Plan Review Details - Permit 14100317
Plan Review Stops For Permit 14100317
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-15 Cont ID  
Sent By rmcdouga Date 2014-10-15 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2014-10-15 Time 18:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-09 Cont ID  
Sent By rmcdouga Date 2014-10-09 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2014-10-09 Time 15:35 Sent To  
Notes
2014-10-09 15:54:57PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE CONTRACT INDICATES THAT THE ROOF TILE WILL BE
 MECHANICALLY FASTENED. SPECIFY THE TYPE AND NUMBER OF
 FASTENERS THAT WILL BE USED TO INSTALL THE ROOF TILE.
 SUBMIT 2 COPIES OF THE PAGES WITH THE APPLICABLE TABLES
 FOR THE REQUIRED OVERTURN MOMENT FOR A 6/12 ROOF SLOPE
 IN EXPOSURE C AND THE MECHANICAL FASTENING ATTACHMENT
 RESISTANCE VALUES. FBC 107.2.1
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 REQUIRED BY DCA RULE 9N-3 FOR THE 3M AH160 FOAM
 ADHESIVE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-15 Cont ID  
Sent By rmcdouga Date 2014-10-15 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2014-10-15 Time 16:21 Sent To  
Notes
2014-10-15 16:22:01TO RM DESK
  