Plan Review Details - Permit 14100293
Plan Review Stops For Permit 14100293
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-24 Cont ID  
Sent By rmcdouga Date 2015-01-24 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2015-01-24 Time 08:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2014-12-11 Time 08:19 Sent To FIRE
Notes
2014-12-11 08:58:43PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. SPECIFY THE SCALE OF THE DRAWINGS ON THE
 PLANS.
  
 3) 602.2 TYPES I AND II.
 TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS
 PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE.
 SPECIFY THE MATERIALS USED TO CONSTRUCT THE SOFFIT,
 WHICH SHALL COMPLY WITH THIS SECTION.
  
 4) 2) FBC 107.2.1 PROVIDE FRAMING DETAILS FOR THE NEW
 SOFFITS. SPECIFY THE FRAMING MATERIALS, THE SPACING AND
 THE NUMBER AND TYPE OF FASTENERS THAT WILL BE USED.
  
 5) FBC 803 SPECIFY THE INTERIOR FINISHING MATERIAL AND
 THE THICKNESS OF THE MATERIAL THAT WILL BE USED TO
 COVER THE SOFFIT. (I.E. DRYWALL, WOOD PANELS, ETC.)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-22 Cont ID  
Sent By rmcdouga Date 2014-10-22 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2014-10-22 Time 08:33 Sent To  
Notes
2014-10-22 08:51:22PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. THE PLANS THAT WERE
 SUBMITTED ARE NOT CLEAR AS TO THE LOCATION OF
 THE SOFFIT AND THERE NO DETAILS TO SHOW HOW THEY WILL
 BE CONSTRUCTED.
  
 2) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  
 3) 602.2 TYPES I AND II.
 TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS
 PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE.
 SPECIFY THE MATERIALS USED TO CONSTRUCT THE SOFFIT,
 WHICH SHALL COMPLY WITH THIS SECTION.
  
 4) SHOW THAT THE NEW SOFFITS WILL NOT AFFECT THE FIRE
 SPRINKLER SYSTEM.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-02-19 Cont ID  
Sent By dhayes Date 2015-02-19 Time 11:53 Rev Time 0.00
Received By dhayes Date 2015-02-19 Time 11:10 Sent To  
Notes
2015-02-19 11:53:0202/19/2015
 PROJECT: INTERIOR IMPROVEMENTS. #1116
 PERMIT#: 14100293
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 4THELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE
 FOLLOWING:
  
 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED WITH
 THIS SUBMITTAL.
  
 2) NEC 210.52, 2100.70
 VERIFY OUTLETS, SWITCHES AND LIGHTING AS REQUIRED ARE
 EXISTING TO REMAIN OR INSTALLED TO BE CODE COMPLIANT.
  
 3) FBC WPB AMENDMENTS. SECTION 109.3
 VERIFY VALUATION INDICATED ON APPLICATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-01-21 Cont ID  
Sent By skennedy Date 2015-02-18 Time 17:40 Rev Time 0.00
Received By dhayes Date 2015-01-21 Time 07:55 Sent To FIRE
Notes
2015-01-21 08:55:271/21/2015
 PROJECT: INTERIOR IMPROVEMENTS. #1116
 PERMIT#: 14100293
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE
 FOLLOWING:
  
 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED IN
 THIS SUBMITTAL.
  
 2) VERIFY SMOKE DETECTORS AS REQUIRED. FBC-RESIDENTIAL
 314 AND 315.
  
 3) VERIFY REUIRED WORKING CLEARANCES. NEC 110.26
  
 4) BOND METAL FRAMING AS REQUIRED. FBC 2704
  
 5) PROVIDE A REVISED PANEL SCHEDULE TO INDICATE ANY NEW
 OR ALTERED CIRCUITS. NEC 408.4
  
 6) PROVIDE A FIXTURE SCHEDULE INDICATING COMPLIANCE
 WITH NEC 110.3 (B)
  
 7) PROVIDE ADDITIONAL DETAIL ON THE METHODS AND
 MATERIALS PROPOSED FOR THE INSTALLATION OF THE CEILING
 FAN IN THE LIVING ROOM.
  
