Plan Review Details - Permit 14100260
Plan Review Stops For Permit 14100260
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-10-15 Cont ID  
Sent By Mgonzale Date 2014-10-15 Time   Rev Time 1.00
Received By mgonzale Date 2014-10-15 Time   Sent To P
Notes
2014-10-15 15:03:15PROVISOS:
  
 #1 CALL 811 BEFORE DIGG, (FLORIDA ADMINISTRATIVE CODE
 CHAPTER 556, 553)
  
 #2 INSTALL ACCESSABLE CLEAN-OUT 5 FEET FROM GREASE
 SEPARATOR ON EFFLUENT LINE.
 (CLEAN-OUT WILL BE UTILIZED TO SAMPLE THE GREASE
 CONTENT UNDER THE CITY'S FOG PROGRAM
 AND TO COMPLY WITH TESTING AS REQUIRED BY STATE OF
 FLORIDA DEPARTMENT OF HEALTH)
 (FLORIDA ADMINISTRATIVE CODE CHAPTER 64E-6)
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-17 Cont ID  
Sent By tklarge Date 2014-10-17 Time 11:38 Rev Time 0.00
Received By tklarge Date 2014-10-08 Time 09:33 Sent To  
Notes
2014-10-08 09:33:26ENG
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-01 Cont ID  
Sent By tklarge Date 2014-12-01 Time 06:15 Rev Time 0.00
Received By tklarge Date 2014-12-01 Time 06:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-17 Cont ID  
Sent By tklarge Date 2014-10-17 Time 11:37 Rev Time 0.00
Received By tklarge Date 2014-10-17 Time 11:37 Sent To  
Notes
2014-10-17 10:37:04WPB AMEND. TO 2010 FBC SEC.107.2.1.4. -
 1) PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE.
 THESE PLANS WOULD ALSO BE REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD PER FL.
 ADMIN. CODE RULE 61G15-23.002.
 2) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 STATES "GREASE TRAP A - FOR BAR" YET THE SUBMITTED SITE
 PLANS SHOWS THE LOCATION FOR GREASE TRAP "A" AND ALSO
 FOR GREASE TRAPS "A"."B", & "C". . WHICH IS IT, A OR B
 OR C ? CLARIFY. CLEARLY WRITE THE FULL DESCRIPTION OF
 THE WORK ON THE PERMIT APPLICATION.
 3) SUBMIT TWO COPIES OF ALL PLANS/ DOCUMENTS FOR THIS
 PERMIT PER WPB AMEND. TO 2010 FBC SEC.107.1. COMPILE
 ALL DOCUMENTS INTO 2 SETS STAPLED TOGETHER.
 4) TWO DIFFERENT DESIGNS FOR THE 750 GAL. CONCRETE
 VAULT TANKS HAS BEEN SUBMITTED. YOU MUST IDENTIFY WHICH
 DESIGN WILL BE USED.THE DESIGN FROM US CONCRETE
 PRODUCTS DOES NOT COMPLY WITH SEC. 1003.5.2 & 1003.5.3
 OF THE 2010 FPC.
 5) YOU HAVE SUBMITTED GREASE INTERCEPTOR SIZING
 CALCULATIONS FROM THE 2010 FPC FOR CONCRETE VAULT TYPE
 GREASE INTERCEPTOR AND ALSO FOR A SCHIER INTERCEPTOR.
 WHICH ONE ARE YOU USING?
 6) YOU HAVE SUBMITTED GREASE INTERCEPTOR SIZING
 CALCULATIONS FOR RESTAURANTS AND ALSO FOR OTHER
 ESTABLISHMENTS WITH COMMERCIAL KITCHENS. WHICH ONE IS
 IT?
 I HAVE NO IDEA WHAT DOCUMENTS YOU ARE ATTEMPTING TO USE
 FOR THIS PERMIT SINCE THIS SUBMITTAL IS VAGUE AND
 CONFUSING WITH THE CONFLICTING DOCUMENTS.WHEN
 RESUBMITTING, ENSURE THAT ALL APPLICABLE DOCUMENTS ARE
 ARRANGED IN TWO SETS WITH ALL INFORMATION CLEAR ENOUGH
 FOR A COMPLETE, COMPREHENSIVE PLAN REVIEW.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  