Plan Review Details - Permit 14100228
Plan Review Stops For Permit 14100228
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By jgomez Date 2014-10-10 Time 13:59 Rev Time 0.00
Received By jgomez Date 2014-10-10 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-09 Cont ID  
Sent By jgomez Date 2014-10-09 Time 11:32 Rev Time 0.00
Received By jgomez Date 2014-10-09 Time 11:32 Sent To  
Notes
2014-10-09 12:03:42RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- INSTALLATION SCHEDULE SUBMITTED INDICATES THAT
 SHUTTERS GLASS SEPARATION IS NOT APPLICABLE (NA).
 PRODUCT APPROVAL FL11964-R1 SUBMITTED REQUIRES GLASS
 SEPARATION. REVISE INSTALLATION SCHEDULE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- INSTALLATION SCHEDULE SUBMITTED INDICATES THAT THE
 BUILDING IS LOCATED IN EXPOSURE "D". THE DESIGN
 PRESSURES SUBMITTED DON'T CORRESPOND TO A BUILDING WITH
 A 20'-0" MEAN ROOF HEIGHT IN EXPOSURE "D". TABLE
 R301.2(3) OF 2010 FBC-RESIDENTIAL. REVISE CALCULATIONS
 OR PROVIDE 2 COPIES OF SIGNED AND SEALED CALCULATIONS.
 SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC.
 ***NOTE: CONNECTION TYPE "ALT. 14". AFTER DESIGN
 PRESSURES ARE REVISED, VERIFY THAT PROPOSED CONNECTION
 TYPE MEETS THE MAX. DESIGN PRESSURES AND MAX. PANEL
 SPAN FOR ALL OPENINGS. FOR EXAMPLE: CHECK OPENING #9.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-10-07 Cont ID  
Sent By fmittner Date 2014-10-07 Time 15:48 Rev Time 0.00
Received By fmittner Date 2014-10-07 Time 15:48 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-10 Cont ID  
Sent By jgomez Date 2014-10-10 Time 13:59 Rev Time 0.00
Received By jgomez Date 2014-10-10 Time 13:58 Sent To  
Notes
2014-10-10 13:58:58RECEIVED E-MAIL FROM TONY BERRIOS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-09 Cont ID  
Sent By jgomez Date 2014-10-09 Time 11:32 Rev Time 0.00
Received By jgomez Date 2014-10-09 Time 11:32 Sent To  
Notes
***NONE***