Plan Review Details - Permit 14100267
Plan Review Stops For Permit 14100267
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-10-13 Cont ID  
Sent By tklarge Date 2014-10-13 Time 05:54 Rev Time 0.00
Received By tklarge Date 2014-10-13 Time 05:53 Sent To  
Notes
2014-10-13 06:00:41****PROVISO****
 1) SEDIMENT TRAPS REQD. ON EQUIP./ APPLIANCE PER 2010
 FUEL GAS CODE SEC.408.4.
 2) REGULATORS TO BE VENTED OUTDOORS IF EQUIPPED W/VENT
 PER 2010 FGC SEC. 410.3.
 3) A LISTED SHUTOFF VALVE IS REQD. IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2010 FGC SEC.409.4
 4) PIPING IN SUBFLOOR SHALL COMPLY W/2010 FGC SEC. 404.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-13 Cont ID  
Sent By tklarge Date 2014-10-13 Time 05:53 Rev Time 0.00
Received By tklarge Date 2014-10-13 Time 05:53 Sent To  
Notes
2014-10-08 10:31:16ROUTED TO PLUMBING LESS THAN $5000