 8) PROVIDE ARC FAULT PROTECTION ON ALL NEW ELECTRICAL
 CIRCUITRY. NEC 210.12
  
 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT NEC 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 11:48 Rev Time 0.00
Received By dhayes Date 2014-12-10 Time 11:43 Sent To B
Notes
2014-12-10 12:05:0412/10/2014
 PROJECT: 701 S. OLIVE STE 1116
 PERMIT#: 14100293
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PLANS MUST BE SIGNED BY THE PERSON RESPONSIBBLE
 FOR THE DESIGN. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. F.S. 471, FBC WPB AMENDMENTS. SECTION 107.2.1.
  
 2) PROVIDE SUBSTANTIATING EVIDENCE OF THE STATED VALUE
 OF THE PROJECT. THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, MECHANICAL SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION. UNLESS
 THE APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES,
 AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND
 VALUE) TO MEET THE APPROVAL OF THE BUILDING OFFICIAL
 THE APPLICATION WILL BE DENIED. FBC WPB AMENDMENTS.
 SECTION 109.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By dhayes Date 2014-10-14 Time 08:07 Rev Time 0.00
Received By dhayes Date 2014-10-14 Time 08:07 Sent To B
Notes
2014-10-14 09:03:55SENT TO MISC. 2
  
  
2014-10-14 09:03:2810/14/2014
 PROJECT: 701 OLIVE
 PERMIT#: 14100293
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. WPB AMENDMENTS TO FBC 107.2.1
  
 2) MINIMUM ELECTRICAL PLAN REVIEW CRITERIA SHALL
 INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: ELECTRIC
 SERVICE RISER WITH WIRE SIZES, CONDUIT AND GROUNDING
 DETAIL. COMPLETE LOAD CALCULATIONS, AND PANEL
 SCHEDULES. WPB AMENDMENTS TO FBC 107.3.5.3 RESIDENTIAL
 (ONE AND TWO-FAMILY). REVISE PLANS TO INCLUDE THE
 LOCATION OF ELECTRICAL PANELS AND THE PANEL SCHEDULES
 FOR THE AFFECTED PANELS.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 4) AN ELECTRICAL PERMIT IS REQUIRED FROM A QUALIFIED
 ELECTRICAL CONTRACTOR FOR THE ELECTRICAL SCOPE OF WORK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-22 Cont ID  
Sent By dhayes Date 2015-01-22 Time   Rev Time 0.00
Received By pleduc Date 2015-01-22 Time 12:58 Sent To B
Notes
2015-01-22 13:06:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By pleduc Date 2014-12-11 Time   Rev Time 0.00
Received By pleduc Date 2014-12-11 Time 15:45 Sent To PC
Notes
2014-12-11 15:51:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 THE ABOVE MUST BE REFRENCED ON THE SUBMITTAL. ANY
 SPRINKLER HEAD LOCATION ON THE SUBMITTED PLAN ARE ONLY
 CONCEPTUAL AND SHALL ONLY BE APPROVED AS CONCEPTUAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-02-19 Cont ID  
Sent By dhayes Date 2015-02-19 Time 11:53 Rev Time 0.00
Received By dhayes Date 2015-02-17 Time 17:40 Sent To  
Notes
2015-02-18 17:40:46TO DHAYES DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-18 Cont ID  
Sent By dhayes Date 2015-01-24 Time 17:39 Rev Time 0.00
Received By skennedy Date 2015-01-20 Time 17:05 Sent To E
Notes
2015-01-23 15:19:11TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time   Rev Time 0.00
Received By pleduc Date 2014-12-08 Time 10:56 Sent To  
Notes
2014-12-09 10:56:47SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-22 Cont ID  
Sent By rmcdouga Date 2014-10-22 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 17:20 Sent To  
Notes
2014-10-08 17:20:53TO ELEC