.909.
 8) CLEANOUTS ARE REQUIRED ON ALL STACKS PER THE 2010
 FPC SEC.708.3.4.
 9) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS
 INDICATE 27 SEATS BUT THE PLAN ONLY SHOWS 8. SUBMIT A
 FULL SEATING PLAN FOR REVIEW. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 10) THE SINK AT THE VESTIBULE SHALL COMPLY W/ THE
 FLORIDA ACCESSIBILITY CODE SEC. 212 & 606.
 11) SUBMIT SPECIFICATIONS FOR THE GREASE TRAP.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 12) SHOW THE DIMENSIONS OF THE TOILET ROOM NEAR THE
 PREP AREA. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By aaponte Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-10-15 13:21:0410/15/14