Plan Review Details - Permit 14100329
Plan Review Stops For Permit 14100329
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-14 Cont ID  
Sent By rmcdouga Date 2014-10-14 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2014-10-14 Time 09:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By rmcdouga Date 2014-10-10 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2014-10-09 Time 18:48 Sent To  
Notes
2014-10-09 18:59:30PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE DESIGN PRESSURE OF -60 PSF FOR THE CERTAINTEED
 MODIFIED ROOFING SYSTEM SPECIFIED ON PAGE 15 OF NOA
 NO.14-0224.03 IS TOO LOW FOR ROOF ZONES 2 AND 3 IN
 EXPOSURE C WITH A 170 MPH VULT WIND SPEED. SUBMIT TWO
 SETS OF RAS 117 CALCULATIONS FOR ENHANCED FASTENING OF
 THE PERIMETER AND CORNER AREAS AS REQUIRED BY
 LIMITATION #7 ON PAGE 16 OF THE NOA. NOTE: CERTAINTEED
 HAS A PRODUCT APPROVAL FOR A MODIFIED ROOFING SYSTEM
 (FL 16709) THAT HAS THE ENHANCED FASTENING REQUIREMENTS
 INCLUDED.
  
 2) FBC - R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12
 UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT
 COMPLYING WITH ASTM D 226, TYPE I OR TYPE II, ASTM D
 4869, TYPE I OR TYPE II OR ASTM D 6757 IS REQUIRED IN
 ACCORDANCE WITH SECTION R905.2.7.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved