Plan Review Details - Permit 14100293
Plan Review Stops For Permit 14100293 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2015-01-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-01-24 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-01-24 |
Time |
08:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-12-11 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-12-11 |
Time |
08:19 |
Sent To |
FIRE |
|
Notes |
2014-12-11 08:58:43 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) FBC 107.2.1 ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. | | | | 2) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | MEDIUM. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN | | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION | | PROGRAM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. SPECIFY THE SCALE OF THE DRAWINGS ON THE | | PLANS. | | | | 3) 602.2 TYPES I AND II. | | TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF | | CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN | | TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS | | PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE. | | SPECIFY THE MATERIALS USED TO CONSTRUCT THE SOFFIT, | | WHICH SHALL COMPLY WITH THIS SECTION. | | | | 4) 2) FBC 107.2.1 PROVIDE FRAMING DETAILS FOR THE NEW | | SOFFITS. SPECIFY THE FRAMING MATERIALS, THE SPACING AND | | THE NUMBER AND TYPE OF FASTENERS THAT WILL BE USED. | | | | 5) FBC 803 SPECIFY THE INTERIOR FINISHING MATERIAL AND | | THE THICKNESS OF THE MATERIAL THAT WILL BE USED TO | | COVER THE SOFFIT. (I.E. DRYWALL, WOOD PANELS, ETC.) | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-10-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-10-22 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-10-22 |
Time |
08:33 |
Sent To |
|
|
Notes |
2014-10-22 08:51:22 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | CODE AND RELEVANT LAWS, ORDINANCES, RULES | | AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. THE PLANS THAT WERE | | SUBMITTED ARE NOT CLEAR AS TO THE LOCATION OF | | THE SOFFIT AND THERE NO DETAILS TO SHOW HOW THEY WILL | | BE CONSTRUCTED. | | | | 2) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | MEDIUM. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN | | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION | | PROGRAM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF | | FLORIDA STATUTES. | | | | 3) 602.2 TYPES I AND II. | | TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF | | CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN | | TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS | | PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE. | | SPECIFY THE MATERIALS USED TO CONSTRUCT THE SOFFIT, | | WHICH SHALL COMPLY WITH THIS SECTION. | | | | 4) SHOW THAT THE NEW SOFFITS WILL NOT AFFECT THE FIRE | | SPRINKLER SYSTEM. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2015-02-19 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-19 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-19 |
Time |
11:10 |
Sent To |
|
|
Notes |
2015-02-19 11:53:02 | 02/19/2015 | | PROJECT: INTERIOR IMPROVEMENTS. #1116 | | PERMIT#: 14100293 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 4THELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION | | | | PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE | | FOLLOWING: | | | | 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED WITH | | THIS SUBMITTAL. | | | | 2) NEC 210.52, 2100.70 | | VERIFY OUTLETS, SWITCHES AND LIGHTING AS REQUIRED ARE | | EXISTING TO REMAIN OR INSTALLED TO BE CODE COMPLIANT. | | | | 3) FBC WPB AMENDMENTS. SECTION 109.3 | | VERIFY VALUATION INDICATED ON APPLICATION. FOR | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-02-18 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-01-21 |
Time |
07:55 |
Sent To |
FIRE |
|
Notes |
