Plan Review Details - Permit 14100294
Plan Review Stops For Permit 14100294
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-03 Cont ID  
Sent By skennedy Date 2014-11-03 Time 13:17 Rev Time 0.00
Received By skennedy Date 2014-11-03 Time 13:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-09 Cont ID  
Sent By shill Date 2014-10-09 Time 09:12 Rev Time 0.00
Received By shill Date 2014-10-09 Time 09:12 Sent To  
Notes
2014-10-09 09:24:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE ARCHITECTURAL QUALITY PLANS, TO SCALE (1/8"
 MINIMUM), WHICH CLEARLY SHOW SCOPE, LOCATION, AND
 NATURE OF PROPOSED CONSTRUCTION FBC 107.2.
  
 2. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED NEW
 OPENING, FBC 107, FBC 16.
  
 3. PLANS ARE TO INCLUDE THE PRINTED NAME AND SIGNATURE
 OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN,
 FBC 107.
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-11-03 Cont ID  
Sent By skennedy Date 2014-11-03 Time 13:17 Rev Time 0.00
Received By skennedy Date 2014-11-03 Time 13:17 Sent To  
Notes
2014-11-03 13:21:421ST REVIEW: FBC 2010
  
 THE APPLICANT, HAS AGREED TO SUBMIT AN ELECTRICAL
 REVISION. THERE ARE NO DETAILS ON THE CURRENT PLAN FOR
 ELECTRICAL REVIEW OR INSPECTION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-29 Cont ID  
Sent By pleduc Date 2014-10-29 Time   Rev Time 0.00
Received By pleduc Date 2014-10-29 Time 12:43 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-10 Cont ID  
Sent By pleduc Date 2014-10-10 Time   Rev Time 0.00
Received By pleduc Date 2014-10-10 Time 11:17 Sent To PC
Notes
2014-10-10 11:30:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SUBMITTED PLANS WERE CONFUSING AND LIFE SAFETY
 REQUIREMENTS UNDETERMINABLE AS TO THE NATURE AND
 LOCATION OF THE PROPOSED PROJECT.
  
 A LIFE SAFETY PLAN WAS NOT NOT SUBMITTED, SHOWING THE
 LOCATION OF THE PROPOSED DOOR AND WALL CHANGES.
  
 THE NATURE OF THE REMODEL MAY AFFECT THE CODE
 REQUIREMENTS OF THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS.
  
 PLEASE PROVIDE GREATER DETAILED PLANS CLEARLY
 INDICATING EXISTING VS. PROPOSED WITH THE ABOVE NOTED
 INFORMATION AND INCLUDING BUILDING DEPARTMENT COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-03 Cont ID  
Sent By skennedy Date 2014-11-03 Time 13:17 Rev Time 0.00
Received By skennedy Date 2014-10-28 Time 11:54 Sent To  
Notes
2014-10-28 12:12:30EXPEDITED, SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-10 Cont ID  
Sent By pleduc Date 2014-10-10 Time 11:30 Rev Time 0.00
Received By pleduc Date 2014-10-08 Time 09:25 Sent To  
Notes
2014-10-09 09:25:18TO FIRE
  