2015-01-21 08:55:27 | 1/21/2015 | | PROJECT: INTERIOR IMPROVEMENTS. #1116 | | PERMIT#: 14100293 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE | | FOLLOWING: | | | | 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED IN | | THIS SUBMITTAL. | | | | 2) VERIFY SMOKE DETECTORS AS REQUIRED. FBC-RESIDENTIAL | | 314 AND 315. | | | | 3) VERIFY REUIRED WORKING CLEARANCES. NEC 110.26 | | | | 4) BOND METAL FRAMING AS REQUIRED. FBC 2704 | | | | 5) PROVIDE A REVISED PANEL SCHEDULE TO INDICATE ANY NEW | | OR ALTERED CIRCUITS. NEC 408.4 | | | | 6) PROVIDE A FIXTURE SCHEDULE INDICATING COMPLIANCE | | WITH NEC 110.3 (B) | | | | 7) PROVIDE ADDITIONAL DETAIL ON THE METHODS AND | | MATERIALS PROPOSED FOR THE INSTALLATION OF THE CEILING | | FAN IN THE LIVING ROOM. | | | | 8) PROVIDE ARC FAULT PROTECTION ON ALL NEW ELECTRICAL | | CIRCUITRY. NEC 210.12 | | | | 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT NEC 406.11 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2014-12-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-12-10 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-12-10 |
Time |
11:43 |
Sent To |
B |
|
Notes |
2014-12-10 12:05:04 | 12/10/2014 | | PROJECT: 701 S. OLIVE STE 1116 | | PERMIT#: 14100293 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE PLANS MUST BE SIGNED BY THE PERSON RESPONSIBBLE | | FOR THE DESIGN. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. F.S. 471, FBC WPB AMENDMENTS. SECTION 107.2.1. | | | | 2) PROVIDE SUBSTANTIATING EVIDENCE OF THE STATED VALUE | | OF THE PROJECT. THE CLAIMED VALUATION OF BUILDING, | | ALTERATION, STRUCTURE, ELECTRICAL, MECHANICAL SYSTEMS | | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION. UNLESS | | THE APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, | | AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND | | VALUE) TO MEET THE APPROVAL OF THE BUILDING OFFICIAL | | THE APPLICATION WILL BE DENIED. FBC WPB AMENDMENTS. | | SECTION 109.3 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-10-14 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-10-14 |
Time |
08:07 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-10-14 |
Time |
08:07 |
Sent To |
B |
|
Notes |
2014-10-14 09:03:55 | SENT TO MISC. 2 | | | | | 2014-10-14 09:03:28 | 10/14/2014 | | PROJECT: 701 OLIVE | | PERMIT#: 14100293 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | BY THE BUILDING OFFICIAL. WPB AMENDMENTS TO FBC 107.2.1 | | | | 2) MINIMUM ELECTRICAL PLAN REVIEW CRITERIA SHALL | | INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: ELECTRIC | | SERVICE RISER WITH WIRE SIZES, CONDUIT AND GROUNDING | | DETAIL. COMPLETE LOAD CALCULATIONS, AND PANEL | | SCHEDULES. WPB AMENDMENTS TO FBC 107.3.5.3 RESIDENTIAL | | (ONE AND TWO-FAMILY). REVISE PLANS TO INCLUDE THE | | LOCATION OF ELECTRICAL PANELS AND THE PANEL SCHEDULES | | FOR THE AFFECTED PANELS. | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS | | TO FBC 107.2.1 | | | | 4) AN ELECTRICAL PERMIT IS REQUIRED FROM A QUALIFIED | | ELECTRICAL CONTRACTOR FOR THE ELECTRICAL SCOPE OF WORK. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-01-22 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-01-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-01-22 |
Time |
12:58 |
Sent To |
B |
|
Notes |
2015-01-22 13:06:06 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-12-11 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-12-11 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-12-11 |
Time |
15:45 |
Sent To |
PC |
|
Notes |
2014-12-11 15:51:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | THE ABOVE MUST BE REFRENCED ON THE SUBMITTAL. ANY | | SPRINKLER HEAD LOCATION ON THE SUBMITTED PLAN ARE ONLY | | CONCEPTUAL AND SHALL ONLY BE APPROVED AS CONCEPTUAL. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2015-02-19 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-19 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-17 |
Time |
17:40 |
Sent To |
|
|
Notes |
2015-02-18 17:40:46 | TO DHAYES DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-02-18 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-01-24 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-01-20 |
Time |
17:05 |
Sent To |
E |
|
Notes |
2015-01-23 15:19:11 | TO RM DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-12-11 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-12-08 |
Time |
10:56 |
Sent To |
|
|
Notes |
2014-12-09 10:56:47 | SENT TO D HAYES |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-10-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-10-22 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-10-08 |
Time |
17:20 |
Sent To |
|
|
Notes |
2014-10-08 17:20:53 | TO ELEC |
|
|
|